Wiring

 

 

 

 

Section 2-1

 

CPU Unit Indicators

A Serial Communications Board is mounted as an Inner Board in the CPU Unit

 

 

and thus affects the CPU Unit ERR/ALM indicator.

 

 

 

 

 

 

 

 

 

Indicator

Color

Status

 

Meaning

 

 

 

 

 

 

 

 

 

ERR/ALM

Red

Lit

Fatal error

If a fatal error occurs, the CPU

 

 

 

 

 

 

Unit will stop operation in

 

 

 

 

 

 

either RUN or MONITOR

 

 

 

 

 

 

mode.

 

 

 

 

Flashing

Non-fatal

If a non-fatal error occurs, the

 

 

 

 

 

error

CPU Unit will continue

 

 

 

 

 

 

operation in either RUN or

 

 

 

 

 

 

MONITOR mode.

 

 

 

 

 

 

 

 

 

 

 

Not lit

Normal

The CPU Unit is operating

 

 

 

 

 

operation

normally. This indicator will

 

 

 

 

 

 

also not be lit when a

 

 

 

 

 

 

watchdog timer error occurs.

If an error in the Inner Board is the cause of the error indicated on the ERR/ALM indicator, the Inner Board Error Flag (SR 25415) will turn ON and information on the error will be stored in AR 0400 to AR 0407. Refer to Section 9 Troubleshoot- ing and Maintenance for details.

2-1-2 RS-232C Port

Protocol

Host Link

No-protocol

Protocol macros

1:1 Data Links

1:N NT Links

1:1 NT Links

 

 

 

 

 

 

 

Communica-

Half-duplex

 

 

 

tions method

 

 

 

 

 

 

 

 

 

 

 

Synchroniza-

Start-stop synchronization (asynchronous)

 

 

 

tion

 

 

 

 

 

 

 

 

 

 

 

Baud rate

1,200/2,400/4,800/9,600/ 19,200 bps

19,200 bps

38,400 bps

19,200 bps

 

 

 

 

 

 

 

Connections

1:1

 

 

1:1

1:1

1:1

 

(1:N possible using Converting Link Adapters)

 

(1:N possible us-

 

 

 

 

 

 

ing Link Adapters)

 

Transmission

15 m max. (See note)

 

 

 

distance

 

 

 

 

 

 

 

 

 

 

 

Interface

Complies with EIA RS-232C

 

 

 

Note The maximum cable length for RS-232C is 15 m. The RS-232C standard, how- ever, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support.

Connector Pin Layout

Pin No.

Abbreviation

Signal name

I/O

 

 

 

 

1 (See note 1)

FG

Shield

---

 

 

 

 

2

SD

Send data

Output

 

 

 

 

3

RD

Receive data

Input

 

 

 

 

4

RTS (RS)

Request to send

Output

 

 

 

 

5

CTS (CS)

Clear to send

Input

 

 

 

 

6 (See note 2)

5V

Power supply

---

 

 

 

 

7

DSR (DR)

Data set ready

Input

 

 

 

 

8

DTR (ER)

Data terminal ready

Output

 

 

(See note 4)

 

 

 

 

 

9

SG

Signal ground

---

 

 

 

 

Shell (See note 1)

FG

Shield

---

Note 1. Pin No. 1 and the shell are connected to the ground terminal (GR) of the Power Supply Unit inside the Serial Communications Board. Therefore, the cable shield can be grounded by grounding GR of the Power Supply Unit.

2.Pin 6 (5 V) is required when the NT-AL001-E Link Adapter is connected. For details on connection methods, refer to 2-3 Wiring.

11

Page 23
Image 23