Therma-Stor Products Group UA-135H owner manual Compressor Release & Noise Abatement, Controls

Page 7

FOR HVAC INSTALLER ONLY

Ultra-Aire return. Always select a return from a central location in the structure in an area that is always open to the rest of the structure. Do not use a return from a room that may have its door closed much of the time or, alternatively, install a separate return from the open part of the house.

4.5F Installation in an Attic with an Existing Forced Air HVAC System

ALWAYS install a catch pan with a drain or float interrupt for condensate under the UA-135H in an attic or condensate may damage the living space below.

The preferred method of installation is to create a separate return for the UA-135H in a central area of the structure. Duct the supply of the UA-135H to the air supply of the existing HVAC system. Connect an insulated duct from outside to the 6" collar of the UA-135H if you wish to provide fresh make-up air. Adjust a damper in the duct to provide the desired amount of fresh air. See Figure 7.

4.5G Installation in a Structure with Two Forced Air HVAC Systems

When installing the UA-135H in a space with two HVAC systems, the outlet air of the UA-135H may be ducted into the supply ducting of each system. The 10" outlet of the UA-135H may be split into two separate ducts by using a “T” or “Y” adapter. It is recommended to install a manual damper (balancing damper) and a backdraft damper in each duct, then connect to the supply ducting of each HVAC system. The balancing dampers provide the ability to control airflow into each system. The backdraft dampers prevent cross flow of air from one system to the other when only one system is active. See Figure 8.

4.5H Installation in a Structure with No Existing Forced Air HVAC System

When installing the UA-135H in a structure that does not have a forced air HVAC system, a single return for the UA-135H should be installed in central open area of the structure. DO NOT locate the return in a bathroom or a kitchen. The supplies of the UA-135H should be located in the remote areas of the structure (such as bedrooms, den, etc.). By ducting this way, the air inside the structure

will circulate through the UA-135H to be filtered and dehumidified. 4" diameter duct is recommended for branches to the bedrooms, 6" diameter duct is recommended for branches to larger areas. Connect an insulated duct from outside to the 6" collar of the UA-135H if you wish to provide fresh make-up air.

4.6 Compressor Release & Noise Abatement

The compressor is attached to the partition with one cable tie and a 1.5" x 1.5" x 4.5" foam pad to secure it during shipment. This rigid attachment must be removed once the unit is installed and may cause noise from compressor vibration. After installation, remove the service panel, cut and remove the cable tie and foam pad securing the compressor's accumulator to the partition. This will prevent the compressor from transmitting vibration to the cabinet.

For further noise abatement, make sure none of the refrigeration tubes are pressed against the cabinet or access panel. Check that the refrigeration tubes are centered in the holes where they pass through the partition. For additional noise control, attach 3⁄4" plywood surround.

A length of 10 feet or more of acoustical flex ducting on the outlet of the UA-135H will reduce air noise from the impeller fan. A length of flexible ducting on all UA-135H duct connections is recommended to reduce noise and vibration transmitted to rigid ductwork in the structure.

4.7 Controls

All control panels should be mounted in a central area of the structure where it can accurately sense the humidity of the air in the living space and be accessed. All controls require field wiring from the unit location to the panel mount location.

To determine how each control operates the UA-135H it must first be determined which control is being used and whether or not the 135H is ducted for fresh air ventilation.

Humidity/Fan Control Panel (P/N 4024155)

4.7A Humidity/Fan Control Panel WITHOUT Fresh Air Ventilation or Damper

4.7B Humidity/Fan Control Panel WITH Fresh Air Ventilation and WITHOUT Damper

4.7C Humidity/Fan Control Panel WITH Fresh Air Ventilation AND Damper

Ventilation Timer/Humidity Control Panel (P/N 4024125)

4.7D Ventilation Timer and Humidity Control WITH Fresh Air AND Motorized Damper

DEH 2000 Digital Control (P/N 4024539)

4.7E Digital Controller WITH Fresh Air AND Damper

4.7F Digital Controller WITHOUT Fresh Air

7

Ultra-Aire 135H Installer’s & Owner’s Manual

Image 7
Contents Air Filtration Hvac Installer Please Leave Manual for HomeownerUA-135H Part No Serial No Dehumidification Fresh Air VentilationTable of Contents /SAFETY Precautions & Specifications Safety Precautions Safety PrecautionsIntended Application for Ultra-Aire 135H For Hvac Installer onlySpecifications Installation4A Lifting Condensate Ducting 5A Installing Duct CollarsElectrical Requirements Condensate Water Removal5D Ducting for Fresh Air Option Humidity/Fan Control Panel P/N Ventilation Timer/Humidity Control Panel P/NCompressor Release & Noise Abatement Controls7E DEH 2000 Digital Controller WITH Fresh Air and Damper Humidity Control AdjustmentFan/Filter Switch Ventilation TimerAutomatic or Manual Mode Setting the TimeVentilation Schedule Page 2B Wiring SpecificationsInstallation 2A Install InstructionsOperation For Hvac Installer and Homeowner3G Fan On Fan Off Fan Program 3E Setting Relative Humidity Set point3F Fan Setting and Operation 3H Damper Operation and Setting Ventilation3I Intermittent or Programmed Ventilation 3J Programming Notes3L Stop Start Low Pressure ControlTechnical Description ServiceTroubleshooting Unit Test to determine problemReplacing a Compressor, Nonburn Out Impeller Fan ReplacementCompressor/Capacitor Replacement Refrigerant ChargingUA-135H With DEH 2000 Digital Controller Wiring DiagramsUA-135H W/Ventilation Timer UA-135H With Humidity/Fan ControlDescription Optional Parts ListService Parts List ULTRA-AIRE 135H Dehumidifier Limited Warranty PO Box 8680 Madison, WI Phone 608-222-5301 Fax

UA-135H specifications

The Therma-Stor Products Group UA-135H is a cutting-edge unit designed for efficient humidity control in various settings, especially in residential and commercial environments. This product stands out due to its robust construction and innovative technology, making it a preferred choice for those looking to maintain optimal air quality.

One of the key features of the UA-135H is its high-capacity dehumidification ability. With a removal capacity of up to 135 pints per day, this unit is ideal for tackling dampness in basements, crawl spaces, and larger living areas. This impressive capacity allows for effective moisture management, which is crucial in preventing mold growth and maintaining a healthy indoor environment.

Technologically advanced, the UA-135H incorporates a powerful compressor and a high-efficiency fan that ensures rapid and uniform air circulation. This design not only aids in faster moisture extraction but also enhances the overall energy efficiency of the unit. The built-in hygrometer monitors the humidity levels in real-time, allowing for automatic adjustments to optimize performance and reduce energy consumption.

Ease of use is another highlight of the UA-135H. The unit features a user-friendly digital control panel, enabling users to set their desired humidity levels with precision. Additionally, the product is equipped with a continuous drainage option, allowing for hassle-free operation without the need for frequent emptying of the water tank.

Durability is a hallmark of the UA-135H, featuring a corrosion-resistant housing that ensures longevity even in challenging environments. The unit operates quietly, providing effective humidity control without disturbing the peace of your home or workplace.

Energy efficiency ratings further enhance the appeal of the UA-135H. It not only meets but often exceeds industry standards, translating to cost savings on energy bills. The unit is also designed for easy maintenance, with accessible filters that can be cleaned or replaced with minimal effort, ensuring optimal performance over time.

In conclusion, the Therma-Stor Products Group UA-135H is a reliable and efficient solution for humidity control. Its combination of high-capacity dehumidification, advanced technology, user-friendly features, and durable design makes it an excellent investment for maintaining a healthy indoor environment. Whether for residential or commercial use, the UA-135H promises effective performance and long-lasting reliability.