E5jK Digital Controller Read Protocol

 

Appendix C

 

 

 

 

 

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

 

 

 

 

 

+0

Number of receive data words

Number of units  6 + 1

 

 

 

 

(4 digits BCD)

 

 

 

 

 

 

 

 

 

+1

1st unit

A999 to 9999

 

 

 

 

Alarm value 1 (4 digits BCD)

F indicates a negative value and A

 

 

 

 

 

indicates –1.

 

 

 

 

 

 

 

 

+2

1st unit

A999 to 9999

 

 

 

 

Alarm value 2 (4 digits BCD)

F indicates a negative value and A

 

 

 

 

 

indicates –1.

 

 

 

 

 

 

 

 

+3

1st unit

A999 to 9999

 

 

 

 

Alarm value 3 (4 digits BCD)

F indicates a negative value and A

 

 

 

 

 

indicates –1.

 

 

 

 

 

 

 

 

+4

1st unit

0001 to 9999

 

 

 

 

Proportional band

 

 

 

 

 

(4 digits BCD)

 

 

 

 

 

 

 

 

 

+5

1st unit

0000 to 3999

 

 

 

 

Integral time (4 digits BCD)

 

 

 

 

 

 

 

 

 

+6

1st unit

0000 to 3999

 

 

 

 

Derivative time (4 digits BCD)

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

D

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

+48

8th unit

0000 to 3999

 

 

 

(max.)

Derivative time (4 digits BCD)

 

 

 

 

 

 

 

 

Read Level 1 Parameters 2 (Sequence No. 020)

Reads parameters in level 1 (cooling coefficient, dead band, manual reset value, hysteresis (heating), hysteresis (cooling), control period (heating), and control period (cooling)) from multiple units and stores the results in the specified words.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

 

Number of send data words

 

send data

 

 

 

 

 

+1

 

Number of units

 

 

 

 

 

 

 

 

 

 

 

+2

 

(Undefined)

Unit No.

 

 

 

 

 

 

 

 

 

 

 

+3

 

(Undefined)

Unit No.

 

 

 

 

 

 

 

 

~

 

~

+9

(Undefined)

Unit No.

(max.)

Offset

Contents (data format)

Data

+0

Number of send data words

Number of units + 2

 

(4 digits BCD)

 

+1

Number of units (4 digits BCD)

0001 to 0008

+2 to 9 Unit No. (2 digits BCD)

00 to 31

165