Therma-Stor Products Group HI-E Dry Vehere Vehere Accessories, Refrigerant Charging, Relay

Page 8

Evaporator coil frosted continuously, low dehumidifying capacity.

1.Defrost thermostat loose or defective

2.Low refrigerant charge

3.Dirty air filters or airflow restricted.

7.3 Refrigerant Charging

WARNING: Only qualified service people should service this unit. The Vehere has a high-pressure refrigerant system and high voltage circuitry. This could present a hazard which could result in death, serious bodily injury, and/or property damage. Only qualified service people should service this unit.

If the refrigerant charge is lost due to service or a leak, a new charge must be accurately weighed in. If any of the old charge is left in the system, it must be removed before weighing in the new charge. Refer to the unit nameplate

for the correct charge weight and refrigerant type. Add the refrigerant through the low side service port. (See Fig. 11)

Figure 11: Low side service port.

7.4 Blower Replacement

The blower has a PSC motor internal thermal overload protection. If defective, the complete assembly must be replaced.

1.Unplug the power cord.

2.Remove the cabinet front.

3.If an outlet duct is connected to the unit, remove it.

4.Disconnect the blower leads: white from the compressor run capacitor, and black connected to the fan switch.

5.Remove the nuts & bolts holding the blower outlet flange to the cabinet end and remove the blower.

6.Reassembling with the new blower is the above procedure reversed.

7.5 Low Pressure Control

If the low side refrigerant pressure drops to 15 PSIG, the low pressure control opens and shuts off the compressor and blower. It is automatically reset. It will close when the refrigerant pressure rises to 35 PSIG. Its primary function is to prevent damage to the compressor if a leak develops in the refrigeration system. It may also open if the unit is

A)used in a cool area (below 50°F) and the defrost timer is not adjusted or B) stored where it is below 40°F and then started. Under these conditions, the unit will restart within several minutes. Until the unit warms up, it may cycle several times.

7.6 Relay

The contacts of the single pole, single throw relay complete the power circuit to the compressor. The contacts are closed when power is provided to the relay coil via the control circuit. The control circuit includes the humidity control, low pressure control, defrost thermostat and timer.

8 Vehere Accessories

Part No.

Item

4025283

Vehere Remote Humidity Sensor/Control

4022646

Indoor/Outdoor Relative Humidity Meter

4024934

Deluxe Indoor Relative Humidity Meter

4021749

Filter (2 Filters Required)

4023539

Collar, Duct, 12”, Galv. (intake)

4023603

Collar Assy, Duct, 12”, Galv. (exhaust)

Optional Ventilator

4019663 Quiet-Vent Exhaust Ventilator

Toll-Free 1-800-533-7533

www.thermastor.com • sales@thermastor.com

Image 8
Contents Read and Save These Instructions Specifications Intended ApplicationVehere Diagram LocationInstallation in humid area with ducting Mounting The Remote Humidity Sensor/ Controller Electrical RequirementsCondensate Removal DuctingOperation Ventilation MaintenanceService Vehere Accessories Blower ReplacementRefrigerant Charging Low Pressure ControlVehere Electrical Wiring Vehere wiring diagram Toll-FreeService Parts HI-E DRY Vehere Dehumidifier Limited Warranty