Hoshizaki KMS-1401MLJ, Condensing Unit Models SRK-14J/3 Freeze-Up - Possible Cause, Freeze Cycle

Models: Condensing Unit Models SRK-14J/3 KMS-1401MLJ

1 54
Download 54 pages 29.87 Kb
Page 42
Image 42
Freeze Cycle

Freeze-Up - Possible Cause

6. Float Switch

a) Dirty, sticking.

See "IV.D. Float Switch Check

b) Defective.

and Cleaning"

 

7. Refrigerant Charge

a) Low.

 

 

8. Control Board

a) Harvest timer (S4 dip switch 1 & 2) set too short.

See "II.C.3. Controls and

 

b) Harvest pump timer (S4 dip switch 7) not in factory default position.

Adjustments" and "IV.B. Control

 

Board Check"

c) Defective.

 

 

9. Bin Control

a) Actuator does not move freely.

See "IV.C. Bin Control Check and

 

Cleaning"

 

 

 

10. Thermistor

a) Loose, disconnected, or defective.

See "IV.E. Thermistor Check"

 

11. Thermostatic Expansion Valve

a) Defective.

 

 

12. Hot Gas Valves (KMS & SRK)

a) Closed or restricted.

 

 

13. Liquid Line Valves (KMS & SRK)

a) Open.

 

 

 

Freeze Cycle

1. Evaporator

a) Scaled up.

 

 

 

b) Damaged.

 

 

2. Spray Tubes and/or Spray

a) Dirty.

Guides

 

b) Out of position.

 

3. Refrigerant Charge

a) Low.

 

 

4. Control Board

a) Freeze timer (S4 dip switch 9 & 10) set incorrectly.

See "IV.B. Control Board Check"

 

b) Defective.

 

 

5. Fill/Refill or Harvest Water Valve

a) Leaking by.

6. Float Switch

a) Float does not move freely.

See "IV.D. Float Switch Check

 

b) Defective.

and Cleaning"

 

 

 

7. Pump Motor

a) RPM too slow.

 

 

 

b) Impeller damaged.

 

 

8. Thermostatic Expansion Valve

a) Bulb loose or defective.

9. Headmaster (C.P.R.)

a) Defective.

 

 

10. Liquid Line Valves (KMS & SRK)

a) Restricted.

 

 

42