Front-panel Indicator Error Displays

 

 

 

 

 

 

 

 

Indicators

Possible cause

Remedy

 

 

 

 

 

 

 

Board

CPU Unit

 

 

 

 

 

 

 

 

 

 

 

RDY

 

ERR/ALM

 

 

 

 

 

 

 

 

 

 

 

Lit

 

Not lit

The Serial Communications Board has

---

 

 

 

 

 

started normally.

 

 

 

 

 

 

 

 

 

Not lit

 

Lit

The Serial Communications Board is faulty

If the ERR and ALM indicators light when

 

 

 

 

(hardware self-diagnostic function).

the Serial Communications Board is

 

 

 

 

Board watchdog timer error: IR 20000 will

mounted to another CPU Unit, replace the

 

 

 

 

turn ON.

Serial Communications Board.

 

 

 

 

A bus error has occurred.

Firmly secure the Serial Communications

 

 

 

 

An initialization recognition error has

Board to the CPU Unit.

 

 

 

 

 

 

 

 

 

 

occurred (the Serial Communications

 

 

 

 

 

 

Board is not correctly recognized by the

 

 

 

 

 

 

CPU Unit).

 

 

 

 

 

 

 

 

 

Not lit

 

Not lit

The CPU Unit is not receiving normal

Check the power supply voltage and

 

 

 

 

power supply.

supply the correct electric power to the

 

 

 

 

 

Unit.

 

 

 

 

The Serial Communications Board is not

Firmly secure the Serial Communications

 

 

 

 

correctly secured to the CPU Unit.

Board.

 

 

 

 

The Serial Communications Board is faulty.

If all the indicators are not lit when the

 

 

 

 

 

 

 

 

 

 

Serial Communications Board is mounted

 

 

 

 

An error (such as a CPU Unit WDT error)

to another CPU Unit, replace the Serial

 

 

 

 

Communications Board.

 

 

 

 

has occurred in the CPU Unit.

 

 

 

 

Eliminate the cause of the error. If the error

 

 

 

 

 

 

 

 

 

 

persists, replace the CPU Unit.

 

 

 

 

 

 

 

Lit

 

Lit

The Serial Communications Board is faulty.

If all the indicators are lit when the Serial

 

 

 

 

 

Communications Board is mounted in

 

 

 

 

 

another CPU Unit, replace the Serial

 

 

 

 

A bus error has occurred.

Communications Board.

 

 

 

 

Check the operating environment and

 

 

 

 

 

 

 

 

 

 

eliminate the cause of the error.

 

 

 

 

 

Firmly secure the Serial Communications

 

 

 

 

 

Board.

 

 

 

 

 

 

 

Lit

 

Flashing

An error has occurred in the CPU Unit.

Eliminate the cause of the error. If the error

 

 

 

 

(Cause of error eliminated, but error not

persists, replace the CPU Unit.

 

 

 

 

cleared.)

 

 

 

 

 

 

 

 

 

Flashing

 

Flashing

A protocol data write error has occurred or

If the indicator status remains the same

 

 

 

 

protocol data has been destroyed.

when the protocol data is retransmitted,

 

 

 

 

(Protocol data error: IR 20002)

replace the Serial Communications Board.

 

 

 

 

Connector may have become loose or the

Transfer protocol data to the Serial

 

 

 

 

PC power supply may have turned OFF

Communications Board.

 

 

 

 

while transferring protocol data.

Conduct a loopback test. If an error

 

 

 

 

 

 

 

 

 

There is no protocol data.

occurs, replace the Serial Communications

 

 

 

 

 

Board.

 

 

 

 

The communications circuit is faulty.

Correct the protocol data and transfer it to

 

 

 

 

(Board Identification Error Flag: IR 20001)

the Serial Communications Board.

 

 

 

 

A protocol data syntax error has occurred.

Try executing a normal sequence for the

 

 

 

 

(Protocol macro error code: 4)

serial port where the error is occurring or

 

 

 

 

 

switch the CPU Unit to PROGRAM mode

 

 

 

 

 

and remove the cause of the error.

 

 

 

 

A PC Setup error has occurred.

Correct the PC Setup settings.

 

 

 

 

 

 

 

 

 

 

(PC Setup Error Flags: IR 20013 to

 

 

 

 

 

 

IR 20015)

 

 

120