E5ZE Temperature Controller Read Protocol

Appendix E

 

 

 

Read Present Set Point (Sequence No. 116)

Reads the present set points during ramp operation and stores the results in the specified word.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

Offset

Contents (data format)

 

Data

 

 

 

 

+0

Number of send data words

0002

(fixed)

 

(4 digits BCD)

 

 

 

 

 

 

+1

Unit No. (2 digits Hex)

00 to

0F

Receive Data Word Allocation (3rd Operand of PMCR)

Receive data

+0

 

storage words

+1

 

 

 

 

 

 

+2

 

 

 

 

 

 

 

 

~

 

 

+15

 

 

+16

 

 

 

 

 

 

Number of receive data words

Present set point (rightmost 4 digits)

Present set point (leftmost 1 digit)

~

Present set point (rightmost 4 digits)

Present set point (leftmost 1 digit)

Channel 0

Channel 7

Offset

Contents (data format)

Data

 

 

 

+0

Number of receive data words

0017

 

(4 digits BCD)

 

 

 

 

+1

Channel 0

Varies according to the temperature sensor

 

Present set point (rightmost 4 digits)

type. Refer to the manual for the E5ZE.

 

(4 digits BCD)

F indicates a negative value.

 

 

+2

Channel 0

 

 

Present set point (leftmost 1 digit)

 

 

(1 digit BCD)

 

 

 

 

 

D

 

 

D

 

 

D

 

 

 

 

+15

Channel 7

Varies according to the temperature sensor

 

Present set point (rightmost 4 digits)

type. Refer to the manual for the E5ZE.

 

(4 digits BCD)

F indicates a negative value.

 

 

+16

Channel 7

 

 

Present set point (leftmost 1 digit)

 

 

(1 digit BCD)

 

Read Output Value Limit (Sequence No. 117)

Reads the output value limits and stores the results in the specified words.

Send Data Word Allocation (2nd Operand of PMCR)

First word of

+0

Number of send data words

send data

 

 

 

+1

(Undefined)

Unit No.

 

 

 

 

 

Offset

Contents (data format)

 

Data

 

 

 

 

+0

Number of send data words

0002

(fixed)

 

(4 digits BCD)

 

 

 

 

 

 

+1

Unit No. (2 digits Hex)

00 to

0F