E5jJ Temperature Controller Protocol

Appendix G

 

 

 

Read Parameters 1 (Sequence No. 208)

Reads the set points, alarm values 1, alarm values 2, and heater burnout alarm values for multiple units and stores the results in the specified words.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

 

Number of send data words

 

send data

 

 

 

 

 

+1

 

Number of units

 

 

 

 

 

 

 

 

 

 

 

+2

 

(Undefined)

Unit No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

~

 

~

+26

(Undefined)

Unit No.

(max.)

Offset

Contents (data format)

Data

+0

Number of send data words

Number of units + 2

 

(4 digits BCD)

 

+1

Number of units (4 digits BCD)

0001 to 0025

+2

1st unit

00 to 31

 

Unit No. (2 digits BCD)

 

+3

2nd unit

00 to 31

 

Unit No. (2 digits BCD)

 

 

D

 

 

D

 

 

D

 

+26

25th unit

00 to 31

(max.)

Unit No. (2 digits BCD)

 

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

 

Number of receive data words

 

 

storage words

 

 

 

 

 

+1

 

Set point

 

 

 

 

 

 

 

 

 

 

+2

 

Alarm value 1

 

 

 

 

 

 

 

+3

 

Alarm value 2

 

 

 

 

 

 

 

+4

 

Heater burnout alarm value

 

 

 

 

 

 

 

 

 

~

~

 

 

 

 

 

 

 

+97

 

Set point

 

 

 

 

 

 

 

 

+98

 

Alarm value 1

 

 

 

 

 

 

 

+99

 

Alarm value 2

 

 

 

 

 

 

 

+100

 

Heater burnout alarm value

 

1st unit

25th unit (max.)

236