E5jK Digital Controller Read Protocol

Appendix C

 

 

 

Send Data Word Allocation (2nd Operand of PMCR)

First word of send +0

data

+1

Number of send data words

(Undefined)

Unit No.

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0002 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

Number of receive data words

storage words

 

 

+1

Alarm value 1

 

 

 

 

 

+2

Alarm value 2

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of receive data words

0003

 

(4 digits BCD)

 

 

 

 

+1

Alarm value 1 (4 digits BCD)

A999 to 9999

 

 

F indicates a negative value and A

 

 

indicates –1.

 

 

 

+2

Alarm value 2 (4 digits BCD)

A999 to 9999

 

 

F indicates a negative value and A

 

 

indicates –1.

 

 

 

Read Proportional Band, Integral Time, and Derivative Time (Sequence No. 005)

Reads the proportional band, integral time, and derivative time and stores the results in the specified words.

Send Data Word Allocation (2nd Operand of PMCR)

First word of send +0

data

+1

Number of send data words

(Undefined)

Unit No.

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

0002 (fixed)

 

(4 digits BCD)

 

 

 

 

+1

Unit No. (2 digits BCD)

00 to 31

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

Number of receive data words

storage words

 

 

+1

Proportional band

 

 

 

 

 

+2

Integral time

 

 

 

 

+3

Derivative time

 

 

 

Offset

Contents (data format)

Data

 

 

 

+0

Number of receive data words

0004

 

(4 digits BCD)

 

 

 

 

+1

Proportional band (4 digits BCD)

0000 to 9999

 

 

 

+2

Integral time (4 digits BCD)

0000 to 3999

 

 

 

+3

Derivative time (4 digits BCD)

0000 to 3999

Read Cooling Coefficient (Sequence No. 006)

Reads the cooling coefficient and stores the results in the specified words.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

send data

+1

 

Number of send data words

(Undefined)

Unit No.

 

 

157

Page 164
Image 164