Heat Controller TGC042C-1K-120 SELECTION6PROCEDURE EXAMPLE, Select heating capacity of the unit

Page 6
SELECTION6PROCEDURE EXAMPLE

SELECTION6PROCEDURE EXAMPLE

1.Determine cooling and heating requirements at design conditions. Example:

Total cooling capacity

43,600 BTUH

Sensible cooling capacity

34,000 BTUH

Heating capacity

96,000 BTUH

Condenser entering air

95°F

Evaporator entering air

63°F wbt/76°F dbt

Indoor air flow

1600 CFM

External static pressure

0.6 in wg

Required efficiency

13 SEER

2.Select unit to meet cooling requirements.

Since total cooling is within the range of 4 ton unit and

requires 13 SEER efficiency level, enter cooling performance from the TGC048C at 95°F outdoor temperature, 63°F wbt

entering indoor air, and 1550 CFM:

Total capacity

....................................47,300 BTUH

Power input

3.5 kW

And also, at 76°F db indoor entering air, and using the formula

at the bottom of the table:

 

Sensible capacity

41,708 BTUH

3.Select heating capacity of the unit.

In the general data tables, note that the heating capacity of the 4 ton model with the 135,000 input heater can deliver 106,500

BTUH, which is suitable for this application.

4.Determine blower speed and power to meet the system

requirements.

At the given external static pressure of 0.6 in wg, the belt model must be selected. Enter the belt drive blower performance data at 1580 CFM and 0.6 in wg ESP:

Watts........635

5.Calculate indoor blower BTUH heat effect.

BTUH = Watts x 3.413 = 2168

6. Calculate net cooling capacities.

Net total cooling = 47,300 – 2168 = 45,132 BTUH

Net sensible cooling = 41,708 – 2168 = 39,540 BTUH

Heat Controller, Inc. -6-

Image 6
Contents ENGINEERING DESIGN GUIDE TGC SERIES HIGH EFFICIENCY 13-SEERNOMINAL SIZES 3-5TONS C VINTAGE PACKAGE GAS ELECTRIC UNITSTABLE2 OF CONTENTS MODEL IDENTIFICATION MODEL NOMENCLATURE - TGC SERIEST G C ENGINEERING4FEATURES ENGINEERING FEATURESControl Box Access INTRODUCTIONEvaporator Coil/Filter Access Compressor Access3.Select heating capacity of the unit SELECTION6PROCEDURE EXAMPLE2.Select unit to meet cooling requirements requirementsGENERAL7DATA NOMINAL 3 TONSGENERAL DATA NOMINAL 3.5 TONSGENERAL9DATA NOMINAL 4 TONSGENERAL10 DATA NOMINAL 5 TONSSYSTEM PERFORMANCE GROSS SYSTEM PERFORMANCE DATA-TGC036CGROSS SYSTEM PERFORMANCE DATA-TGC042C GROSS SYSTEM PERFORMANCE DATA-TGC048C GROSS SYSTEM PERFORMANCE DATA-TGC060CSYSTEM PERFORMANCE AIRFLOW PERFORMANCE DIRECT DRIVE DIRECT-DRIVE208 VOLT AIRFLOW PERFORMANCE14AIRFLOW PERFORMANCE-DIRECTDRIVE DIRECT-DRIVE230 VOLT AIRFLOW PERFORMANCEAIRFLOW PERFORMANCE-DIRECTDRIVE DIRECT-DRIVE460 VOLT AIRFLOW PERFORMANCEAIRFLOW PERFORMANCE-5TON BELT DRIVE ELECTRICAL DATA ELECTRICALELECTRICAL DATA Unit InformationPACKAGE GAS ELECTRIC UNITS UNIT DIMENSIONSUNIT DIMENSIONS BOTTOM VIEWUNIT DIMENSIONS PACKAGE GAS ELECTRIC UNITS UNIT DIMENSIONSHeat Controller, Inc UNIT20DIMENSIONS WEIGHTSACCESSORIES ACCESSORY EQUIPMENT-FIELDINSTALLEDfor Natural Gas Only ➀ TYPICAL INSTALLATION ACCESSORIES22ROOFCURBS Full Perimeter ROOFCURB FOR TGC036C-TGC060CMODELSRXRD-KECM3-SingleEnthalpy with Barometric Relief ECONOMIZERSACCESSORIES RXRX-AV02-DualEnthalpy Kit RXRX-AR02-CO2 SensorPOWER EXHAUST KIT SPECIFICATIONS ACCESSORIES24INTEGRAL POWER EXHAUST FOR ECONOMIZER FRESH AIR DAMPERRectangular to Round Transitions Downflow ACCESSORIESDUCT ADAPTERS For use with Concentric DiffusersSIDE DISCHARGE CONCENTRIC DIFFUSER ACCESSORIES26DIMENSIONAL DATA ENGINEERING DATADIMENSIONAL DATA FLUSH MOUNT CONCENTRIC DIFFUSERACCESSORIES ENGINEERING DATARECOMMENDED THERMOSTATS WITH AND W/O ECONOMIZER ACCESSORIES28THERMOSTATS GAS/ELECTRIC Single Stage Cool w/o EconomizerWIRING SCHEMATIC-TGC060C-1K w/X-13 Heat Controller, IncWIRING SCHEMATIC-TGC036/048C-1Kw/PSC Heat Controller, IncWIRING SCHEMATIC-TGC036/060C-3Kw/PSC Heat Controller, IncWIRING SCHEMATIC-TGC060C-3K w/X-13 Heat Controller, IncWIRING SCHEMATIC-TGC060C-4Kw/BELT DRIVE Heat Controller, IncWIRING SCHEMATICS-TGC036/048C-4Kw/PSC Heat Controller, IncTHE QUALITY LEADER IN CONDITIONING AIR Design, material, performance data and componentssubject to change without notice 04/04/07