E5ZE Temperature Controller Write Protocol

Appendix F

 

 

 

 

 

 

 

 

 

Offset

Contents (data format)

Data

 

 

 

 

 

 

 

 

+0

Number of send data words

0018 (fixed)

 

 

 

 

(4 digits BCD)

 

 

 

 

 

 

 

 

 

+1

Unit No. (2 digits Hex)

00 to 0F

 

 

 

 

 

 

 

 

+2

Channel 0

0000 to 1000

 

 

 

 

Output value (4 digits BCD)

 

 

 

 

 

 

 

 

 

+3

Channel 0

0000 to 1000

 

 

 

 

Cooling output value

 

 

 

 

 

(4 digits BCD)

 

 

 

 

 

 

 

 

 

+4

Channel 1

0000 to 1000

 

 

 

 

Output value (4 digits BCD)

 

 

 

 

 

 

 

 

 

+5

Channel 1

0000 to 1000

 

 

 

 

Cooling output value

 

 

 

 

 

(4 digits BCD)

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

D

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

+16

Channel 7

0000 to 1000

 

 

 

 

Output value (4 digits BCD)

 

 

 

 

 

 

 

 

 

+17

Channel 7

0000 to 1000

 

 

 

 

Cooling output value

 

 

 

 

 

(4 digits BCD)

 

 

Receive Data Word Allocation (3rd Operand of PMCR)

None.

Write Output Value Limit (Sequence No. 166)

Writes the output value limits that restrict the values of the control outputs.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

 

Number of send data words

 

 

send data

 

 

 

 

 

 

+1

 

(Undefined)

Unit No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+2

 

Output value lower limit

 

 

 

 

 

 

 

+3

 

Output value upper limit

 

 

 

 

 

 

 

 

+4

 

Cooling output value lower limit

 

 

 

 

 

 

+5

 

Cooling output value upper limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

~

 

~

 

 

 

 

 

 

 

+30

 

Output value lower limit

 

 

 

+31

 

Output value upper limit

 

 

+32

 

Cooling output value lower limit

 

 

 

 

 

 

 

 

+33

 

Cooling output value upper limit

 

 

 

 

 

 

 

Channel 0

Channel 7

221

Page 227
Image 227
Omron CQM1H-SCB41 operation manual Write Output Value Limit Sequence No