d) Pump-Out Cycle
LEDs 1, 3, and 2 are on. Comp and FMRs remain energized, HGVs and X10 relay energize. LLVs de‑energize. PM stops for 2 seconds, then X11 relay energizes, allowing PM and DV to energize for 10 or 20 seconds (S4 dip switch 3 & 4). Water is removed from the bottom of the water tank and sent down the drain. At the same time, water flows through the small F/S tube to power flush F/S. When the pump‑out timer terminates,
The 1st
10 cycles. Timing of the first
S4 Dip Switch Setting | 1st | |||
No. 5 | No. 6 | Frequency | ||
| ||||
|
|
|
| |
OFF | OFF | Every cycle | After 2nd freeze cycle | |
ON | OFF | Every 2 cycles | After 3rd freeze cycle | |
|
|
|
| |
OFF | ON | Every 5 cycles | After 6th freeze cycle | |
|
|
|
| |
ON | ON | Every 10 cycles | After 11th freeze cycle | |
|
|
|
|
e) Harvest Cycle
LEDs 1, 4, and 2 are on. Same as the initial harvest cycle. See "II.B.1.b) Initial Harvest Cycle."
Note: Icemaker continues to cycle until BC is satisfied or power is turned off. The icemaker always restarts at the
f)Shutdown
When BC is activated (BC open), the yellow "BC OPEN" LED comes on. The icemaker then shuts down as outlined in the table below.
Cycle at Bin | Shutdown |
Control Activation |
|
|
|
Fill Cycle | 15 seconds after activation. |
|
|
Harvest Cycle | At the end of the harvest cycle, or up to 15 seconds into the freeze cycle if activated |
| at the end of the harvest cycle. |
|
|
Freeze Cycle | 15 seconds after activation if activated at least 15 seconds before the |
| cycle protection timer terminates. Otherwise, at the end of the next harvest cycle. |
|
|
Legend:
14