Appendix G

E5jJ Temperature Controller Protocol

The E5jJ Temperature Controller Protocol performs various settings and controls in remote mode for the Tem- perature Controller connected to the Serial Communications Board via RS-232C or RS-422A/485 cable.

Note Negative values cannot be written. All values must be set as unsigned BCD.

Structure of the Protocol

The following table shows the structure of the E5jJ Temperature Controller Protocol.

Sequence

Communications

Function

Ladder interface

No.

sequence name

 

 

 

 

Send word

Receive word

 

 

 

 

 

 

allocation

allocation

200

Select remote mode

Switches the Controller to remote mode.

Yes

No

 

 

 

 

 

201

Select local mode

Switches the Controller to local mode.

Yes

No

 

 

 

 

 

202

Select backup mode

Switches from set point write mode to back-

Yes

No

 

 

up mode.

 

 

 

 

 

 

 

203

Select RAM write

Switches from set point write mode to RAM

Yes

No

 

mode

write mode.

 

 

 

 

 

 

 

204

Save set point

Saves the set point.

Yes

No

 

 

 

 

 

205

Write parameters 1

Writes the set point, alarm value 1, alarm

Yes

No

 

 

value 2, and heater burnout alarm value.

 

 

 

 

 

 

 

206

Write parameters 2

Writes the proportional band, integral time,

Yes

No

 

 

and derivative time.

 

 

 

 

 

 

 

207

Write input shift value

Writes the input shift value.

Yes

No

 

 

 

 

 

208

Read parameters 1

Reads the set point, alarm value 1, alarm

Yes

Yes

 

 

value 2, and heater burnout alarm value.

 

 

209

Read parameters 2

Reads the proportional band, integral time,

Yes

Yes

 

 

and derivative time.

 

 

210

Read input shift value

Reads the input shift value and writes it in

Yes

Yes

 

 

IOM.

 

 

 

 

 

 

 

211

Read output value

Reads the output value and stores it in IOM.

Yes

Yes

 

 

 

 

 

212

Read process value

Reads the process value and stores it in

Yes

Yes

 

 

IOM.

 

 

 

 

 

 

 

213

Read set point limit

Reads the set point limits and stores them in

Yes

Yes

 

 

IOM.

 

 

 

 

 

 

 

214

Read heater current

Reads the heater current and stores it in

Yes

Yes

 

 

IOM.

 

 

 

 

 

 

 

215

Read initial status

Reads the initial status and stores it in IOM.

Yes

Yes

 

 

 

 

 

216

General-purpose write

Writes the specified parameter by setting a

Yes

No

 

 

header code.

 

 

217

General-purpose read

Reads the specified parameter by setting a

Yes

Yes

 

 

header code.

 

 

Note Ladder Interface Settings

 

YES:

User settings are required for the 2nd or 3rd operands of PMCR.

NO:

Send word allocation:

Set the constant 0000 for the 2nd operand (S).

 

Receive word allocation:

Set a dummy word (e.g., DM 0000) address for the 3rd operand (D).

229

Page 234
Image 234
Omron CQM1H-SCB41 operation manual Appendix G, E5jJ Temperature Controller Protocol