Omron CQM1H-SCB41 operation manual 123

Models: CQM1H-SCB41

1 421
Download 421 pages 6 Kb
Page 131
Image 131

Board Replacement

 

 

 

Section 9-2

 

 

 

 

 

 

 

Serial com-

Indicator

Status

I/O memory

Cause

Remedy

munications

status

information,

 

 

 

 

mode

 

etc.

 

 

 

 

 

 

 

 

 

 

Serial commu-

The COMMj

There is a

The error code in

The communica-

Review the PC Setup, the

nications mode

indicators are

transmission

IR 20100 to

tions conditions

host’s settings, and pro-

is set to Host

flashing, but

error.

IR 20103 for port 1

and baud rate do

gram (such as commands

Link. (Contin-

the response

 

or IR 20108 to

not match the set-

and frame format) based

ued)

has not been

 

IR 20111 for port 2

tings at the host.

on the response and the

 

returned to the

 

is 1 (parity error), 2

 

error code.

 

host.

 

(framing error), or 3

 

 

 

 

 

There is noise in-

Use shielded twisted-pair

 

 

 

(overrun error).

 

 

 

terference.

cables.

 

 

 

 

 

 

 

 

 

Lay power lines separate-

 

 

 

 

 

ly using ducts.

 

 

 

 

 

Review the installation

 

 

 

 

 

environment to reduce

 

 

 

 

 

noise interference.

 

 

 

 

 

 

 

The COMMj

There is no

IR 20100 to

A command was

Review the host’s settings

 

indicators are

transmission

IR 20103 or

sent from the host

and program (such as pa-

 

flashing, and

error.

IR 20108 to

with incorrect pa-

rameter settings) based

 

an error re-

 

IR 20111 are

rameters.

on the response contents.

 

sponse has re-

 

0 Hex.

 

 

 

 

turned to the

 

 

 

 

 

 

There is a

The error code in

The communica-

Review the PC Setup, the

 

host.

 

transmission

IR 20100 to

tions conditions

host’s settings and pro-

 

 

 

 

error.

IR 20103 for port 1

and baud rate do

gram (such as commands

 

 

 

or IR 20108 to

not match the set-

and frame format) based

 

 

 

IR 20111 for port 2

tings at the host.

on the response, and the

 

 

 

is 1 (parity error), 2

 

error code in IR 20100 to

 

 

 

(framing error), or 3

 

IR 20103 or IR 20108 to

 

 

 

(overrun error).

 

IR 20111.

 

 

 

 

 

 

 

The COMMj

There is an

The error code in

The baud rate is

Review the PC Setup.

 

indicators are

intermittent

IR 20100 to

outside the allow-

Review the host’s settings

 

flashing, but

transmission

IR 20103 for port 1

able range, and the

 

and program (such as

 

sometimes

error.

or IR 20108 to

stop bits do not

 

baud rate and frame for-

 

there is no re-

 

IR 20111 for port 2

match, causing the

 

 

mat).

 

sponse re-

 

is 1 (parity error), 2

bits to be out of

 

 

 

 

 

turned.

 

(framing error), or 3

alignment.

 

 

 

 

 

(overrun error).

 

 

 

 

 

 

 

 

 

 

 

 

Terminating resist-

Cables are incor-

Check the wiring.

 

 

 

ance switch

rectly connected.

 

 

 

 

 

(TERM) status

The RS-422A/485

Turn ON the terminating

 

 

 

 

 

 

 

 

port 2-wire/4-wire

 

 

 

 

resistance of the Serial

 

 

 

 

terminating resist-

 

 

 

 

Communications Board

 

 

 

 

ance setting is in-

 

 

 

 

and the last node by us-

 

 

 

 

correct.

 

 

 

 

ing the terminating resist-

 

 

 

 

 

 

 

 

 

Adapters such as

ance switch. Turn OFF

 

 

 

 

the NT-AL001-E

the terminating resistance

 

 

 

 

are incorrectly

of other nodes.

 

 

 

 

wired or the termi-

 

 

 

 

 

 

nating resistance is

 

 

 

 

 

 

incorrectly set.

 

 

 

 

 

 

 

 

 

 

 

The error code in

Transmission er-

Use shielded twisted-pair

 

 

 

IR 20100 to

rors are occurring

cables.

 

 

 

IR 20103 for port 1

that are caused by

Lay power lines separate-

 

 

 

or IR 20108 to

noise interference.

 

 

 

ly using ducts.

 

 

 

IR 20111 for port 2

 

 

 

 

 

Review the installation

 

 

 

is not 0.

 

 

 

 

 

 

environment to reduce

 

 

 

 

 

noise interference.

123

Page 131
Image 131
Omron CQM1H-SCB41 operation manual 123