Kenmore 153.330702, 153.330502, 153.330752, 153.330552, 153.330402 owner manual Gas Piping

Page 14

Installation Instructions (cont'd)

Venting (cont'd)

All vent gases must be completely vented to the outdoors of the

structure (dwelling). install only the draft hood provided with the new water heater and no other draft hood.

Vent pipes must be secured at each joint with sheet metal screws.

TO

CHIMNEY

!

VENT PIPE INSTALLATION

There must be a minimum of 6" clearance between single wall vent pipe and any combustible material. Fill and seal any clear-

ance between single wall vent pipe and combustible material with mortar mix, cement, or other noncombustible substance.

For other than single wall, follow vent pipe manufacturer's clear- ance specifications. To insure a tight fit of the vent pipe in a

brick chimney, seal around the vent pipe with mortar mix cement.

AWARNING

Failureto haverequired clearancesbetween vent pipingand combustiblematerial will result in a fire hazard.

AWARNING]

Be sure vent pipe ispropody connectedto preventescapeof I dangerousflue gaseswhichcouldcausedeadlyasphyxiation. ]

AWARNING

Chemical vapor corrosionof the flue and vent system may occurif air for combustioncontainscertain chemicalvapors. Spray can propellants,cleaningsolvents,refrigerator and air conditioner refrigerants, swimming pool chemicals,calcium and sodiumchloride,waxes,bleach,and processchemicalsare typicalcompoundswhichare potentiallycorrosive.

Gas Piping

AWARNING

Make sure the gassupplied is the same type listed on the model rating plate. The inlet gaspressuremust not exceed 10.5in. water column (2.6kPa)for natural gasor 13in. water column (3.2kPa) for propane (L.P.)gas.The minimum inlet

gaspressurelistedon the model rating plate is for the pur- poseof input adjustment.

AWARNING,

If the gascontrolvalveis subjectedto pressuresexceeding'A poundper squareinch(3.5kPa), the damage to the gascon-

trol valvecouldresult in a fire or explosionfrom leakinggas.

_WARNING

If the main gasline shutoffservingall gasappliancesisused, alsoturn "OFF" the gasat eachappliance. Leaveall gasappli.

ancesshutoff untilthe water heater installationiscomplete.

A gas line of sufficient size must be run to the water heater. Consult the latest edition of National Fuel Gas Code ANSI

Z223.1, also referred to as NFPA 54 and the gas company con- cerning pipe size.

There must be:

A readily accessible manual shut offvalve in the gas supply llne serving the water heater, and

A drip leg (sediment trap) ahead of the gas control valve to help

prevent dirt and foreign materials from entering the gas control valve.

A flexible gas connector or a ground joint union between the shutoffvalve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lil_hting the water heater. Use a soapy water solution, not a match or open

flame. Rinse offsoapy solution and wipe dry.

Standard Models are for installation up to 3,300 feet above sea level.

High Altitude Models are for installation from 3,300 to 5,500 feet above sea level.

If a standard model is installed above 3,300 feet or a high altitude model is installed above 5,500 feet, the input rating must he

reduced at the rate of 4 percent for each 1,000 feet above sea level.

Contact your local Sears Service Center or gas utility for further information.

f

AWARNING

 

 

The applianceand it_

must be leak tested

 

beforeplacingthe appliance in operation.

14

Image 14
Contents Injury Property DAM For Your SafetyAN Odorant is Added to the GAS Used by this Water Heater Safety Precautions AwarningSafety Precautions Safety Precautions onAwarning Contents Specifications Customer ResponsibilitiesTubing Cutters or Hacksaw Materials and Basic Tools NeededMaterials Needed Propane TorchInstallation Instructions Removing the Old Water HeaterFacts to Consider About Location Installation Instructions contdWater Heaters Eventually Leak Installationof Confined Spaces Installation Completed Using Sears Installation KIT Water PipingInstallation Instructions Filling the Water Heater VentingGas Piping GAS Piping with ALL Black Iron Pipe to GAS Control GAS Piping withSediment Trap Check for Leaks Installation ChecklistBefore Lighting the Pilot II Warning Operating InstructionsLighting Not Force Operating Instructions contdWhatto Doif Yousmellgas ForceHotter Water can SCALDWater heatersareintendedto Temperature RegulationInstructions Contd Burner Cleaning Service and AdjustmentTank Sediment Cleaning Burner InspectionDrain Valve Washer Replacement Service and Adjustment contdTemperature-Pressure Relief DrainingSMOKE/ODOR Expansion Tank Sizing ChartStart Up Conditions ThermalAIR in HOT Water Faucets Troubleshooting Guide contdStrange Sounds High Temperature Shut OFF System Water is TOO HOT Operational Conditions contdTroubleshooting Guide contd Leakage CheckpointsPower Miser TM 12 GAS Water Heaters Parts Order ListPower Miser TM 12 GAS Water Heaters Model Numbers Parts Order List contdWarranty MY-HOME