E5jK Digital Controller Write Protocol

Appendix D

 

 

 

Write Level 2 Parameters 2 (Sequence No. 069)

Writes parameters in level 2 (input digital filter, alarm 1 hysteresis, alarm 2 hysteresis, alarm 3 hysteresis, input shift upper limit, and input shift lower limit) to multiple units.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

 

 

send data

+1

 

 

 

 

 

 

+2

 

 

 

+3

 

 

 

+4

 

 

 

+5

 

 

 

+6

 

 

 

+7

 

 

 

+8

 

 

 

~

 

 

 

 

 

+51

 

 

 

+52

 

 

 

+53

 

 

 

+54

 

 

 

+55

 

 

 

+56

 

 

 

+57

 

 

 

 

 

 

Number of send data words

Number of units

(Undefined)

Unit No.

 

 

Input digital filter

alarm 1 hysteresis

alarm 2 hysteresis

alarm 3 hysteresis

Input shift upper limit

Input shift lower limit

~

(Undefined)

 

Unit No.

Input digital filter

 

alarm 1 hysteresis

alarm 2 hysteresis

alarm 3 hysteresis

Input shift upper limit

Input shift lower limit

1st unit

8th unit (max.)

Offset

Contents (data format)

Data

 

 

 

+0

Number of send data words

Number of units  7 + 2

 

(4 digits BCD)

 

 

 

 

+1

Number of units (4 digits BCD)

0001 to 0008

 

 

 

+2

1st unit

00 to 31

 

Unit No. (2 digits BCD)

 

 

 

 

+3

1st unit

0000 to 9999

 

Input digital filter (4 digits BCD)

 

 

 

 

+4

1st unit

0001 to 9999

 

Alarm 1 hysteresis

 

 

(4 digits BCD)

 

 

 

 

+5

1st unit

0001 to 9999

 

Alarm 2 hysteresis

 

 

(4 digits BCD)

 

 

 

 

+6

1st unit

0001 to 0099

 

Alarm 3 hysteresis

 

 

(4 digits BCD)

 

 

 

 

+7

1st unit

000 to 9999

 

Input shift upper limit (4 digits BCD)

 

 

 

 

+8

1st unit

000 to 9999

 

Input shift lower limit (4 digits BCD)

 

 

 

 

 

D

 

 

D

 

 

D

 

 

 

 

+57

8th unit

000 to 9999

(max.)

Input shift lower limit (4 digits BCD)

 

 

 

 

Receive Data Word Allocation (3rd Operand of PMCR)

None.

181

Page 188
Image 188
Omron CQM1H-SCB41 operation manual Write Level 2 Parameters 2 Sequence No