Basic Operating Procedure

Section 1-4

 

 

 

 

 

 

1-3

Specifications

 

 

1-3-1

Serial Communications Board

 

 

 

 

 

Device name

 

Serial Communications Board

 

 

 

 

 

Model number

 

CQM1H-SCB41

 

 

 

 

 

Classification

 

CQM1H-series Inner Board

 

 

 

 

 

Supporting CPU Units

 

CQM1H-CPU51/61

 

 

 

 

 

Number of mountable Boards/PC and

One Board per PC maximum, must be in Inner Board slot 1

 

mounting location

 

 

 

 

Serial communications

Port 1

RS-232C

 

ports

 

 

 

 

 

 

Port 2

RS-422A/485

 

 

 

 

 

 

 

 

Protocols

Port 1

Host Link, protocol macro, no-protocol, 1:1 Data Link, 1:N-mode NT Link

 

 

 

 

or 1:1-mode NT Link can be selected for each port.

 

 

 

Port 2

 

 

 

 

 

 

 

 

 

 

Software interface with CPU Unit

IR 200 to IR 207 (words for Inner Board slot 1)

 

 

 

 

 

PC Setup settings

 

DM 6550 to DM 6559 (in read-only DM area in CPU Unit)

 

 

 

 

Set from Programming Device

 

 

 

 

Current consumption (see note)

200 mA max. at 5 V DC

 

 

 

 

 

Dimensions

 

25 110 107 (mm) (W H D)

 

 

 

 

 

 

Weight

 

 

90 g max.

 

 

 

 

 

Standard accessories

 

Socket: XM2SA-0901 (OMRON) (two included)

 

 

 

 

Hood: XM2SA-0911-E (OMRON) (two included, ESD compatible)

Note The current consumption is for one Serial Communications Board. Power is sup- plied from the CQM1H

When an NT-AL001-E Link Adapter is connected to the Serial Communications Board, power is supplied to the Link Adapter from the Board. A current consump- tion of 150 mA must be added for each Link Adapter that is connected. In the above specifications, “x” indicates that 150 mA must be added for each port to which an NT-AL001-E Link Adapter is connected to provide the required 5-V power supply.

1-3-2 General Specifications

Conform to SYSMAC CQM1H-series CPU Unit specifications.

1-4 Basic Operating Procedure

An overview of the basic operating procedure is provided here. Details are pro- vided in sections 4 to 8 of this manual according to the serial communications mode.

1, 2, 3... 1. Turn OFF the power supply to the PC.

2.Mount the Board.

3.Connect the Board and the external device(s).

4.Turn ON the power supply to the PC.

5.Set the PC Setup settings from a Programming Device (e.g., Programming Console or CX-Protocol).

6.Execute communications.

Use the control bits, flags, and words allocated in the IR area in the ladder program to control communications.

8

Page 20
Image 20
Omron CQM1H-SCB41 operation manual Basic Operating Procedure, Serial Communications Board, General Specifications