Carrier 48ZG, ZN030-105, ZW, Z6, 48ZT, Z8075-105 SGC Thermistor Designations, Point

Page 59

Table 19 — SGC Thermistor Designations

 

PIN

FUNCTION AND LOCATION

 

THERMISTOR

CONNECTION

 

PART NO.

Thermistors

 

POINT

 

 

 

 

SAT1

 

Supply-Air Thermistor (SAT) — Inserted into supply section

 

J8 – 1,2 (SGC)

underneath the gas heat section (factory-provided,

 

 

 

field-installed)

 

SAT2

 

Supply-Air Thermistor (SAT) — Inserted into supply section

 

J8 – 3,4 (SGC)

underneath the gas heat section (factory-provided,

 

 

 

field-installed)

HH79NZ033

SAT3

 

Supply-Air Thermistor (SAT) — Inserted into supply section

 

J8 – 5,6 (SGC)

underneath the gas heat section (factory-provided,

 

 

 

field-installed)

 

LIMTTEMP

J8 – 15,16 (SGC)

Limit Switch Thermistor (LIMTTEMP) — Inserted next the

 

lower limit switch (factory-installed)

 

 

 

 

SGC — Staged Gas Controller

 

 

Install Unit Accessories — For applications requiring accessories, the following packages are available:

All units:

barometric relief

space temperature sensor

CO2 sensor

space temperature sensor with CO2

airflow switch

filter switch

smoke detector

All 48ZG,ZT,Z6 units:

modulating power exhaust

pressure operated unloaders

All 48ZN,ZW,Z8 units:

modulating power exhaust

VFD remote display

Refer to the individual accessory installation instructions in each accessory package for information on installing accessories.

CONTROLS INSTALLATION

Constant Volume (CV) Units — The 48ZG,ZT,Z6 units may be used in applications with additional control features, options, or accessories. Refer to the appropriate accessory installation instructions for more information on installing that accessory. Control options and accessories available for CV units are:

thermostats

enthalpy sensor

enthalpy switch

relative humidity sensor

CEM (controls expansion module)

Navigator™ hand-held display

CONTROL WIRING — The unit can be controlled with a Carrier-approved accessory electro-mechanical or electronic thermostat that has two stages of cooling, two stages of heating control, and an output for fan control. The thermostat may also include time of day scheduling or use scheduling routines built into the ComfortLink™ controls.

Install the thermostat according to the installation instruc- tions shipped with the accessory thermostat. Locate thermostat assembly on a solid interior wall to sense average temperature.

Route thermostat cable or equivalent leads of colored wire from subbase terminals through conduit into the low voltage connections in the main control box. For thermostat TB203 connections, see Fig. 67.

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger

than no. 18 AWG cannot be directly connected at the thermostat and will require a junction box and splice at the thermostat.

Variable Air Volume (VAV) Units — The 48ZN, ZW, Z8 units may be used in applications with additional con- trol features, options, or accessories. Refer to the appropriate accessory installation instructions for more information on in- stalling that accessory. Refer to the Controls and Troubleshoot- ing manual for more information concerning installation and configuration of options and accessories. Control options and accessories available for VAV units are:

enthalpy sensor

enthalpy switch

relative humidity sensor

CEM (controls expansion module)

Navigator hand-held display

VFD remote display

VAV CONTROL WIRING — The recommended types of control wiring are shown below:

MANUFACTURER

PART NO.

Regular Wiring

Plenum Wiring

 

Alpha

1895

American

A21451

A48301

Belden

8205

884421

Columbia

D6451

Manhattan

M13402

M64430

Quabik

6130

SENSORS — Sensors should be wired using single twisted pairs of 20 AWG (American Wire Gage) conductor cable rated for the application, except for the T-56 accessory sensor which requires 3-conductor cable.

NOTE: Humidity and CO2 sensors must be powered from isolated 24-v power supplies.

HUMIDITY CONTROL AND HOT WATER AND STEAM VALVES — These devices require 20 AWG twisted pair conductor cables rated for the application for the 4 to 20 mA signal.

SPACE TEMPERATURE SENSOR (T-55) — The space tem- perature sensor (P/N 33ZCT55SPT) is shipped standard with every unit, and is located in the main control box. Space tem- perature sensor wires are to be connected to terminals in the unit main control box.

CAUTION

Jumper MUST be in place between pins 1 and 3, 3 and 4 or inaccurate readings could result.

To connect the space temperature sensor, see Fig. 68.

59

Image 59
Contents Installation Instructions Installation Base Unit Physical Data 48ZG,ZN030-050Alternate High-Capacity Evaporator Coil Base Unit Physical Data 48ZG,ZN055-070Base Unit Physical Data 48ZG,ZN075-105Outside AIR Screens Physical Data 48Z6,Z8075-105 RETURN/EXHAUST FAN Physical Data 48ZT,ZW075-105 Power Exhaust Operating Weights of Options and Accessories lbReturn/Exhaust Fan Drive Data 48Z6,Z8 Units Power Exhaust Fan Drive DataHigh-Capacity Power Exhaust Fan Drive Data 48ZT,ZW Units Supply Fan Drive DataRoof Curb Sizes 055-105 Roof Curb Sizes 075-105 with High-Capacity Power Exhaust Condenser Section Roof Curb Size 055 and 060 Only Condenser Section Roof Curb Size 070-105 Only Condenser END Support Gasket Location on Roof Curb 48ZT,ZW075-105 Units Rigging Label Size 055-105 Units Standard Chassis Rigging Label Size 055,060 Units Extended Chassis Weight Distribution and Center of Gravity Page 24 → Page Page A48-8451 Page Page A48-8452 A48-8453 A48-8454 Install Outdoor Hoods 48ZG,ZN,Z6,Z8 Units Outdoor Air Hood Installation Sizes Install Economizer Hoods 48ZT,ZW Units Field Wire Routing Disconnect Location Size 030-050 Units Disconnect Location 48ZG,ZN055-105 and 48Z6,Z8075-105 Units Field Power Wiring Connections MCA Mocp FLA Electrical Data, 48ZG,ZN030 UnitsElectrical Data, 48ZG,ZN035 Units Electrical Data, 48ZG,ZN040 Units Electrical Data, 48ZG,ZN050 Units MCA Mocp FLA Electrical Data, 48ZG,ZN055 UnitsElectrical Data, 48ZG,ZN060 Units 460 Electrical Data, 48ZG,ZN070 UnitsElectrical Data 48ZG,ZN075-105 Units Electrical Data 48Z6,Z8075-105 Units Electrical Data 48ZT,ZW075-105 Units Indoor Evaporator Fan Motor Auxiliary Control Box Location Sizes Sizes Sizes 055-105 without Return Fan Auxiliary Control Box DetailsReturn/Exhaust-Fan Shipping Brackets 48Z6 Shipping Brackets Sizes Compressor Mounting 48Z Series Staged Gas Implementation Gas Piping DetailsFlue/Inlet Hood Locations, 030-060 Units Inlet Hood View Port Cover Installation Units Only Point SGC Thermistor DesignationsCCN Connection Approved Shielded Cables Smoke Control Modes Field Control Thermostat WiringSpace Temperature Averaging Wiring Heat Interlock Relay Wiring Fan Status Switch Wiring Return Air Smoke Detector Wiring CCN Connections Page Copyright 2009 Carrier Corporation
Related manuals
Manual 8 pages 37.42 Kb

Z6, 48ZG, 48ZT, ZW, Z8075-105 specifications

The Carrier Z8075-105, Z6, 48ZG, 48ZT, and ZW series of HVAC systems represent a significant advancement in heating, ventilation, and air conditioning technology. These units are specifically designed for enhanced energy efficiency, superior performance, and ultimate comfort in residential and commercial spaces.

The Carrier Z8075-105 model stands out due to its impressive cooling and heating capabilities. It features a high Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), allowing for reduced energy consumption and lower utility bills. This model is equipped with advanced inverter technology that enables variable speed operation, significantly reducing noise levels and providing consistent temperature control.

Turning to the Z6 model, it is engineered for both robustness and reliability. It incorporates a modular design that allows for easy installation and maintenance. One of its key features is the use of innovative insulation materials that minimize sound levels, making it ideal for noise-sensitive environments. Furthermore, the Z6 series comes with a smart control system that allows users to monitor and adjust settings remotely, further optimizing energy usage.

The 48ZG and 48ZT models are designed with durability in mind. They utilize a fully enclosed compressor system that protects critical components from environmental damage. These models also boast enhanced dehumidification capabilities, making them suitable for humid climates. Equipped with advanced filtration systems, they improve indoor air quality by removing allergens and particulates effectively.

Carrier's ZW series exemplifies cutting-edge technology with its dual fuel capability, which allows the system to switch between a heat pump and a gas furnace, depending on outdoor temperatures. This feature maximizes energy savings while ensuring a comfortable indoor climate year-round. The ZW models also support integration with smart home systems, providing seamless control through mobile apps.

Collectively, these Carrier models are designed to meet the diverse needs of today’s consumers, offering a blend of efficiency, comfort, and intelligent control. Their ability to adapt to various environmental conditions while maintaining optimal performance makes them a leading choice in the HVAC market. With a focus on sustainability, these systems not only offer significant energy savings but also contribute to reducing the carbon footprint. As technology continues to evolve, Carrier remains at the forefront, delivering reliable, innovative HVAC solutions.