PC Setup SettingsSection 3-3

3-3

Control Bits, Flags, and Status Information

 

 

 

 

Control bits, flags, and status information for the Serial Communications Board

 

 

 

is available in the Inner Board Slot 1 area. The addresses in this area are as fol-

 

 

 

lows:

 

 

 

 

 

 

Inner Board Slot 1 Area: IR 200 to IR 207

 

 

 

 

The following bits are often used in Protocol Macro Mode. Refer to 5-6 Control

 

 

 

Bits, Flags, and Status Information for details.

 

 

 

 

 

 

 

 

Word

Bits

 

 

Function

 

Communications

 

 

 

 

 

 

modes

 

 

 

 

 

 

IR 200

00

Serial Communications Board Hardware Error Flag

 

All modes

 

 

 

 

 

 

 

01

Board Identification Error Flag (hardware error)

 

 

 

 

 

 

 

 

 

 

02

Protocol Data Error Flag

 

 

Protocol macro

 

 

 

 

 

 

 

 

03 to 10

Not used.

 

 

 

 

 

 

 

 

 

 

11

Port 2 Protocol Macro Execution Error Flag

 

 

 

 

 

 

 

 

 

12

Port 1 Protocol Macro Execution Error Flag

 

 

 

 

 

 

 

 

 

 

13

Port 2 PC Setup Error Flag

 

 

All modes

 

 

 

 

 

 

 

 

14

Port 1 PC Setup Error Flag

 

 

 

 

 

 

 

 

 

 

 

15

PC Setup Error Flag

 

 

 

 

 

 

 

 

 

 

IR 201

00 to 03

Port 1

Error Code

 

 

All modes

 

 

 

0: Normal operation

1: Parity error

2: Framing error

 

 

 

 

3: Overrun error

4: FCS error

5: Timeout error

 

 

 

 

6: Checksum error

7: Command error

 

 

 

 

 

 

 

 

 

04

 

Communications Error Flag

 

 

 

 

 

 

 

 

 

05

 

Transmission Enabled Flag

 

Host Link or

 

 

 

Turns ON when transmission is enabled, OFF when transmissions

No-protocol

 

 

 

 

 

 

 

are being processed for TXD(––).

 

 

 

 

 

Use with flag as an execution condition for TXD(––) when using

 

 

 

 

No-protocol or Host Link Mode.

 

 

 

 

 

 

 

 

 

06

 

Reception Completed Flag

 

 

 

 

 

Turns ON when receptions for RXD(––) have been completed in

 

 

 

 

No-protocol Mode.

 

 

 

 

 

 

 

 

 

 

07

 

Reception Overflow Flag

 

 

 

 

 

In No-protocol Mode, turns ON when the next data is received before

 

 

 

 

previous data is read out using RXD(––).

 

 

 

 

 

 

 

 

 

 

 

Sequence Abort Completion Flag

 

Protocol macro

 

 

 

 

 

 

 

 

08 to 11

Port 2

Error Code

 

 

All modes

 

 

 

0: Normal operation

1: Parity error

2: Framing error

 

 

 

 

3: Overrun error

4: FCS error

5: Timeout error

 

 

 

 

6: Checksum error

7: Command error

 

 

 

12

 

Communications Error Flag

 

 

 

 

 

 

 

 

 

13

 

Transmission Enabled Flag

 

Host Link or

 

 

 

Turns ON when transmission is enabled, OFF when transmissions

No-protocol

 

 

 

 

 

 

 

are being processed for TXD(––).

 

 

 

 

 

Use with flag as an execution condition for TXD(––) when using

 

 

 

 

No-protocol or Host Link Mode.

 

 

 

14

 

Reception Completed Flag

 

 

 

 

 

Turns ON when receptions for RXD(––) have been completed in

 

 

 

 

No-protocol Mode.

 

 

 

 

 

 

 

 

 

 

15

 

Reception Overflow Flag

 

 

 

 

 

In No-protocol Mode, turns ON when the next data is received before

 

 

 

 

previous data is read out using RXD(––).

 

 

 

 

 

Sequence Abort Completion Flag

 

Protocol macro

30

Page 42
Image 42
Omron CQM1H-SCB41 operation manual Control Bits, Flags, and Status Information, Word Bits Function Communications Modes