CompoWay/F Master Protocol

Appendix B

 

 

 

RS-422 4-wire Connections

RS-422 connections can be one-to-one, or one-to-N when a 3G2A9-AL001 Link Adapter is used. A maximum of 32 Serial Communications Boards can be connected in one-to-N systems.

The total cable length can be 500 m max.

Use shielded, twisted-pair cable.

Be sure to turn ON the terminating resistance switches at the device at each end of the transmission line.

Serial

 

 

 

 

Communications

Intelligent Signal

 

Board

RS-422

 

 

Processor

 

 

 

SN751177N or equivalent

 

Abbreviation

 

 

 

 

 

Terminal

 

 

 

 

 

 

Pin

Ab-

220 block switch

 

Shell

No.

brevi-

 

 

ation

 

 

6

 

 

 

8

1

2

*1: Set the 2-/4-wire switch to the 4-wire setting.

*2: Turn ON the terminat- ing resistance switch.

220

Shield

The terminator (220 ) is set with the terminal block switch.

RS-485 2-wire Connections

RS-485 connections can be one-to-one or one-to-N. A maximum of 32 Serial Communications Boards can be connected in one-to-N systems.

The total cable length can be 500 m max.

Use shielded, twisted-pair cable.

Be sure to turn ON the terminator switches only in the devices at each end of the transmission line.

Serial

Communications

Board RS-485

Abbreviation

Shell 1 2

Shield

*1: Set the 2-/4-wire switch to the 2-wire setting.

*2: Turn ON the terminat- ing resistance switch.

Intelligent Signal Processor

SN751177N or equivalent

Turn OFF all terminal block

 

switches except at the end-station.

 

 

 

Terminal

 

Termi- Ab-

220

block

 

switch

 

nal brevi-

 

 

 

 

ation

+

Intelligent Signal

Processor end-station

Termi-

Ab-

Terminal

220 block switch ON

nal

brevi-

 

ation

 

 

+

 

 

 

Terminal block switch ON at the end station.

Shield

Note SYSMAC BUS Wired Remote I/O devices cannot be connected.

152