E5jK Digital Controller Read Protocol

Appendix C

 

 

 

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

 

Number of receive data words

 

 

storage words

 

 

 

 

 

+1

 

Cooling coefficient

 

 

 

 

 

 

 

 

 

 

 

+2

 

Dead band

 

 

 

 

 

 

 

 

+3

 

Manual reset value

 

 

+4

 

Hysteresis (heating)

 

 

+5

 

Hysteresis (cooling)

 

 

 

 

 

 

 

+6

 

Control period (heating)

 

 

 

 

 

 

 

 

 

 

 

+7

 

Control period (cooling)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

~

~

 

 

 

 

 

 

 

+50

 

Cooling coefficient

 

 

 

 

 

 

 

 

+51

 

Dead band

 

 

 

 

 

 

 

+52

 

Manual reset value

 

 

+53

 

Hysteresis (heating)

 

 

+54

 

Hysteresis (cooling)

 

 

 

 

 

 

 

+55

 

Control period (heating)

 

 

 

 

 

 

 

+56

 

Control period (cooling)

 

 

 

 

 

 

1st unit

8th unit (max.)

Offset

Contents (data format)

Data

 

 

 

+0

Number of receive data words

Number of units  7 + 1

 

(4 digits BCD)

 

 

 

 

+1

1st unit

0001 to 9999

 

Cooling coefficient (4 digits BCD)

 

 

 

 

+2

1st unit

A999 to 9999

 

Dead band (4 digits BCD)

F indicates a negative value and A

 

 

indicates –1.

 

 

 

+3

1st unit

0000 to 1000

 

Manual reset value

 

 

(4 digits BCD)

 

 

 

 

+4

1st unit

0001 to 9999

 

Hysteresis (heating)

 

 

(4 digits BCD)

 

 

 

 

+5

1st unit

0001 to 9999

 

Hysteresis (cooling) (4 digits BCD)

 

 

 

 

+6

1st unit

0001 to 0099

 

Control period (heating)

 

 

(4 digits BCD)

 

 

 

 

+7

1st unit

0001 to 0099

 

Control period (cooling)

 

 

(4 digits BCD)

 

 

 

 

 

D

 

 

D

 

 

D

 

 

 

 

+56

8th unit

0001 to 0099

(max.)

Control period (cooling)

 

 

(4 digits BCD)

 

 

 

 

166