Kenmore 153.339572, 153.33955, 153.339473, 153.339372 All Air from Outdoors, Louvers and Grilles

Page 18

gas utilization equipment in the area. If you are unsure that the structure meets this requirement, contact your local gas utility company or other qualified agency for a safety inspection.

Each of the two openings shall have a minimum free area of 1 square inch per 1,000 BTUH of the total input rating of all gas utilization equipment in the confined area, but not less than 100 square inches (Figure 13).

CONFINED

SPACE

PERMANENT

OPENINGS

1 SQUARE

INCH/1000

BTUH

(MINIMUM

100 SQ. IN.)

FIGURE 13.

All Air from Outdoors

Outdoor fresh air can be provided to a confined area either directly or by the use of vertical and horizontal ducts. The fresh air can be taken from the outdoors or from crawl or attic spaces that freely communicate with the outdoors. Attic or crawl spaces cannot be closed and must be properly ventilated to the outside.

Ductwork must be of the same cross-sectional area as the free area of the opening to which they connect. The minimum dimension of rectangular air ducts cannot be less than three inches.

The size of each of the two openings is determined by the method in which the air is to be provided. Refer to Table 4 to calculate the minimum free area for each opening. Figures 14, 15, 16 and 17 are typical examples of each method.

Louvers and Grilles

In calculating free area for ventilation and combustion air supply openings, consideration must be given to the blocking effect of protection louvers, grilles, and screens. These devices can reduce airflow, which in turn may require larger openings to achieve the required minimum free area. Screens must not be smaller than 1/4” mesh. If the free area through a particular design of louver or grille is known, it should be used in calculating the specified free area of the opening. If the design and free area are not known, it can be assumed that most wood louvers will allow 20 - 25% of free area while metal louvers and grilles will allow 60 - 75% of free area.

Louvers and grilles must be locked open or interconnected with the equipment so that they are opened automatically during equipment operation.

Keep louvers and grilles clean and free of debris or other obstructions.

TABLE 4

Minimum Free Area of Permanent Openings for Ventilation and Combustion Air Supply - All Air from Outdoors Only.

Based on total BTUH input rating for all utilizing equipment within the confined space.

 

Minimum Free Area

Reference

Opening Source

Per Opening (sq. in.)

Drawing

*Direct to outdoors

1 sq. in, per 4000 BTUH

Figure 14

Vertical Ducts

1 sq. in, per 4000 BTUH

Figure 15

Horizontal Ducts

1 sq. in, per 2000 BTUH

Figure 16

Single Opening

1 sq. in, per 3000 BTUH

Figure 17

 

 

 

Example: A water heater with an input rating of 50,000 BTUH using horizontal ducts would require each opening to have a minimum free area of 25 square inches.

Minimum free area = 50,000 BTUH x 1 sq. in. / 2000 BTUH = 25 sq. in.

*These openings connect directly with the outdoors through a ventilated attic, a ventilated crawl space, or through an outside wall.

Consult the local codes of your area for specific ventilation and combustion air requirements.

 

GABLE VENT

 

TO OUTDOORS

 

INSTALL ABOVE

 

INSULATION

CONFINED

OUTLET

SPACE

AIR TO

 

ATTIC 1 SQ.

 

INCH PER

 

4000 BTUH

 

ALTERNATE

 

 

 

 

 

INLET AIR FROM

 

AIR INLET

 

 

 

 

 

THE CRAWL SPACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 SQ. INCH PER

 

 

 

 

 

OPEN

 

4000 BTUH

 

 

 

 

 

FOUNDATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENT

ALL AIR FROM OUTDOORS: INLET AIR FROM VENTILATED

CRAWL SPACE/OUTLET AIR TO VENTILATED ATTIC

FIGURE 14.

 

GABLE VENT

 

TO OUTDOORS

 

INSTALL ABOVE

 

INSULATION

 

OUTLET AIR

CONFINED

TO ATTIC

1 SQ. INCH

SPACE

PER 4000

 

BTUH

INLET AIR DUCT 1 SQ. INCH PER 4000 BTUH

12” MAXIMUM ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC

FIGURE 15.

18

Image 18
Contents Power Miser 9 GAS Water Heater Sears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.ASafe INSTALLATION, USE and Service Safety PrecautionsFire or Explosion Harzard Table of Contents Troubleshooting Guide Product Warranty Year Limited Warranty on Water HeaterCustomer Responsibilities Important Information About This Water HeaterProduct Specifications Jacket TOPMaterials and Basic Tools Needed Materials NeededTypical Installation GET to Know Your Water Heater GAS ModelsInstallation Checklist Important Information about this Water HeaterInstallation Instructions Removing the Old Water HeaterLocation Requirements Site LocationClearances and Accessibility Insulation BlanketsGas Requirements Filling the Water HeaterGAS Supply Gas PipingGas Pressure Testing Gas PressureLP Gas Only Combustion AIR Supply & Ventilation Unconfined SpaceAll Air from Inside the Building All Air from Outdoors Louvers and GrillesVent Pipe System Draft Hood InstallationVent Connectors Vent Pipe SizeChimney Connection Vertical Exhaust Gas VentPiping Installation Water System PipingTemperature and Pressure Relief Valve Closed System/Thermal ExpansionOperating Your Water Heater Lighting InstructionsBurner Flames Water Temperature RegulationChecking the Draft Emergency Shut Down110 Burner Cleaning Service and AdjustmentTank Sediment Cleaning Vent System Inspection Burner InspectionAnode Rod Inspection Temperature-Pressure Relief Valve OperationHousekeeping Draining and FlushingService Maintenance of Your Water Heater Replacing the Pilot/ Pilot Tube Assembly Cleaning the Combustion Chamber and Flame-arrestorReplacing the Manifold/Burner Assembly Piezoelectric Igniter SystemRemoving and Replacing the Gas Control Valve/Thermostat Testing the Igniter SystemFvir System Operational Checklist Removing the Gas ValveTroubleshooting Guide Start Up ConditionsOperational Conditions CondensationLeakage Checkpoints Troubleshooting Chart Problem Possible Causes Corrective ActionThermostat Fails to Pilot Light Troubleshooting Flowchart YESParts Order List Model Numbers Part DescriptionGet it fixed, at your home or ours MY-HOME1-800-469-4663

153.339432, 153.339372, 153.33955, 153.339572, 153.339482 specifications

Kenmore, a brand synonymous with quality home appliances, offers a wide range of products designed to make household tasks more efficient and enjoyable. Among their notable offerings are models 153.339432, 153.339482, 153.33955, 153.339473, and 153.339372. These models stand out due to their innovative features, advanced technologies, and user-friendly characteristics.

The Kenmore 153.339432 model is recognized for its sleek design and powerful performance. It boasts an energy-efficient motor that not only reduces electricity consumption but also enhances the longevity of the appliance. This model is equipped with multiple speed settings, allowing users to tailor operations according to their specific needs, whether it’s for intensive cleaning or gentle care.

In contrast, the 153.339482 emphasizes versatility with its multi-function capabilities. This model accommodates a variety of cooking styles and methods, ranging from steaming to conventional baking. Its digital interface simplifies the cooking process, making it easy for users to navigate settings and timers, ensuring that meals are cooked to perfection every time.

The Kenmore 153.33955 is distinguished by its smart technology integration. This model can be controlled remotely via a smartphone app, providing the convenience of monitoring cooking from anywhere in the home. Users can set cooking times, adjust temperatures, and receive notifications when the food is ready, merging traditional cooking wisdom with modern technological advancements.

Model 153.339473 offers an enhanced safety profile, featuring automatic shut-off functions and child lock settings. This ensures peace of mind for families, particularly those with young children. The durable construction and high-quality materials used in this model further enhance safety and reliability, making it a top choice for parents.

Lastly, the Kenmore 153.339372 is engineered with sustainability in mind. It incorporates eco-friendly materials and processes, reducing its environmental footprint without compromising on performance. This model also features an intuitive energy-saving mode, which encourages users to optimize cooking habits and reduce waste.

Together, these Kenmore models exemplify the brand's commitment to innovation, safety, and environmental consciousness, catering to diverse consumer needs while ensuring quality and reliability in every use. With Kenmore, customers can trust that they are investing in products designed to enhance their daily lives.