Hayes Modem AT Command Protocol

Appendix N

 

 

 

MD144FB5V (OMRON)

The following command is set in the words specified by the second operand of PMCR.

ATE0V0X4\V2\N3%C0*C0\Q0&M0&D0%B9600S26=10

0023 0041

A T E 0 V 0 X 4 \ V 2 \ N 3 % C 0 * C 0 \ Q 0 & M 0 & D 0 % B 9 6 0 0 S 2 6 = 1 0

Character string length of modem initialization command (bytes)

Code length of PMCR when it is used (words)

ME1414VBII/ME1414BII (OMRON)

The following command is set in the words specified by the second operand of PMCR.

AT\J1B8E0V0S0=1X4\V2\N3&M0%C0&D0&E0\X1S26=10

0024

0044

A T \ J 1 B 8 E 0 V 0 S 0 = 1 X 4 \ V 2 \ N 3 & M 0 % C 0 & D 0 & E 0 \ X 1 S 2 6 = 1 0

Character string length of modem initialization command (bytes)

Code length of PMCR when it is used (words)

Note Turn ON DIP switch SW3 on in the rear of the Modem.

Dialling

To dial telephone numbers for the OMRON Modems using sequences No. 561, 571, 581, set the dialling command and telephone number in the words specified by the second operand of PMCR. However, for other Modems, make the following settings for the Data Send/Receive sequence.

This is an example of telephone number settings for the above mentioned 3 OMRON Modems.

Operand and Word Settings of PMCR

Operand 1

 

MD24FB10V

#x561 (x: Communications port)

 

 

 

 

MD144FB5V

#x571

 

 

 

 

ME1414VB2/B2

#x581

 

 

 

 

 

 

Operand 2

 

First address C of send data (dialling operation)

 

 

 

 

 

 

 

Operand 3

 

None

 

 

 

 

 

C+0

Number of words from address set for operand 2 to end of

4 digits BCD

 

data

 

 

 

 

 

 

C+1

Number of bytes of send data (dialling operation)

4 digits BCD

 

 

 

C+2

Send data (dialling operation)

ASCII

:

(Fill data to left for odd numbers of bytes)

 

C+n

 

 

 

 

 

 

 

 

 

 

 

406

Page 409
Image 409
Omron CQM1H-SCB41 operation manual Dialling, Operand and Word Settings of Pmcr