Heat Controller TGC048C-1K-135, TGC060C-4K-135, TGC048C-3K-135 manual GENERAL10 DATA, NOMINAL 5 TONS

Page 10

GENERAL10 DATA

NOMINAL 5 TONS

Model

TGC060C-1K-135

TGC060C-3K-135

TGC060C-4K-135

Cooling Performance1

 

 

 

Gross Cooling Capacity Btuh

60000

60000

60000

EER/SEER2

11.6/13

11.6/13

11.6/13

Nominal CFM/ARI Rated CFM

2000/1900

2000/1900

2000/1900

ARI Net Cooling Capacity Btuh

58000

58000

58000

Net Sensible Capacity Btuh

42000

42000

42000

Net Latent Capacity Btuh

16000

16000

16000

Net System Power kW

5

5

5

Heating Performance (Package Gas/Electric) 3

 

 

Heating Input Btuh

135000

135000

135000

Heating Output Btuh

106500

109400

109400

Temperature Rise ºF

40-70

40-70

40-70

AFUE (%)

80

80

80

Steady State Efficiency (%)

81

81

81

Qty of Burners

6

6

6

Qty of Stages

1

1

1

Gas Connection Pipe Size, in.

.5

.5

.5

Compressor

 

1/Copeland Scroll

 

Qty/Type

 

 

Outdoor Sound Rating (dB)

83

78

78

Outdoor Coil—Fin Type

 

Louvered

 

Tube Type

Rifled

Rifled

Rifled

Tube Size in. OD

0.375

0.375

0.375

Face Area sq. ft.

16.56

16.56

16.56

Rows / Fins per inch

2/22

2/22

2/22

Indoor Coil—Fin Type

 

Corrugated

 

Tube Type

Rifled

Rifled

Rifled

Tube Size in.

0.375

0.375

0.375

Face Area sq. ft.

5.17

5.17

5.17

Rows / Fins per inch

3/15

3/15

3/15

Refrigerant Control

TXV

TXV

TXV

Drain Connection Qty/Size, in.

1/0.75

1/0.75

1/0.75

Outdoor Fan—Type

 

Propeller

 

Qty Used/Diameter in.

1/24

1/24

1/24

Drive Type/Speeds

Direct/1

Direct/1

Direct/1

CFM

3930

3930

3930

Qty Motors-HP

1-1/3

1-1/3

1-1/3

Motor RPM

1075

1075

1075

Indoor Fan—Type

 

Forward Curved Centrifugal

 

Qty Used/Diameter in.

1/10x10

1/10x10

1/10x10

Drive Type/Speeds

Direct/3

Direct/3

Belt/Variable

Motor Qty

1

1

1

Motor HP

1

1

3/4

Motor RPM

1075

1075

1725

Motor Frame Size

48

48

56

Filter—Type

 

Disposable

 

Furnished

Yes

Yes

Yes

(Qty) Size Recommended in.

(2)16x25x1

(2)16x25x1

(2)16x25x1

Refrigerant Charge Oz.

160

160

160

Weights

 

 

 

Net Weight lbs.

597

597

597

Ship Weight lbs.

604

604

604

Notes: 1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units are certified and rated per ARI Standard 210/240.

2.EER/SEER are rated ARI condition and accordance with DOE test procedures.

3.Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each 1000 feet above sea level.

Heat Controller, Inc. -10-

Image 10
Contents ENGINEERING DESIGN GUIDE TGC SERIES HIGH EFFICIENCY 13-SEERNOMINAL SIZES 3-5TONS C VINTAGE PACKAGE GAS ELECTRIC UNITSTABLE2 OF CONTENTS MODEL NOMENCLATURE - TGC SERIES MODEL IDENTIFICATIONT G C ENGINEERING4FEATURES ENGINEERING FEATURESControl Box Access INTRODUCTIONEvaporator Coil/Filter Access Compressor Access3.Select heating capacity of the unit SELECTION6PROCEDURE EXAMPLE2.Select unit to meet cooling requirements requirementsGENERAL7DATA NOMINAL 3 TONSGENERAL DATA NOMINAL 3.5 TONSGENERAL9DATA NOMINAL 4 TONSGENERAL10 DATA NOMINAL 5 TONSGROSS SYSTEM PERFORMANCE DATA-TGC036C SYSTEM PERFORMANCEGROSS SYSTEM PERFORMANCE DATA-TGC042C GROSS SYSTEM PERFORMANCE DATA-TGC060C GROSS SYSTEM PERFORMANCE DATA-TGC048CSYSTEM PERFORMANCE AIRFLOW PERFORMANCE DIRECT DRIVE DIRECT-DRIVE208 VOLT AIRFLOW PERFORMANCE14AIRFLOW PERFORMANCE-DIRECTDRIVE DIRECT-DRIVE230 VOLT AIRFLOW PERFORMANCEAIRFLOW PERFORMANCE-DIRECTDRIVE DIRECT-DRIVE460 VOLT AIRFLOW PERFORMANCEAIRFLOW PERFORMANCE-5TON BELT DRIVE ELECTRICAL DATA ELECTRICALELECTRICAL DATA Unit InformationPACKAGE GAS ELECTRIC UNITS UNIT DIMENSIONSUNIT DIMENSIONS BOTTOM VIEWUNIT DIMENSIONS UNIT DIMENSIONS PACKAGE GAS ELECTRIC UNITSHeat Controller, Inc UNIT20DIMENSIONS WEIGHTSACCESSORY EQUIPMENT-FIELDINSTALLED ACCESSORIESfor Natural Gas Only ➀ TYPICAL INSTALLATION ACCESSORIES22ROOFCURBS Full Perimeter ROOFCURB FOR TGC036C-TGC060CMODELSRXRD-KECM3-SingleEnthalpy with Barometric Relief ECONOMIZERSACCESSORIES RXRX-AV02-DualEnthalpy Kit RXRX-AR02-CO2 SensorPOWER EXHAUST KIT SPECIFICATIONS ACCESSORIES24INTEGRAL POWER EXHAUST FOR ECONOMIZER FRESH AIR DAMPERRectangular to Round Transitions Downflow ACCESSORIESDUCT ADAPTERS For use with Concentric DiffusersSIDE DISCHARGE CONCENTRIC DIFFUSER ACCESSORIES26DIMENSIONAL DATA ENGINEERING DATADIMENSIONAL DATA FLUSH MOUNT CONCENTRIC DIFFUSERACCESSORIES ENGINEERING DATARECOMMENDED THERMOSTATS WITH AND W/O ECONOMIZER ACCESSORIES28THERMOSTATS GAS/ELECTRIC Single Stage Cool w/o EconomizerWIRING SCHEMATIC-TGC060C-1K w/X-13 Heat Controller, IncWIRING SCHEMATIC-TGC036/048C-1Kw/PSC Heat Controller, IncWIRING SCHEMATIC-TGC036/060C-3Kw/PSC Heat Controller, IncWIRING SCHEMATIC-TGC060C-3K w/X-13 Heat Controller, IncWIRING SCHEMATIC-TGC060C-4Kw/BELT DRIVE Heat Controller, IncWIRING SCHEMATICS-TGC036/048C-4Kw/PSC Heat Controller, IncTHE QUALITY LEADER IN CONDITIONING AIR Design, material, performance data and componentssubject to change without notice 04/04/07