Using Protocol Macros

 

Section 5-1

 

 

 

 

 

 

Protocol Macro Function Specifications

 

 

 

 

 

 

 

 

 

Item

 

 

Description

 

 

 

 

 

 

Number of protocols (20 max.)

Can be created and registered with the Protocol Support Tool

 

 

 

(CX-Protocol).

 

 

 

Number of sequences (1,000 max.)

 

 

 

 

 

 

 

 

 

 

 

 

 

Per protocol

Number of

60 max.

 

 

 

 

sequences

 

 

 

 

 

Number of

300 max.

 

 

 

 

messages

 

 

 

 

 

Number of

100 max.

 

 

 

 

reception

 

 

 

 

 

matrixes

 

 

 

 

 

 

 

 

 

Protocol data memory

 

Flash memory in the Serial Communications Board (Retained even

 

 

 

when the power supply to the PC is turned OFF.)

 

Sequence execution condition

Using the CPU Unit’s PMCR(––) instruction (specifying the sequence

 

 

 

number)

 

 

 

Communications mode

 

Half-duplex

 

 

 

 

 

 

 

 

Synchronous mode

 

Start-stop synchronization (asynchronous mode)

 

 

 

 

 

 

Baud rate (see note)

 

RS-232C port and RS-422A/485 ports:

 

 

 

1,200/2,400/4,800/9,600/19,200 bps

 

 

 

Default setting: 9,600 bps

 

 

 

 

 

Communications distance (see note)

RS-232C port: 15 m max.

 

 

 

RS-442A/485 port: 500 m max. (The total combined cable length is

 

 

 

500 m max. T-branch lines must be a maximum of 10 m long.)

 

 

 

 

 

Connection configuration

RS-232C port: 1:1 (1:N (N = 32 Units max.) is possible using a

 

 

 

Converting Link Adapter.)

 

 

 

RS-422A/485 port: 1:N (N = 32 Units max.)

 

Number of connected Units

32 Units max. (unit numbers 0 to 31; unit number 0 is set for 1:1

 

 

 

connection)

 

 

 

 

 

 

 

 

Maximum number of

Operand setting

127 words

Including the word that specifies the number of

 

data exchange words

 

 

words (1 word)

 

between PC and

 

 

 

 

 

Link word setting

128 words

O1, O2, I1, and I2: 128 words total

 

protocol macro

 

 

 

 

 

 

Direct setting

128 words

Maximum number of words per data attribute

 