Wiring

Section 2-3

Note The Hood (FG) is internally connected to the ground terminal (GR) on the Power Supply Unit. Therefore, FG is grounded by grounding the ground terminal (GR) on the Power Supply Unit. Although there is conductivity between the Hood (FG) and pin 1 (FG), connect the Hood (FG) to the shield because the Hood (FG) has smaller contact resistance with the shield than pin 1 (FG), and thus provides bet- ter noise resistance.

Serial Communications Board

Power Supply Unit

 

Hood and GR are

 

internally connected.

Ground to 100 or less

Grounding the GR terminal

 

grounds the Hood (FG).

2-3-6 Recommended RS-422A/485 Wiring Examples

Recommended RS-422A/485 Cable

We recommend the following wiring methods to ensure quality transmissions for

RS-422A/485 communications.

1, 2, 3... 1. Always use shielded twisted-pair cables for the communications cables.

Model

Manufacturer

 

 

CO-HC-ESV-3Px7/0.2

Hirakawa Hewtech Corp.

2.Connect the shield of the communications cable to the Hood (FG) of the

RS-422A/485 connector on the Serial Communications Board. At the same time, ground the ground (GR) terminal of the Power Supply Unit to 100 or less.

Note Always ground the shield only at the Board end. Grounding both ends of the shield may damage the device due to the potential difference between the ground terminals.

Connection examples are shown below.

2-Wire Connections

Serial Communications

Remote device

Board

 

Pin Signal

Signal

Hood

Shield

 

21

Page 33
Image 33
Omron CQM1H-SCB41 operation manual Recommended RS-422A/485 Wiring Examples, Recommended RS-422A/485 Cable, Wire Connections