Application ProcedureSection 4-5

4-5-2 RS-422A/485 Ports

Take the following differences into consideration when changing from an exist- ing Host Link System to one using an RS-422A/485 port on a CQM1H-series Serial Communications Board.

Previous

Model number

Changes required for CQM1H-series product

products

 

 

 

 

Wiring

Other

 

 

 

 

 

 

C-series Host

3G2A5-LK201-E

Wiring pins have been

It may be possible to use the host computer

Link Units

C200H-LK202

changed as shown below.

programs without alteration as long as the

 

SDA: Pin 9 to pin 1

same communications settings (e.g., baud

 

3G2A6-LK202-E

 

rate) are used. It may be necessary,

 

SDB: Pin 5 to pin 2

 

 

however, to change programs to allow for

 

 

RDA: Pin 6 to pin 6

 

 

different text lengths in frames or different

 

 

RDB: Pin 1 to pin 8

 

 

CQM1H command specifications. (See

 

 

SG: Pin 3 to

 

 

note.)

 

 

Not connected

 

 

 

 

 

FG: Pin 7 to pin

 

 

 

Connector hood

 

 

 

 

 

C200HX/HG/HE

C200HW-COMjj-E

No changes have been

It may be possible to use the host computer

Communications

 

made in wiring.

programs without alteration as long as the

Board

 

 

same communications settings (e.g., baud

 

 

 

rate) are used. It may be necessary,

 

 

 

however, to change programs to allow for

 

 

 

different CQM1H command specifications.

 

 

 

 

CS1-series CPU

CS1G/H-CPUjj

No changes have been

It may be possible to use the host computer

Unit

 

made in wiring.

programs without alteration as long as the

 

 

 

same communications settings (e.g., baud

CS1-series Serial

CS1W-SCB21/41

 

 

rate) are used. It may be necessary,

Communications

CS1W-SCU21

 

 

however, to change programs to allow for

Board or Unit

 

 

 

 

different CQM1H command specifications.

 

 

 

 

 

 

 

CVM1 or

CVM1/CV-CPUjj

No changes have been

It may be possible to use the host computer

CV-series CPU

 

made in wiring.

programs without alteration as long as the

Units

 

 

same communications settings (e.g., baud

 

 

 

rate) are used. It may be necessary,

CVM1 or

CV500-LK201

 

 

however, to change programs to allow for

CV-series Host

 

 

 

 

different CQM1H command specifications.

Link Unit

 

 

 

 

 

Note The number of words that can be read and written per frame (i.e., the text lengths) when using C-mode Host Link commands is different for C-series Host Link Units and CQM1H-series Serial Communications Boards. A host computer program previously used for C-series Host Link Units may not function correctly if used for CQM1H-series PCs. Check the host computer program before using it and make any corrections required to handle different frame text lengths.

55

Page 67
Image 67
Omron CQM1H-SCB41 operation manual 2 RS-422A/485 Ports