Bryant 581J Natural Gas Supply Line Pressure Ranges, Unit Model Unit Size MIN MAX

Page 14

581J

This unit is factory equipped for use with Natural Gas fuel at elevations up to 2000 ft (610 m) above sea level. Unit may be field converted for operation at elevations above 2000 ft (610 m) and/or for use with liquefied petroleum fuel. See accessory kit installation instructions regarding these accessories.

NOTE: Furance gas input rate on rating plate is for installation up to 2000 ft (610 m) above sea level. In U.S.A. the input rating for altitudes above 2000 ft (610 m) must be derated by 4% for each 1000 ft (305 m) above sea level. In Canada the input rating must be derated by 10% for altitudes of 2000 ft (610 m) to 4500 ft (1372 m) above sea level.

For natural gas applications, gas pressure at unit gas connection must not be less than 4 in. wg (996 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating. For liquified petroleum applications, the gas pressure must not be less than 11 in. wg (2740 Pa) or greater than 13 in. wg (3240 Pa) at the unit connection.

X

9” MINIMUM CLEARANCE

FOR PANEL REMOVAL

GAS

REGULATOR*

MANUAL GAS

SHUTOFF VALVE*

BASE UNIT

 

48” MINIMUM

 

 

DRIP LEG

 

BASE RAIL

PER NFGC*

FIELD-FABRICATED

 

ROOF

 

SUPPORT*

FROM

CURB

LEGEND

 

GAS

 

METER

NFGC – National Fuel Gas Code

 

*Field supplied.

NOTE: Follow all local codes.

STEEL PIPE

SPACING OF SUPPORTS

NOMINAL DIAMETER

X DIMENSION

(in.)

(ft)

1/2

6

3/4 or 1

8

11/4 or larger

10

The gas supply pipe enters the unit at the burner access panel on the front side of the unit, through the long slot at

Fig. 15 - Gas Piping Guide

C11091

the bottom of the access panel. The gas connection to the unit is made to the 1/2-in. or 3/4-in. FPT gas inlet port on the unit gas valve.

Table 2 – Natural Gas Supply Line Pressure Ranges

UNIT MODEL

UNIT SIZE

MIN

MAX

 

 

 

 

 

 

581J

07, 08, 09, 12

4.0 in. wg

13.0 in. wg

 

(996 Pa)

(3240 Pa)

 

 

 

 

 

 

 

 

 

 

 

 

 

!

CAUTION

 

 

 

 

 

 

 

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in damage to equipment.

When connecting the gas line to the unit gas valve, the installer MUST use a backup wrench to prevent damage to the valve.

Install a gas supply line that runs to the unit heating section. Refer to the NFPA 54/NFGC or equivalent code for gas pipe sizing data. Do not use a pipe smaller than the size specified. Size the gas supply line to allow for a maximum pressure drop of 0.5-in wg (124 Pa) between gas regulator source and unit gas valve connection when unit is operating at high-fire flow rate.

The gas supply line can approach the unit in three ways: horizontally from outside the unit (across the roof), thru-curb/under unit basepan (accessory kit required) or through unit basepan (factory-option or accessory kit required). Consult accessory kit installation instructions for details on these installation methods. Observe clearance to gas line components per Fig. 15.

(with Accessory Thru-the-Curb Service Connections)

Factory-Option Thru-Base Connections (Gas Connections) —

This service connection kit consists of a NPT gas adapter fitting, an electrical bulkhead connector and a 3/4-in electrical bulkhead connector, all factory-installed in the embossed (raised) section of the unit basepan in the condenser section.

LOW VOLTAGE

CONDUIT

CONNECTOR

HIGH VOLTAGE

CONDUIT

CONNECTOR

STAINLESS STEEL FITTING

C008621

Fig. 16 - Thru-Base Connection Fittings

The thru-base gas connector has male and female threads. The male threads protrude above the basepan of the unit; the female threads protrude below the basepan.

Check tightness of connector lock nuts before connecting gas piping.

Gas Line: Install a 1/2-in (08 & 09 size Low Gas units only) or 3/4-in (for all other units) NPT street elbow on the thru-base gas fitting. Attach an appropriate size pipe nipple with minimum length of 16-in (406 mm) (field-supplied) to the street elbow and extend it through the access panel at the gas support bracket. See Fig. 17.

14

Image 14
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing Sizes Unit Dimensional Drawing Sizes 07-09 Unit Dimensional Drawing Size Unit Dimensional Drawing Size 12 Roof Mount Operating WeightsPlan for Unit Location Units LB KGProvide Unit Support Plan for Sequence of Unit InstallationInspect Unit Roof Curb Details Sizes Roof Curb Details Size Rig and Place Unit MAX Weight Dimensions UnitField Fabricate Ductwork Convert to Horizontal and Connect Ductwork when requiredInstall Outside Air Hood Positioning on CurbEconomizer Hood and Two-Position Hood Install Flue HoodInstall Gas Piping Unit Model Unit Size MIN MAX Steel Pipe Spacing of Supports Nominal Diameter DimensionNatural Gas Supply Line Pressure Ranges Gas Line Piping Install External Condensate Trap and Line Condensate Drain Pan Side ViewMake Electrical Connections Field Power SupplyUnits Without Factory-Installed Disconnect All UnitsWeatherproof Cover Installation Convenience Outlet LocationThermostat Field Control WiringUnits without Thru-Base Connections Unit Connect Primary TransformerField Control Wiring Raceway Heat Anticipator Settings To connect a field-supplied humidistat Perfect Humidityt Control ConnectionsPerfect Humidity Space RH Controller To connect the Edge Programmable Thermidistat T6-PRH01-AOAT RRS RTU Open Control System RTU Open Multi-Protocol Control BoardRTU Open System Control Wiring Diagram C11070 Supply Air Temperature SAT Sensor RTU Open Controller Inputs and OutputsEconoMi$er2 Space Temperature SPT SensorsField Connections IAQ Sensor SEN J4-2 COM J4-3 24 VAC Space Relative Humidity Sensor Typical Wiring Relative Humidity Sensors Space or Duct MountedDuct Relative Humidity Sensor Typical Wiring Connecting Discrete InputsProtocol DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 Communication Wiring ProtocolsGeneral Baud Rate DS2 DS1Local Access RTU Open TroubleshootingLEDs on the RTU Open show the status of certain functions Outdoor Air Enthalpy Control PNO 33CSENTHSWLEDs Differential Enthalpy ControlReturn Air Enthalpy Sensor WiringSmoke Detectors SystemSupply Air See Completing Installation of Return Air SmokeSmoke Detector Locations Return Air Detector Shipping Position Unit Wire/Fuse or Hacr Breaker Sizing Data Unit NOM IFM Combustion Power No P.E Hacr FLA LRA BrkrUnbalanced 3-Phase Supply Voltage EconoMi$er IV Occupancy Switch Adjust Factory-Installed OptionsInstall Accessories Smoke Detectors
Related manuals
Manual 66 pages 2.92 Kb

581J specifications

The Bryant 581J is a high-efficiency gas furnace that exemplifies advanced heating technology and innovative design. Known for its reliability and comfort, the Bryant 581J offers impressive performance features that cater to both residential and commercial heating needs. One of its standout characteristics is the two-stage heating system, which allows the furnace to operate at a lower stage when the heating demand is modest, providing improved comfort and energy efficiency. This feature also minimizes temperature fluctuations, ensuring a more consistent and comfortable indoor environment.

Energy efficiency is a critical aspect of the Bryant 581J. With an annual fuel utilization efficiency (AFUE) rating of up to 96%, this furnace is designed to convert a high percentage of fuel into usable heat, which helps homeowners save on energy bills. The high-efficiency design also contributes to a reduced carbon footprint, aligning with modern environmental concerns.

The Bryant 581J is equipped with technologically advanced features, including the ComfortTechâ„¢ control system. This system enables enhanced temperature regulation and integrates easily with smart home systems, allowing homeowners the convenience of remote control through smartphones and tablets. Additionally, the furnace includes an electronically commutated motor (ECM) blower, which optimizes airflow and reduces energy consumption while enhancing the overall comfort level within the space.

Noise reduction is another key characteristic of the Bryant 581J. The furnace is engineered with sound-dampening technology, resulting in quieter operation compared to conventional furnaces. This attention to noise management makes it an appealing choice for residential applications, where peace and tranquility are crucial.

The durable construction of the Bryant 581J ensures longevity and reliability. With a robust cabinet and quality materials, it is built to withstand the rigors of daily operation. Furthermore, the furnace comes with a warranty that provides peace of mind, protecting the investment over the years.

Overall, the Bryant 581J represents a blend of efficiency, advanced technology, and reliable performance. With its high AFUE rating, innovative features, and quiet operation, it stands out in the market as a top choice for anyone seeking a dependable heating solution. Whether for new installations or replacements, the Bryant 581J is designed to meet the heating demands of today's energy-conscious homeowners.