Bryant 581J Field Connections, Space Temperature SPT Sensors, EconoMi$er2

Page 27

EconoMi$er2 —

The RTU Open control is used with EconoMi$er2 (option or accessory) for outdoor air management. The damper position is controlled directly by the RTU Open control; EconoMi$er2 has no internal logic device.

Outdoor air management functions can be enhanced with field-installation of these accessory control devices:

Enthalpy control (outdoor air or differential sensors) Space CO2 sensor

Outdoor air CO2 sensor

Field Connections

Field connections for accessory sensors and input devices are made the RTU Open, at plugs J1, J2, J4, J5, J11 and J20. All field control wiring that connects to the RTU Open must be routed through the raceway built into the corner post as shown in Fig. 30. The raceway provides the UL required clearance between high- and low-voltage wiring. Pass the control wires through the hole provided in the corner post, then feed the wires thorough the raceway to the RTU Open. Connect to the wires to the removable Phoenix connectors and then reconnect the connectors to the board.

Space Temperature (SPT) Sensors —

There are 2 types of SPT sensors available from Bryant, resistive input non-communicating (T55, T56, and T59) and Rnet communicating (SPS, SPPL, SPP, and SPPF) sensors. Each type has a variety of options consisting of: timed override button, set point adjustment, a LCD screen, and communication tie in. Space temperature can be also be written to from a building network or zoning system. However, it is still recommended that return air duct sensor be installed to allow stand-alone operation for back-up. Refer to the configuration section for details on controller configurations associated with space sensors.

S 33ZCT55SPT, space temperature sensor with override button (T-55)

S 33ZCT56SPT, space temperature sensor with override button and setpoint adjustment (T-56)

S 33ZCT59SPT, space temperature sensor with LCD (liquid crystal display) screen, override button, and

1

2

3

4

5

6

RED(+)

 

 

 

 

 

 

WHT(GND)

CCN COM

 

 

 

 

 

 

BLK(-)

 

 

 

 

 

 

 

 

 

 

SEN

 

 

 

 

 

SW1

 

 

 

 

 

 

 

 

 

 

 

BRN (GND)

SENSOR WIRING

 

 

 

 

 

BLU (SPT)

 

 

 

 

 

C08201

 

Fig. 38 - T-55 Space Temperature Sensor Wiring

581J

 

 

 

 

 

 

 

 

 

 

 

 

SEN

 

J20-1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SEN J20-2

Fig. 39 - RTU Open T-55 Sensor ConnectionsC08460

Connect T-56:See Fig. 40 for T-56 internal connections. Install a jumper between SEN and SET terminals as illustrated. Connect T-56 terminals to RTU Open J20-1, J20-2 and J20-3 per Fig. 41.

1

2

3

4

5

6

RED(+)

 

 

 

 

 

 

WHT(GND)

CCN COM

 

 

 

 

 

 

BLK(-)

 

 

 

 

 

 

 

 

 

 

SEN

 

SET

 

 

 

SW1

 

 

 

 

BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(T56)

 

 

 

 

 

 

BRN (GND)

SENSOR WIRING

 

 

 

 

 

BLU (SPT)

 

 

 

 

 

 

 

 

JUMPER

 

 

 

 

 

 

 

TERMINALS

 

 

 

 

 

 

 

AS SHOWN

setpoint adjustment (T-59)

Use 20 gauge wire to connect the sensor to the controller. The wire is suitable for distances of up to 500 ft. Use a three-conductor shielded cable for the sensor and setpoint adjustment connections. If the setpoint adjustment (slidebar) is not required, then an unshielded, 18 or 20 gauge, two-conductor, twisted pair cable may be used.

Connect T-55:See Fig. 38 for typical T-55 internal connections. Connect the T-55 SEN terminals to RTU Open J20-1 and J20-2. See Fig. 39.

Cool Warm

Fig. 40 - T-56 Internal Connections

SEN J20-1

SEN J20-2

Jumper

SET

SET J20-3

C08202

Fig. 41 - RTU Open T-56 Sensor ConnectionsC08461

27

Image 27
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing Sizes Unit Dimensional Drawing Sizes 07-09 Unit Dimensional Drawing Size Unit Dimensional Drawing Size 12 Units LB KG Operating WeightsPlan for Unit Location Roof MountPlan for Sequence of Unit Installation Inspect UnitProvide Unit Support Roof Curb Details Sizes Roof Curb Details Size MAX Weight Dimensions Unit Field Fabricate DuctworkRig and Place Unit Positioning on Curb Ductwork when requiredInstall Outside Air Hood Convert to Horizontal and ConnectInstall Flue Hood Install Gas PipingEconomizer Hood and Two-Position Hood Steel Pipe Spacing of Supports Nominal Diameter Dimension Natural Gas Supply Line Pressure RangesUnit Model Unit Size MIN MAX Gas Line Piping Condensate Drain Pan Side View Install External Condensate Trap and LineAll Units Field Power SupplyUnits Without Factory-Installed Disconnect Make Electrical ConnectionsConvenience Outlet Location Weatherproof Cover InstallationUnit Connect Primary Transformer Field Control WiringUnits without Thru-Base Connections ThermostatField Control Wiring Raceway Heat Anticipator Settings To connect the Edge Programmable Thermidistat T6-PRH01-A Perfect Humidityt Control ConnectionsPerfect Humidity Space RH Controller To connect a field-supplied humidistatOAT RRS RTU Open Multi-Protocol Control Board RTU Open Control SystemRTU Open System Control Wiring Diagram C11070 RTU Open Controller Inputs and Outputs Supply Air Temperature SAT SensorSpace Temperature SPT Sensors Field ConnectionsEconoMi$er2 IAQ Sensor SEN J4-2 COM J4-3 24 VAC Relative Humidity Sensors Space or Duct Mounted Space Relative Humidity Sensor Typical WiringConnecting Discrete Inputs Duct Relative Humidity Sensor Typical WiringBaud Rate DS2 DS1 Communication Wiring ProtocolsGeneral Protocol DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1RTU Open Troubleshooting Local AccessDifferential Enthalpy Control Outdoor Air Enthalpy Control PNO 33CSENTHSWLEDs LEDs on the RTU Open show the status of certain functionsSystem WiringSmoke Detectors Return Air Enthalpy SensorSee Completing Installation of Return Air Smoke Smoke Detector LocationsSupply Air Return Air Detector Shipping Position Unit Wire/Fuse or Hacr Breaker Sizing Data Hacr FLA LRA Brkr Unit NOM IFM Combustion Power No P.EUnbalanced 3-Phase Supply Voltage Smoke Detectors Adjust Factory-Installed OptionsInstall Accessories EconoMi$er IV Occupancy Switch
Related manuals
Manual 66 pages 2.92 Kb

581J specifications

The Bryant 581J is a high-efficiency gas furnace that exemplifies advanced heating technology and innovative design. Known for its reliability and comfort, the Bryant 581J offers impressive performance features that cater to both residential and commercial heating needs. One of its standout characteristics is the two-stage heating system, which allows the furnace to operate at a lower stage when the heating demand is modest, providing improved comfort and energy efficiency. This feature also minimizes temperature fluctuations, ensuring a more consistent and comfortable indoor environment.

Energy efficiency is a critical aspect of the Bryant 581J. With an annual fuel utilization efficiency (AFUE) rating of up to 96%, this furnace is designed to convert a high percentage of fuel into usable heat, which helps homeowners save on energy bills. The high-efficiency design also contributes to a reduced carbon footprint, aligning with modern environmental concerns.

The Bryant 581J is equipped with technologically advanced features, including the ComfortTechâ„¢ control system. This system enables enhanced temperature regulation and integrates easily with smart home systems, allowing homeowners the convenience of remote control through smartphones and tablets. Additionally, the furnace includes an electronically commutated motor (ECM) blower, which optimizes airflow and reduces energy consumption while enhancing the overall comfort level within the space.

Noise reduction is another key characteristic of the Bryant 581J. The furnace is engineered with sound-dampening technology, resulting in quieter operation compared to conventional furnaces. This attention to noise management makes it an appealing choice for residential applications, where peace and tranquility are crucial.

The durable construction of the Bryant 581J ensures longevity and reliability. With a robust cabinet and quality materials, it is built to withstand the rigors of daily operation. Furthermore, the furnace comes with a warranty that provides peace of mind, protecting the investment over the years.

Overall, the Bryant 581J represents a blend of efficiency, advanced technology, and reliable performance. With its high AFUE rating, innovative features, and quiet operation, it stands out in the market as a top choice for anyone seeking a dependable heating solution. Whether for new installations or replacements, the Bryant 581J is designed to meet the heating demands of today's energy-conscious homeowners.