2. Brazing

WARNING

R-404A itself is not flammable at atmospheric pressure and temperatures up to

176°F (80°C).

R-404A itself is not explosive or poisonous. However, when exposed to high temperatures (open flames), R-404A can be decomposed to form hydrofluoric acid and carbonyl fluoride both of which are hazardous.

Do not use silver alloy or copper alloy containing arsenic.

Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with pressurized air for leak testing.

1)Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.

Note: Because the pipes in the evaporator case are specially coated to resist corrosion, it is important to make connections outside the evaporator case when possible. If it is necessary to braze inside the evaporator case, use sandpaper to remove the coating from the brazing connections before unbrazing the components.

NOTICE

Always install a new drier every time the sealed refrigeration system is opened.

Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant flow.

When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C).

2)Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with pressurized air for leak testing.

3.Evacuation and Recharge (R-404A)

The condensing unit is provided with refrigerant shutoff valves and the icemaker is provided with refrigerant service valves. Evacuation and recharge via the condensing unit's refrigerant shutoff valves is recommended.

1)Attach a vacuum pump to the system. Be sure to connect the charging hoses to both high and low-side refrigerant shutoff valves.

IMPORTANT

The vacuum level and vacuum pump may be the same as those for current refrigerants. However, the rubber hose and gauge manifold to be used for evacuation and refrigerant charge should be exclusively for POE oils.

45

Page 45
Image 45
Hoshizaki Condensing Unit Models SRK-14J/3, KMS-1401MLJ service manual Brazing, Evacuation and Recharge R-404A

Condensing Unit Models SRK-14J/3, KMS-1401MLJ specifications

The Hoshizaki KMS-1401MLJ and the Condensing Unit Models SRK-14J/3 are critical components in the commercial refrigeration sector, designed to provide efficient and reliable cooling for various applications. These models stand out for their exceptional performance, advanced technologies, and robust characteristics that meet the demanding needs of food service, hospitality, and retail establishments.

One of the primary features of the Hoshizaki KMS-1401MLJ is its high-capacity cooling capability. With a refrigerating capacity suitable for larger applications, this unit is designed to handle significant load demands while maintaining energy efficiency. This is particularly advantageous in environments where consistent temperature control is vital for preserving perishable goods.

The SRK-14J/3 models further enhance the functionality of this system by incorporating advanced inverter technology. This innovation allows for variable speed operation, adjusting the compressor's output based on the actual cooling demand. As a result, users can experience reduced energy costs and lower environmental impact. This efficiency not only decreases the overall operating expenses but also extends the lifespan of the unit due to reduced wear and tear on the compressor.

The Hoshizaki units are also renowned for their user-friendly interface, which features intuitive controls for easy operation and monitoring. This ensures that users can quickly adjust settings to accommodate specific storage needs, improving overall convenience and efficiency in the workplace.

Additionally, both the KMS-1401MLJ and the SRK-14J/3 models are designed with durability in mind. Constructed from high-quality materials, they are built to withstand the rigorous demands of a commercial kitchen or storage facility. Features such as corrosion-resistant coatings and robust insulation enhance the longevity of these units, making them a wise investment for business owners.

In terms of maintenance, Hoshizaki has incorporated several design elements to facilitate ease of service. Access points for routine checks and cleaning have been strategically placed, enabling technicians to perform maintenance tasks without disrupting the operation of the units.

In conclusion, the Hoshizaki KMS-1401MLJ and Condensing Unit Models SRK-14J/3 offer a perfect blend of efficiency, durability, and technological advancement. Their ability to provide reliable cooling solutions makes them integral to any establishment focused on quality and performance in food and beverage storage. For businesses seeking to enhance operational efficiency while ensuring the preservation of their products, these models represent a leading choice in the commercial refrigeration market.