Bryant 581J RTU Open Controller Inputs and Outputs, Supply Air Temperature SAT Sensor

Page 26

581J

Table 3 – RTU Open Controller Inputs and Outputs

 

 

POINT NAME

BACnet OBJECT

 

TYPE OF I/O

CONNECTION PIN

 

 

NAME

 

NUMBER(S)

 

 

 

 

 

 

 

 

DEDICATED INPUTS

 

Space Temp / Zone Temp

zone_temp

 

AI (10K Thermistor)

J20--- 1, 2

Supply Air Temperature

sa_temp

 

AI (10K Thermistor)

J2--- 1, 2

Outdoor Air Temperature

oa_temp

 

AI (10K Thermistor)

J2--- 3, 4

Space Temperature Offset Pot

stpt_adj_offset

 

AI (100K Potentiometer)

J20--- 3

Safety Chain Feedback

safety_status

 

DI (24 VAC)

J1--- 9

Compressor Safety Status

comp_status

 

DI (24 VAC)

J1--- 2

Fire Shutdown Status

firedown_status

 

DI (24 VAC)

J1--- 10

Enthalpy Status

enthalpy_status

 

DI (24 VAC)

J2--- 6

Humidistat Input Status

humstat_status

 

DI (24 VAC)

J5--- 7

 

 

 

CONFIGURABLE INPUTS

 

Indoor Air CO2

iaq

 

AI (4--- 20 ma)

 

Outdoor Air CO2

oaq

 

AI (4--- 20 ma)

J4--- 2 or J4--- 5

Space Relative Humidity

space_rh

 

AI (4--- 20 ma)

 

Supply Fan Status*

sfan_status

 

DI (24 VAC)

 

Filter Status*

filter_status

 

DI (24 VAC)

J5--- 1 or J5---3 or

Door Contact Input*

door_contact_status

 

DI (24 VAC)

J5 5 or J5--- 7

Occupancy Contact*

occ_contact_status

 

DI (24 VAC)

 

 

 

 

OUTPUTS

 

 

Economizer Output

econ_output

 

AO (4--- 20ma)

J2--- 5

Supply Fan Relay State

sfan

 

DO Relay (24VAC , 1A)

J1--- 4

Compressor 1 Relay State

comp_1

 

DO Relay (24VAC , 1A)

J1--- 8

Compressor 2 Relay State

comp_2

 

DO Relay (24VAC , 1A)

J1--- 7

Heat Stage 1 Relay State

heat_1

 

DO Relay (24VAC , 1A)

J1--- 6

Heat Stage 2 Relay State

heat_2

 

DO Relay (24VAC , 1A)

J1--- 5

Power Exhaust Relay State

pexh

 

DO Relay (24VAC , 1A)

J11--- 3

Dehumidification Relay State

dehum

 

DO Relay (24VAC, 1A)

J11--- 7, 8

LEGEND

 

 

 

 

AI

---

Analog Input

 

 

 

 

AO ---

Analog Output

 

 

 

 

DI

---

Discrete Input

 

 

 

 

DO ---

Discrete Output

 

 

 

 

*These inputs (if installed) take the place of the default input on the specific channel according to schematic. Parallel pins J5--- 1 = J2--- 6, J5--- 3 = J1--- 10, J5---5 = J1--- 2 are used for field--- installation.

The RTU Open controller requires the use of a Bryant space sensor. A standard thermostat cannot be used with the RTU Open system.

Supply Air Temperature (SAT) Sensor —

On FIOP-equipped 581J unit, the unit is supplied with a supply-air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6-inches (12.7 mm) in length. It is a nominal 10-k ohm thermistor.

The SAT is factory-wired. The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-in. hole in the flange or duct.

SUPPLY AIR TEMPERATURE

SENSOR

SUPPLY AIR

ROOF CURB

RETURN AIR

C08200

Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 37.

Fig. 37 - Typical Mounting Location for Supply Air Temperature (SAT) Sensor on Small Rooftop Units

Outdoor Air Temperature (OAT) Sensor —

The OAT is factory-mounted in the EconoMi$er2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring.

26

Image 26
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing Sizes Unit Dimensional Drawing Sizes 07-09 Unit Dimensional Drawing Size Unit Dimensional Drawing Size 12 Roof Mount Operating WeightsPlan for Unit Location Units LB KGProvide Unit Support Plan for Sequence of Unit InstallationInspect Unit Roof Curb Details Sizes Roof Curb Details Size Rig and Place Unit MAX Weight Dimensions UnitField Fabricate Ductwork Convert to Horizontal and Connect Ductwork when requiredInstall Outside Air Hood Positioning on CurbEconomizer Hood and Two-Position Hood Install Flue HoodInstall Gas Piping Unit Model Unit Size MIN MAX Steel Pipe Spacing of Supports Nominal Diameter DimensionNatural Gas Supply Line Pressure Ranges Gas Line Piping Install External Condensate Trap and Line Condensate Drain Pan Side ViewMake Electrical Connections Field Power SupplyUnits Without Factory-Installed Disconnect All UnitsWeatherproof Cover Installation Convenience Outlet LocationThermostat Field Control WiringUnits without Thru-Base Connections Unit Connect Primary TransformerField Control Wiring Raceway Heat Anticipator Settings To connect a field-supplied humidistat Perfect Humidityt Control ConnectionsPerfect Humidity Space RH Controller To connect the Edge Programmable Thermidistat T6-PRH01-AOAT RRS RTU Open Control System RTU Open Multi-Protocol Control BoardRTU Open System Control Wiring Diagram C11070 Supply Air Temperature SAT Sensor RTU Open Controller Inputs and OutputsEconoMi$er2 Space Temperature SPT SensorsField Connections IAQ Sensor SEN J4-2 COM J4-3 24 VAC Space Relative Humidity Sensor Typical Wiring Relative Humidity Sensors Space or Duct MountedDuct Relative Humidity Sensor Typical Wiring Connecting Discrete InputsProtocol DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 Communication Wiring ProtocolsGeneral Baud Rate DS2 DS1Local Access RTU Open TroubleshootingLEDs on the RTU Open show the status of certain functions Outdoor Air Enthalpy Control PNO 33CSENTHSWLEDs Differential Enthalpy ControlReturn Air Enthalpy Sensor WiringSmoke Detectors SystemSupply Air See Completing Installation of Return Air SmokeSmoke Detector Locations Return Air Detector Shipping Position Unit Wire/Fuse or Hacr Breaker Sizing Data Unit NOM IFM Combustion Power No P.E Hacr FLA LRA BrkrUnbalanced 3-Phase Supply Voltage EconoMi$er IV Occupancy Switch Adjust Factory-Installed OptionsInstall Accessories Smoke Detectors
Related manuals
Manual 66 pages 2.92 Kb

581J specifications

The Bryant 581J is a high-efficiency gas furnace that exemplifies advanced heating technology and innovative design. Known for its reliability and comfort, the Bryant 581J offers impressive performance features that cater to both residential and commercial heating needs. One of its standout characteristics is the two-stage heating system, which allows the furnace to operate at a lower stage when the heating demand is modest, providing improved comfort and energy efficiency. This feature also minimizes temperature fluctuations, ensuring a more consistent and comfortable indoor environment.

Energy efficiency is a critical aspect of the Bryant 581J. With an annual fuel utilization efficiency (AFUE) rating of up to 96%, this furnace is designed to convert a high percentage of fuel into usable heat, which helps homeowners save on energy bills. The high-efficiency design also contributes to a reduced carbon footprint, aligning with modern environmental concerns.

The Bryant 581J is equipped with technologically advanced features, including the ComfortTechâ„¢ control system. This system enables enhanced temperature regulation and integrates easily with smart home systems, allowing homeowners the convenience of remote control through smartphones and tablets. Additionally, the furnace includes an electronically commutated motor (ECM) blower, which optimizes airflow and reduces energy consumption while enhancing the overall comfort level within the space.

Noise reduction is another key characteristic of the Bryant 581J. The furnace is engineered with sound-dampening technology, resulting in quieter operation compared to conventional furnaces. This attention to noise management makes it an appealing choice for residential applications, where peace and tranquility are crucial.

The durable construction of the Bryant 581J ensures longevity and reliability. With a robust cabinet and quality materials, it is built to withstand the rigors of daily operation. Furthermore, the furnace comes with a warranty that provides peace of mind, protecting the investment over the years.

Overall, the Bryant 581J represents a blend of efficiency, advanced technology, and reliable performance. With its high AFUE rating, innovative features, and quiet operation, it stands out in the market as a top choice for anyone seeking a dependable heating solution. Whether for new installations or replacements, the Bryant 581J is designed to meet the heating demands of today's energy-conscious homeowners.