Hoshizaki Condensing Unit Models SRK-14J/3, KMS-1401MLJ Controls and Adjustments, S4 Dip Switch

Models: Condensing Unit Models SRK-14J/3 KMS-1401MLJ

1 54
Download 54 pages 29.87 Kb
Page 19
Image 19
3. Controls and Adjustments

3. Controls and Adjustments

NOTICE

Dip switches are factory set. Failure to maintain factory settings may adversely affect performance and warranty coverage. For more information, contact Hoshizaki Technical Support at 1-800-233-1940.

a)Default Dip Switch Settings

The dip switches are factory-adjusted to the following positions:

 

 

 

 

 

S4 Dip Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dip Switch No.

1

2

 

3

 

4

 

5

 

6

7

8

9

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KMS-1401MLJ

OFF

OFF

OFF

ON

ON

ON

ON

OFF

OFF

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S5 Dip Switch (Do Not Adjust)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dip Switch No.

1

2

 

3

 

4

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KMS-1401MLJ

ON

ON

 

OFF

OFF

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S4 Dip Switch

 

 

 

 

 

 

 

 

 

 

 

 

S5 Dip Switch

ON

 

 

10

Freeze Timer (9 & 10)

 

 

 

 

 

 

 

 

 

Factory Use (8)

 

 

 

 

9

 

 

 

 

8

 

 

 

 

 

 

 

 

 

Harvest Pump Timer (7) (Do not adjust)

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

6

Pump-Out Frequency Control (5 & 6)

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

3

Pump-Out Timer (3 & 4)

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

1

Harvest Timer (1 & 2)

 

 

 

 

 

 

 

 

 

 

Do Not Adjust

 

 

 

 

 

 

5

Refill Counter

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

3

(2 through 5)

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

1

Float Switch

 

 

 

 

 

 

 

 

 

 

 

Selector (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b)Harvest Timer (S4 dip switch 1 & 2)

The harvest timer starts counting when the thermistor reads 48°F (9°C) at the evaporator outlet and the control board reads the thermistor's 3.9 kΩ signal. The harvest timer is factory set, and generally no adjustment is required. However, a setting longer than the factory setting may be advised in cases where the flush provided at harvest needs to be prolonged for extra cleaning. Before changing this setting, contact Hoshizaki Technical

Support at 1‑800‑233‑1940 for recommendations. Keep in mind that setting the harvest timer to a longer setting decreases 24-hour production.

Note that the pump‑out timer (S4 dip switch 3 & 4) acts in place of the harvest timer during cycles with a pump-out. For details, see "II.C.3.c) Pump-Out Timer (S4 dip switch

3 & 4)."

Dip Switch Setting

Time (seconds)

No. 1

No. 2

 

OFF

OFF

60

 

 

 

ON

OFF

90

 

 

 

OFF

ON

120

ON

ON

180

 

 

 

19

Page 19
Image 19
Hoshizaki Condensing Unit Models SRK-14J/3 Controls and Adjustments, a Default Dip Switch Settings, S4 Dip Switch