E5jK Digital Controller Write Protocol

Appendix D

 

 

 

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Write Input Digital Filter (Sequence No. 062)

Writes the input digital filter.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

 

+2

Input digital filter

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0003 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

 

 

 

+2

Input digital filter (4 digits BCD)

0000 to 9999

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Write Alarm Hysteresis (Sequence No. 063)

Writes the alarm 1 hysteresis and alarm 2 hysteresis.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

 

+2

Alarm 1 hysteresis

 

 

 

 

+3

Alarm 2 hysteresis

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0004 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

 

 

 

+2

Alarm 1 hysteresis

0001 to 9999

 

(4 digits BCD)

 

 

 

 

+3

Alarm 2 hysteresis

0001 to 9999

 

(4 digits BCD)

 

 

 

 

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Write Input Shift Value (Sequence No. 064)

Writes the input shift upper limit and input shift lower limit.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

 

+2

Input shift upper limit

 

 

 

 

+3

Input shift lower limit

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0004 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

 

 

 

+2

Input shift upper limit (4 digits BCD)

0000 to 9999

 

 

 

+3

Input shift lower limit (4 digits BCD)

0000 to 9999