Installation

 

Section 2-3

 

 

 

 

 

 

 

Pin

 

Function

Factory

 

 

 

 

setting

 

 

 

 

 

1

Not used. Always set this pin to ON.

ON

 

 

 

 

 

2

Built-in terminating resistance setting

ON

 

 

ON:

Connects terminating resistance.

 

 

 

 

OFF:

Disconnects terminating resistance.

 

 

 

 

 

 

 

3

2/4-wire setting

OFF

 

 

2-wire: Set both pins to ON.

 

 

 

4

OFF

 

4-wire: Set both pins to OFF.

 

 

 

 

 

 

 

 

 

5

Transmission mode (See note)

ON

 

 

Constant transmission: Set both pins to OFF.

 

 

 

 

Transmission performed when CTS signal in RS-232C

 

 

 

6

interface is at high level: Set pin 5 to OFF and pin 6 to ON.

OFF

 

 

Transmission performed when CTS signal in RS-232C

 

 

 

 

interface is at low level: Set pin 5 to ON and pin 6 to OFF.

 

 

Note When connecting to a CQM1H-series CPU Unit, turn OFF pin 5 and turn ON pin 6.

2-3-5 Recommended RS-232C Wiring Examples

It is recommended that RS-232C cables be connected as described below, es- pecially when the Serial Communications Board is used in an environment where it is likely to be subject to electrical noise.

1, 2, 3... 1. Always use shielded twisted-pair cables as communications cables.

Model

Manufacturer

 

 

UL2464 AWG28x5P IFS-RVV-SB (UL-approved)

Fujikura Ltd.

AWG28x5P IFVV-SB (not UL-approved)

 

 

 

UL2464-SB (MA) 5Px28AWG (7/0.127) (UL-approved)

Hitachi Cable,

CO-MA-VV-SB 5Px28AWG (7/0.127) (not UL-approved)

Ltd.

2.Combine signal wires and SG (signal ground) wires in a twisted-pair cable. At the same time, bundle the SG wires to the connectors on the Serial Com- munications Board and the remote device.

3.Connect the shield of the communications cable to the Hood (FG) terminal of the RS-232C connector on the Serial Communications Board. At the

same time, ground the ground (GR) terminal of the Power Supply Unit to 100 or less.

4.A connection example is shown below.

Example: Twisted-pair Cable Connecting SD-SG, RD-SG, RTS-SG, and CTS-SG Terminals

Serial

Communications

Board

Pin

Signal

 

 

SD

 

 

RD

 

 

RTS

 

 

CTS

 

 

SG

 

Hood

FG

Shield

 

FG

Remote device

Signal

RD

SD

CTS

RTS

SG

FG

Actual Wiring Example

SG signal wires

Twist the braided shield to make it thinner and connect to Pin No. 1 (FG). Cover this section with heat-shrink tube to avoid contact with other sections.

Bundle the SG wires.

Aluminum foil

XM2S-0911-E

20

Page 32
Image 32