Carrier Z6, ZN030-105, ZW, 48ZT, Z8075-105, 48ZG installation instructions Installation

Page 2

CAUTION

Disconnect gas piping from units when leak testing at pres- sures greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in a hazardous condition. If gas valve is subjected to pressure greater than

0.5psig, it must be replaced. When pressure testing field- supplied gas piping at pressures of 0.5 psig or less, the unit connected to such piping must be isolated by manually closing the gas valve.

INSTALLATION

Jobsite Survey — Complete the following checks before installation.

1.Consult local building codes and the NEC (National Electrical Code) (ANSI/NFPA [National Fire Protection Association] 70) for special installation requirements.

2.Determine unit location (from project plans) or select unit location.

3.Check for possible overhead obstructions which may in- terfere with unit lifting or rigging.

CAUTION

Do not lift unit with forklift truck. Move unit with over- head rigging only.

Unit Placement — Inspect unit for transportation dam- age. File claim with transportation agency.

Provide clearance around and above unit for airflow, safety, and service access. Do not restrict top (area above condenser fans) in any way. Allow at least 6 ft on all sides for rated perfor- mance, code compliance, and service.

Check unit dimensional drawings for unit arrangement and minimum performance and service clearances.

Do not install unit in an indoor location. Do not locate air in- lets near exhaust vents or other sources of contaminated air.

On units equipped with power exhaust option, high velocity air is exhausted out the hood. Unit should be positioned with at least 10 ft clearance between the exhaust hood and any obstruc- tion. Although unit is weatherproof, guard against water from higher level runoff and overhangs.

Level by using unit frame as a reference. Physical data is shown in Tables 1A-6.

Roof Mount — Check building codes for weight distribu- tion requirements. Unit weight is shown in Tables 1A-1E and 2. Unit may be mounted on class A, B, or C roofing material.

ROOF CURB — Assemble and install roof curb as described in instructions shipped with the accessory. Accessory roof curb and information required to field fabricate a roof curb is shown in Fig. 1-5. Install insulation, cant strips, roofing and counter flashing as required. For unit condensate drain to function properly, curb must be level or within tolerances shown in Fig. 1-5.

STEEL BEAMS — If roof curb is not used, support unit with steel beams along its entire length and then support steel as re- quired. As a minimum, unit must be supported across its width at each lifting lug location.

Slab Mount — Provide a level concrete slab that extends beyond unit cabinet at least 6 inches. Make a slab 8 in. thick with 4 in. above grade. Use gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow. Ensure that slab is of sufficient height to allow for con- densate trap of 4 in. on sizes 030-070 or 7 in. on sizes 075-105.

Curb Gasketing

SIZE 030-050 UNITS — After ductwork has been connected to the roof curb, attach adhesive-backed gasketing on all end rails, cross rails, and duct rails. Be sure all joints and corners of gasket are square and flush to prevent possible water leaks. Follow all applicable building codes.

SIZE 055-105 UNITS — After ductwork has been connected to the roof curb, apply gasket material (1/2-in. thick x 11/2-in. wide neoprene) where indicated.

Single-Thickness Gasketing (See Fig. 6-8 for Item Num- bers) — Apply gasketing in the following places:

1.Along both side rails (1) — 2 places, full length

2.Along return air end rail (2) — 1 place

3.Around return air internal duct flange (3) — 1 or 2 places

4.Around supply air internal duct flanges (4) — 3 places

Double-Thickness Gasketing (See Fig. 6 and 8 and Detail A-A) — Locate a line 93/4-in. from the supply air end of the accessory curb. Apply a double-thickness of gasket material along with line per detail A-A.

NOTE: Do not apply gasket material along the outside edge of the curb (area “X”). This pan area of the curb extends out beneath the end of the unit’s air handler section; applying gas- ket here develops a potential water trap area on top of the curb.

Condenser Section Roof Curb (See Fig. 7) — Apply single- thickness gasket along both side rails (5).

Field-Fabricated Ductwork

WARNING

For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install a 90-degree turn in the supply and return ductwork between the unit and the conditioned space. If a 90-degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space. Failure to follow these instructions could result in personal injury or property damage due to falling objects.

The 48ZG,ZN,ZT,ZW,Z6,Z8 units are designed for vertical supply/return only. Field-fabricated ductwork must be attached to the roof curb, on to the support steel, prior to the final rigging and installation of the unit. Supply and return duct dimensions are shown in Fig. 1-3.

To attach ductwork to roof curb, insert duct approximately 10 to 11 in. up into roof curb. Connect ductwork to 14-gage roof curb material with sheet metal screws driven from inside the duct.

Secure all ducts to the building structure, using flexible duct connectors between roof curbs and ducts as required. Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. Outlet grilles must not lie directly below unit discharge. The return duct must have a 90-degree elbow before opening into the building space if the unit is equipped with power exhaust.

Design supply duct strong enough to handle expected static pressures.

Rigging — Do not drop unit; keep upright. Use spreader bars over unit to prevent sling or cable damage. Sheets of ply- wood placed along the condenser coils will provide additional protection. All lifting lugs MUST be used when lifting unit. Level by using unit frame as a reference. See Fig. 9-13 for in- formation. Unit and accessory weights are shown in Tables 1A- 1E and 2. Weight distribution and center of gravity can be found in Fig. 14.

2

Image 2
Contents Installation Instructions Installation Physical Data 48ZG,ZN030-050 Base UnitAlternate High-Capacity Evaporator Coil Physical Data 48ZG,ZN055-070 Base UnitPhysical Data 48ZG,ZN075-105 Base UnitOutside AIR Screens Physical Data 48Z6,Z8075-105 RETURN/EXHAUST FAN Physical Data 48ZT,ZW075-105 Operating Weights of Options and Accessories lb Power ExhaustSupply Fan Drive Data Power Exhaust Fan Drive DataHigh-Capacity Power Exhaust Fan Drive Data 48ZT,ZW Units Return/Exhaust Fan Drive Data 48Z6,Z8 UnitsRoof Curb Sizes 055-105 Roof Curb Sizes 075-105 with High-Capacity Power Exhaust Condenser Section Roof Curb Size 055 and 060 Only Condenser Section Roof Curb Size 070-105 Only Condenser END Support Gasket Location on Roof Curb 48ZT,ZW075-105 Units Rigging Label Size 055-105 Units Standard Chassis Rigging Label Size 055,060 Units Extended Chassis Weight Distribution and Center of Gravity Page 24 → Page Page A48-8451 Page Page A48-8452 A48-8453 A48-8454 Install Outdoor Hoods 48ZG,ZN,Z6,Z8 Units Outdoor Air Hood Installation Sizes Install Economizer Hoods 48ZT,ZW Units Field Wire Routing Disconnect Location Size 030-050 Units Disconnect Location 48ZG,ZN055-105 and 48Z6,Z8075-105 Units Field Power Wiring Connections Electrical Data, 48ZG,ZN030 Units MCA Mocp FLAElectrical Data, 48ZG,ZN035 Units Electrical Data, 48ZG,ZN040 Units Electrical Data, 48ZG,ZN050 Units Electrical Data, 48ZG,ZN055 Units MCA Mocp FLAElectrical Data, 48ZG,ZN060 Units Electrical Data, 48ZG,ZN070 Units 460Electrical Data 48ZG,ZN075-105 Units Electrical Data 48Z6,Z8075-105 Units Electrical Data 48ZT,ZW075-105 Units Indoor Evaporator Fan Motor Auxiliary Control Box Location Sizes Auxiliary Control Box Details Sizes Sizes 055-105 without Return FanReturn/Exhaust-Fan Shipping Brackets 48Z6 Shipping Brackets Sizes Compressor Mounting Gas Piping Details 48Z Series Staged Gas ImplementationFlue/Inlet Hood Locations, 030-060 Units Inlet Hood View Port Cover Installation Units Only SGC Thermistor Designations PointCCN Connection Approved Shielded Cables Field Control Thermostat Wiring Smoke Control ModesSpace Temperature Averaging Wiring Heat Interlock Relay Wiring Fan Status Switch Wiring Return Air Smoke Detector Wiring CCN Connections Page Copyright 2009 Carrier Corporation
Related manuals
Manual 8 pages 37.42 Kb

Z6, 48ZG, 48ZT, ZW, Z8075-105 specifications

The Carrier Z8075-105, Z6, 48ZG, 48ZT, and ZW series of HVAC systems represent a significant advancement in heating, ventilation, and air conditioning technology. These units are specifically designed for enhanced energy efficiency, superior performance, and ultimate comfort in residential and commercial spaces.

The Carrier Z8075-105 model stands out due to its impressive cooling and heating capabilities. It features a high Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), allowing for reduced energy consumption and lower utility bills. This model is equipped with advanced inverter technology that enables variable speed operation, significantly reducing noise levels and providing consistent temperature control.

Turning to the Z6 model, it is engineered for both robustness and reliability. It incorporates a modular design that allows for easy installation and maintenance. One of its key features is the use of innovative insulation materials that minimize sound levels, making it ideal for noise-sensitive environments. Furthermore, the Z6 series comes with a smart control system that allows users to monitor and adjust settings remotely, further optimizing energy usage.

The 48ZG and 48ZT models are designed with durability in mind. They utilize a fully enclosed compressor system that protects critical components from environmental damage. These models also boast enhanced dehumidification capabilities, making them suitable for humid climates. Equipped with advanced filtration systems, they improve indoor air quality by removing allergens and particulates effectively.

Carrier's ZW series exemplifies cutting-edge technology with its dual fuel capability, which allows the system to switch between a heat pump and a gas furnace, depending on outdoor temperatures. This feature maximizes energy savings while ensuring a comfortable indoor climate year-round. The ZW models also support integration with smart home systems, providing seamless control through mobile apps.

Collectively, these Carrier models are designed to meet the diverse needs of today’s consumers, offering a blend of efficiency, comfort, and intelligent control. Their ability to adapt to various environmental conditions while maintaining optimal performance makes them a leading choice in the HVAC market. With a focus on sustainability, these systems not only offer significant energy savings but also contribute to reducing the carbon footprint. As technology continues to evolve, Carrier remains at the forefront, delivering reliable, innovative HVAC solutions.