Application Procedure

Section 4-5

 

A response will not be received with some errors, regardless of the command.

These errors are listed in the following table.

 

 

Error

PC operation

 

 

Parity, overrun, or framing error during

The Communications Error Flag will be turned ON, an error code will

command reception. (Same even for

be registered, and receptions will be reset. (The error will be cleared

commands address to other Units.)

automatically if communications restart normally.)

 

The Communications Error Flags are as follows:

 

Peripheral port: AR 0812

 

Built-in RS-232C port: AR 0804

 

Serial Communications Board port 1: IR 20104,

 

Serial Communications Board port 2: IR 20112

 

 

A command is received that does not have the

The command will be discarded.

@ character at the beginning of the first frame.

 

 

 

 

Incorrect node number (Not a local unit or over

The command will be discarded.

31)

 

 

 

 

The data in an intermediate or final frame for

An FCS error will occur.

multiframe writes is 2 bytes or longer.

 

 

4-5

Changes from Previous Products

 

 

 

There are differences between Host Link Systems created using the CQM1H-

 

 

series Serial Communications Boards in comparison to Host Link Systems

 

 

created with Host Link Units and CPU Units in other PC product series. These

 

 

differences are described in this section.

4-5-1

RS-232C Ports

 

 

 

 

 

Take the following differences into consideration when changing from an exist-

 

 

ing Host Link System to one using an RS-232C port on a CQM1H-series CPU

 

 

Unit or Serial Communications Boards.

 

 

 

 

Previous

Model number

Changes required for CQM1H-series product

products

 

 

 

 

 

Wiring

 

Other

 

 

 

 

 

 

 

 

 

C-series Host

3G2A5-LK201-E

The connector has been

 

The following changes are necessary for

Link Units

C500-LK203

changed from a 25-pin to a

 

systems that sync with ST1, ST2, and RT.

 

 

9-pin connector.

 

Synchronized transfers will no longer be

 

 

3G2A6-LK201-E

 

 

 

 

 

 

 

The CQM1H-series

 

possible.

 

 

 

 

 

 

 

products do not support the

 

Half-duplex transmissions will be possible

 

 

 

ST1, ST2, and RT signals

 

 

 

 

 

with the CQM1H-series product, but the host

 

 

 

and wiring them is not

 

 

 

 

 

computer’s communications program,

 

 

 

required.

 

 

 

 

 

hardware, or both will need to be altered.

 

 

 

 

 

 

 

 

 

 

The following changes are necessary for

 

 

 

 

 

systems that did not sync with ST1, ST2,

 

 

 

 

 

and RT.

 

 

 

 

 

It may be possible to use the host computer

 

 

 

 

 

programs without alteration as long as the

 

 

 

 

 

same communications settings (e.g., baud

 

 

 

 

 

rate) are used. It may be necessary, however,

 

 

 

 

 

to change programs to allow for different text

 

 

 

 

 

lengths in frames or different CQM1H

 

 

 

 

 

command specifications. (See note.)

 

 

C200H-LK201

The connector has been

 

It may be possible to use the host computer

 

 

 

changed from a 25-pin to a

programs without alteration as long as the

 

 

 

9-pin connector.

 

same communications settings (e.g., baud

 

 

 

 

 

rate) are used. It may be necessary, however,

 

 

 

 

 

to change programs to allow for different text

 

 

 

 

 

lengths in frames or different CQM1H

 

 

 

 

 

command specifications. (See note.)

53

Page 65
Image 65