E5ZE Temperature Controller Read Protocol

Appendix E

 

 

 

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

Number of receive data words

storage words

 

 

+1

Output value lower limit

 

 

 

 

 

+2

Output value upper limit

 

 

 

 

+3

Cooling control output value lower limit

 

+4

Cooling control output value upper limit

~

~

+29

 

Output value lower limit

 

 

+30

 

 

 

 

 

Output value upper limit

 

 

 

 

 

 

 

+31

 

Cooling control output value lower limit

 

 

 

 

 

 

 

+32

 

Cooling control output value upper limit

 

 

 

 

 

 

 

Channel 0

Channel 7

Offset

Contents (data format)

Data

 

 

 

+0

Number of receive data words

0033

 

(4 digits BCD)

 

 

 

 

+1

Channel 0

0000 to 1000

 

Output value lower limit

 

 

(4 digits BCD)

 

 

 

 

+2

Channel 0

0000 to 1000

 

Output value upper limit

 

 

(4 digits BCD)

 

 

 

 

+3

Channel 0

0000 to 1000

 

Cooling control output value upper

 

 

limit (4 digits BCD)

 

 

 

 

+4

Channel 0

0000 to 1000

 

Cooling control output value upper

 

 

limit (4 digits BCD)

 

 

 

 

 

D

 

 

D

 

 

D

 

 

 

 

+31

Channel 7

0000 to 1000

 

Cooling control output value upper

 

 

limit (4 digits BCD)

 

 

 

 

+32

Channel 7

0000 to 1000

 

Cooling control output value upper

 

 

limit (4 digits BCD)

 

 

 

 

Read Output Value Change Rate Limit (Sequence No. 118)

Reads the output value change rate limits and stores the results in the specified words.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

Offset

Contents (data format)

 

Data

 

 

 

 

+0

Number of send data words

0002

(fixed)

 

(4 digits BCD)

 

 

 

 

 

 

+1

Unit No. (2 digits Hex)

00 to

0F

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

 

storage words

+1

 

 

 

 

 

 

+2

 

 

 

 

 

 

 

 

~

 

+8

 

 

 

 

 

 

 

Number of receive data words

Output value change rate limit

Output value change rate limit

Output value change rate limit

Channel 0 Channel 1

~

Channel 7

204

Page 210
Image 210
Omron CQM1H-SCB41 operation manual Read Output Value Change Rate Limit Sequence No