Kenmore 153.339473, 153.339572, 153.33955, 153.339372 Chimney Connection, Vertical Exhaust Gas Vent

Page 20

The vent connector must be accessible for cleaning, inspection, and replacement.

Vent connectors cannot pass through any ceiling, floor, firewall, or fire partition.

It is recommended (but not mandatory) that a minimum 12 inches of vertical vent pipe be installed on the draft hood prior to any elbow in the vent system.

IMPORTANT: Existing vent systems must be inspected for obstructions, corrosion, and proper installation.

Chimney Connection

IMPORTANT: Before connecting a vent to a chimney, make sure the chimney passageway is clear and free of obstructions. The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces. Also consult local and state codes for proper chimney sizing and application or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition.

The connector must be installed above the extreme bottom

 

of the chimney to prevent potentially blocking the flue

 

gases.

The connector must be firmly attached and sealed to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

separation, and maintain clearances to combustible materials (Figures 20 and 21).

IMPORTANT: This gas vent must be terminated in a vertical position to facilitate the removal of the burnt gases.

An unused chimney flue or masonry enclosure may be used as a passageway for the installation of a gas vent (Figure 21).

Common (combined) venting is allowable with vertical type B vent systems and lined masonry chimneys as long as proper draft for the water heater is established under all conditions of operation. CAUTION: DO NOT common vent this water heater with any power vented appliance.

Figures 19-21 are examples of vent pipe system installations and may or may not be typical for your specific application. Consult the “National Fuel Gas Code”, NFPA 54, ANSI Z223.1- current edition and the guidelines set forth by prevailing local codes.

LISTED VENT CAP

 

2 FT. MINIMUM ABOVE ANY OBJECT

3 FT. MINIMUM

WITHIN 10 FT. HORIZONTALLY

SUPPORT

STRAP

 

prevent it from falling out.

To aid in removing the connector, a thimble or slip joint may

 

be used.

The connector must not extend beyond the inner edge of

 

the chimney as it may restrict the space between it and the

 

opposite wall of the chimney (Figure 19).

LISTED LINED

CHIMNEY

*MAINTAIN CLEARANCE

VENT

CONNECTOR

SLOPE UP

1/4 IN. PER FT.

MINIMUM

TYPE B DOUBLE WALL VENT PIPE

**MAINTAIN

SPECIFIED CLEARANCE

 

2 FT. MINIMUM ABOVE ANY OBJECT

3 FT. MINIMUM

WITHIN 10FT. HORIZONTALLY

SUPPORT

STRAP

VERTICAL GAS VENT SYSTEM WITH

TYPE B DOUBLE WALL VENT PIPE.

FIGURE 20.

MAINTAIN

CLEARANCE*

SEAL

SLOPE

UP 1/4 IN.

PER FT.

MINIMUM

DO NOT EXTEND VENT BEYOND EDGE OF CHIMNEY

VENT

CONNECTOR

 

 

LISTED VENT CAP

MAINTAIN MANUFACTURER’S

 

 

SPECIFIED MINIMUM CLEARANCE

**MAINTAIN

 

 

 

 

SPECIFIED

 

 

CLEARANCE

SUPPORT

 

 

STRAP

 

 

*MAINTAIN

 

 

CLEARANCE

SEAL

 

 

 

CHIMNEY TERMINATION VENT SYSTEM

FIGURE 19.

Do not terminate the vent connector in a chimney that has not been certified for this purpose. Some local codes may prohibit the termination of vent connectors in a masonry chimney.

Vertical Exhaust Gas Vent

Vertical exhaust gas vents must be installed with U.L. listed type B vent pipe according to the vent manufacturer’s instructions and the terms of its listing.

It must be connected to the water heater’s draft hood by a listed vent connector or by directly originating at the draft hood opening.

Vertical gas vents must terminate with a listed cap or other roof assembly and be installed according to their manufacturer’s instructions.

Gas vents must be supported to prevent damage, joint

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENT CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

UNUSED CHIMNEY

SLOPE UP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLUE OR MASONRY

1/4 IN. PER FT.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENCLOSURE

MINIMUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENTING THROUGH A CHIMNEY WITH

TYPE B DOUBLE WALL VENT PIPE.

FIGURE 21.

*Maintain vent pipe clearance requirements to local, state and/or the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition.

**NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances states that these chimneys are intended to be installed in accordance with the installation instructions provided with each chimney support assembly. Minimum air space clearance to combustible materials should be maintained as marked on the chimney sections.

20

Image 20
Contents Power Miser 9 GAS Water Heater Sears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.ASafe INSTALLATION, USE and Service Safety PrecautionsFire or Explosion Harzard Table of Contents Troubleshooting Guide Product Warranty Year Limited Warranty on Water HeaterCustomer Responsibilities Important Information About This Water HeaterProduct Specifications Jacket TOPMaterials and Basic Tools Needed Materials NeededTypical Installation GET to Know Your Water Heater GAS ModelsInstallation Checklist Important Information about this Water HeaterInstallation Instructions Removing the Old Water HeaterLocation Requirements Site LocationClearances and Accessibility Insulation BlanketsFilling the Water Heater GAS SupplyGas Requirements Gas PipingLP Gas Only Gas Pressure TestingGas Pressure All Air from Inside the Building Combustion AIR Supply & VentilationUnconfined Space All Air from Outdoors Louvers and GrillesDraft Hood Installation Vent ConnectorsVent Pipe System Vent Pipe SizeChimney Connection Vertical Exhaust Gas VentPiping Installation Water System PipingTemperature and Pressure Relief Valve Closed System/Thermal ExpansionOperating Your Water Heater Lighting InstructionsWater Temperature Regulation Checking the DraftBurner Flames Emergency Shut Down110 Service and Adjustment Tank Sediment CleaningBurner Cleaning Vent System Inspection Burner InspectionTemperature-Pressure Relief Valve Operation HousekeepingAnode Rod Inspection Draining and FlushingService Maintenance of Your Water Heater Replacing the Pilot/ Pilot Tube Assembly Cleaning the Combustion Chamber and Flame-arrestorReplacing the Manifold/Burner Assembly Piezoelectric Igniter SystemTesting the Igniter System Fvir System Operational ChecklistRemoving and Replacing the Gas Control Valve/Thermostat Removing the Gas ValveTroubleshooting Guide Start Up ConditionsOperational Conditions CondensationLeakage Checkpoints Troubleshooting Chart Problem Possible Causes Corrective ActionThermostat Fails to Pilot Light Troubleshooting Flowchart YESParts Order List Model Numbers Part DescriptionGet it fixed, at your home or ours MY-HOME1-800-469-4663

153.339432, 153.339372, 153.33955, 153.339572, 153.339482 specifications

Kenmore, a brand synonymous with quality home appliances, offers a wide range of products designed to make household tasks more efficient and enjoyable. Among their notable offerings are models 153.339432, 153.339482, 153.33955, 153.339473, and 153.339372. These models stand out due to their innovative features, advanced technologies, and user-friendly characteristics.

The Kenmore 153.339432 model is recognized for its sleek design and powerful performance. It boasts an energy-efficient motor that not only reduces electricity consumption but also enhances the longevity of the appliance. This model is equipped with multiple speed settings, allowing users to tailor operations according to their specific needs, whether it’s for intensive cleaning or gentle care.

In contrast, the 153.339482 emphasizes versatility with its multi-function capabilities. This model accommodates a variety of cooking styles and methods, ranging from steaming to conventional baking. Its digital interface simplifies the cooking process, making it easy for users to navigate settings and timers, ensuring that meals are cooked to perfection every time.

The Kenmore 153.33955 is distinguished by its smart technology integration. This model can be controlled remotely via a smartphone app, providing the convenience of monitoring cooking from anywhere in the home. Users can set cooking times, adjust temperatures, and receive notifications when the food is ready, merging traditional cooking wisdom with modern technological advancements.

Model 153.339473 offers an enhanced safety profile, featuring automatic shut-off functions and child lock settings. This ensures peace of mind for families, particularly those with young children. The durable construction and high-quality materials used in this model further enhance safety and reliability, making it a top choice for parents.

Lastly, the Kenmore 153.339372 is engineered with sustainability in mind. It incorporates eco-friendly materials and processes, reducing its environmental footprint without compromising on performance. This model also features an intuitive energy-saving mode, which encourages users to optimize cooking habits and reduce waste.

Together, these Kenmore models exemplify the brand's commitment to innovation, safety, and environmental consciousness, catering to diverse consumer needs while ensuring quality and reliability in every use. With Kenmore, customers can trust that they are investing in products designed to enhance their daily lives.