Hoshizaki KMS-1401MLJ d Pump-Out Cycle, e Harvest Cycle, f Shutdown, After 11th freeze cycle

Models: Condensing Unit Models SRK-14J/3 KMS-1401MLJ

1 54
Download 54 pages 29.87 Kb
Page 14
Image 14

d) Pump-Out Cycle

LEDs 1, 3, and 2 are on. Comp and FMRs remain energized, HGVs and X10 relay energize. LLVs de‑energize. PM stops for 2 seconds, then X11 relay energizes, allowing PM and DV to energize for 10 or 20 seconds (S4 dip switch 3 & 4). Water is removed from the bottom of the water tank and sent down the drain. At the same time, water flows through the small F/S tube to power flush F/S. When the pumpout timer terminates, pump-out is complete.

The 1st pump-out occurs after the 11th freeze cycle, then every 10th cycle thereafter. The pump-out frequency control is factory set, and generally no adjustment is required. However, where water quality is bad and the icemaker needs a pump-out more often, the pump-out frequency can be adjusted. The pump-out frequency control (S4 dip switch 5 & 6) can be set to have a pump-out occur every cycle, or every 2, 5, or

10 cycles. Timing of the first pump-out is dependent on S4 dip switch 5 & 6 settings. See the table below.

S4 Dip Switch Setting

Pump-Out

1st Pump-Out

No. 5

No. 6

Frequency

 

 

 

 

 

OFF

OFF

Every cycle

After 2nd freeze cycle

ON

OFF

Every 2 cycles

After 3rd freeze cycle

 

 

 

 

OFF

ON

Every 5 cycles

After 6th freeze cycle

 

 

 

 

ON

ON

Every 10 cycles

After 11th freeze cycle

 

 

 

 

e) Harvest Cycle

LEDs 1, 4, and 2 are on. Same as the initial harvest cycle. See "II.B.1.b) Initial Harvest Cycle."

Note: Icemaker continues to cycle until BC is satisfied or power is turned off. The icemaker always restarts at the 1-minute fill cycle.

f)Shutdown

When BC is activated (BC open), the yellow "BC OPEN" LED comes on. The icemaker then shuts down as outlined in the table below.

Cycle at Bin

Shutdown

Control Activation

 

 

 

Fill Cycle

15 seconds after activation.

 

 

Harvest Cycle

At the end of the harvest cycle, or up to 15 seconds into the freeze cycle if activated

 

at the end of the harvest cycle.

 

 

Freeze Cycle

15 seconds after activation if activated at least 15 seconds before the 5-minute short

 

cycle protection timer terminates. Otherwise, at the end of the next harvest cycle.

 

 

Legend: CB–control board; Comp–compressor; DV–drain valve; FMRs–fan motors‑remote; F/S–float switch; HGVs–hot gas valves; LLVs–liquid line valves; PM–pump motor; WV1–fill/refill water valve; WV2–harvest water valve