Kenmore 153.339511 HA, 153.33996, 153.33956 Temperature-Pressure Relief Valve, Water Damage Hazard

Page 13

LookatthetopofthewaterheaterThecoldwaterinlet.is

marked "COLD". Put two or three turns of teflon tape around the threaded end of the threaded-to-sweat coupling and around both ends of the 3/4" NPT threaded nipple. Using

flexible connectors, connect the cold water pipe to the cold water inlet of the water heater.

NOTE: This water heater is super insulated to minimize heat loss from the tank. Further reduction in heat loss

can be accomplished by insulating the hot water lines from the water heater.

INSTALLATION COMPLETED USING

INSTALLATION KIT

FLEXIBLE

WATER

CONNECTORS

HOT

WAITR--

 

 

COLe WATER

OUTLE

/'_

 

INLET

l

_

_

l s_UTVCEFF

COUPLING _

COUPLING

DRAFT Heed

TEMPERATURE

_'-_-PRESSURE RELIEF VALVE

DISCHARGE PIPE

(Do not c_p or plug)

%.

AIR

GAP

FLeeR DRAIN

FIGURE15.

Temperature-Pressure Relief Valve

Explosion Hazard

Temperature-pressure relief valve

! •must comply with ANSI Z21.22 and ASME code•

Properly sized temperature- pressure relief valve must be installed in opening provided.

Can result in overheating and excessive tank pressure.

Can cause serious injury or death.

This heater is provided with a properly certified combination temperature - pressure relief valve by the manufacturer.

The valve is certified by a nationany recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22 and the code requirements of ASME.

If replaced, the valve must meet the requirements of local codes, but not less than a combination temperature and pressure relief valve certified as indicated in the above paragraph.

The valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 psi = 1,035kPa) and a discharge capacity not less than the water heater input rate as shown on the model rating plate.

For safe operation of the water heater, the relief valve must not be removed from its designated opening nor plugged.

The temperature-pressure relief valve must be installed directly into the fitting of the water heater designed for the relief valve. Position the valve downward and provide tubing so that any discharge will exit only within 6 inches (153 mm) above, or at any distance below the structural floor, see Figure 16. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size

under any circumstances. Excessive length, over 30 feet (9.14 mr, or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve.

No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6 inch air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must

be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.

Water Damage Hazard

Temperature-pressurerelief valve discharge pipe rRuetterminate at adequate drain•

The Discharge Pipe:

Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.

Shall not be plugged or blocked.

Shall be of material listed for hot water distribution.

Shall be installed so as to allow complete drainage of both

the temperature-pressure relief valve, and the discharge pipe.

Shall terminate at an adequate drain.

Shall not have any valve between the relief valve and tank.

13

Image 13
Contents Sears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.A Installation and service must beDo not store or use gasoline or other Model noIndicates An imminently Symbol indicates a potentially hazardousCould result in death or injury Death or injuryFire Hazard Improper installation and use may result Property damageExplosion Hazard Feel water before bathing or showeringPage Dimensions RecoveryType Rategals DiameterMaterials Needed When Sweat SolderingBasic Tools Additional Tools Needed You may or may not need all these tools, depending on yourManuaIGas Shut-off Valve AnodeThermostat Pilot & Main BurnerTurn OFF the gas supply to Water Heater Removing the Old Water HeaterProperty Damage Hazard Facts to Consider About LocationFire or ExpJosion Hazard Ii ,i Insulation BlanketsFIGUREll ALL AIR from Inside BuildingsHotter Water can Scald Water PipingWater Damage Hazard Temperature-Pressure Relief ValveVenting Filling the Water HeaterFire and Explosion Hazard Gas PipingIre and Explosion Hazard Sediment TrapsGAS Piping with ALL Black Iron Pipe to GAS Control What to do if YOU Smell GAS RreOsoTemperature Regulation Burner Cleaning Tank Sediment Cleaning Burner InspectionHousekeeping Temperature-Pressure Relief Valve OperationAnode Rod Inspection DrainingService Drain Valve Washer ReplacementSee Figure Thermal Expansion Start Up ConditionsInlet* Water Heater Capacity Ganons Pressure Operational Conditions MakenecessaryairsupplychangestocorrectILII/I Leaking T&P Valve Page Page Model Numbers Part Description BurnerassemblyInformation 153.339560 153.339760By calling 1-800-366-PART 1-800-366-7278. If the parts you Page Limited Warranty on Tanks That Leak Full ONE Year Warranty on Water HeaterLimited Warranty on Parts Sears Installation Service