E5ZE Temperature Controller Read Protocol

Appendix E

 

 

 

Read Hysteresis (Sequence No. 109)

Reads the hysteresis and stores the results in the specified words.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

Offset

Contents (data format)

 

Data

 

 

 

 

+0

Number of send data words

0002

(fixed)

 

(4 digits BCD)

 

 

 

 

 

 

+1

Unit No. (2 digits Hex)

00 to

0F

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

 

Number of receive data words

 

 

 

storage words

 

 

 

 

 

 

+1

 

Hysteresis

 

 

 

 

 

 

 

 

 

 

 

 

+2

 

Cooling hysteresis

 

 

 

 

 

 

 

 

 

+3

 

Hysteresis

 

 

 

 

 

 

 

+4

 

Cooling hysteresis

 

 

 

 

 

 

 

 

 

 

 

~

~

 

 

 

 

 

 

 

 

+15

 

Hysteresis

 

 

 

 

 

 

 

 

 

 

+16

 

Cooling hysteresis

 

 

Channel 0

Channel 1

Channel 7

Offset

Contents (data format)

Data

 

 

 

+0

Number of receive data words

0017

 

(4 digits BCD)

 

 

 

 

+1

Channel 0

0000 to 0999

 

Hysteresis (4 digits BCD)

 

 

 

 

+2

Channel 0

0000 to 0999

 

Cooling hysteresis (4 digits BCD)

 

 

 

 

 

D

 

 

D

 

 

D

 

 

 

 

+15

Channel 7

0000 to 0999

 

Hysteresis (4 digits BCD)

 

 

 

 

+16

Channel 7

0000 to 0999

 

Cooling hysteresis (4 digits BCD)

 

 

 

 

Read Operation Status (Sequence No. 110)

Reads the operation status of the E5ZE and stores the results in the specified words.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

Offset

Contents (data format)

 

Data

 

 

 

 

+0

Number of send data words

0002

(fixed)

 

(4 digits BCD)

 

 

 

 

 

 

+1

Unit No. (2 digits Hex)

00 to

0F

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

 

Number of receive data words

 

 

storage words

 

 

 

 

 

+1

 

Status code

 

Channel 0

 

 

 

 

 

 

 

 

 

 

+2

 

Status code

 

Channel 1

 

 

 

 

 

 

 

 

 

 

 

 

 

~

 

~

 

+8

 

Status code

 

Channel 7

 

 

 

 

 

 