Carrier ZW, ZN030-105, Z6, 48ZT, Z8075-105, 48ZG Smoke Control Modes, Field Control Thermostat Wiring

Page 61

d. Secure shield wire to CCN screw terminal SHIELD on the COMM board.

IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent unit from starting. If abnormal conditions occur, unplug the connec- tor. If conditions return to normal, check CCN connector, and run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus.

RJ14 PLUG WIRING — Units on the CCN can be monitored from the space at the sensor through the RJ14 connector, if desired. To wire the RJ14 connector into the CCN (Fig. 80):

IMPORTANT: The cable selected for the RJ14 connector wiring MUST be identical to the CCN communication bus wire used for the entire network.

1.Cut the CCN wire and strip ends of the red (+), white (ground), and black (–) conductors. (If another wire color scheme is used, strip ends of appropriate wires.)

2.Secure the red (+) wire to CCN screw terminal + on the COMM board.

3.Secure the white (ground) wire to CCN screw terminal C on the COMM board.

4.Secure the black (–) wire to CCN screw terminal – on the COMM board.

5.Secure shield wire to CCN screw terminal SHIELD on the COMM board.

6.Connect the other end of the communication bus cable to the CCN communication bus.

Smoke Control Modes — Rooftop units can be used for aid in building smoke control in the event of a building fire. The available functions include: Fire Shutdown, Pressuriza- tion, Evacuation, and Smoke Purge. These functions are enhanced when multiple rooftop units are used to zone a build- ing. See Table 21 and Fig. 78 and 79.

FIRE SHUTDOWN — Fire Shutdown mode terminates all unit operation (cooling, heating, supply fan, and power exhaust). This mode prevents recirculation of contaminated air back into the space. The mode will not allow admission into the space of unsuitable outside air. See Fig. 78 for wiring.

PRESSURIZATION — Pressurization mode is intended to keep smoke out of a zone. The factory-installed optional econ- omizer is required for this function. Pressurization is accom- plished by the following:

opening the economizer (option)

running the supply fan (optional inlet guide vanes open or optional VFD at normal duct static pressure set point)

closing the power exhaust dampers (if installed as option or accessory)

shutting off the power exhaust fans (if installed as option or accessory)

This allows the space to be overpressurized relative to adja- cent zones and prevents or slows entry of smoke into this space from adjacent zones. See Fig. 79 for wiring.

EVACUATION — Evacuation mode removes smoke or un- desirable air from interior spaces without reintroducing unsuit- able air. The factory-installed optional economizer with option/ accessory power exhaust is required for this function. Evacua- tion is accomplished by the following:

turning the supply fan off

opening the economizer (option required)

running the exhaust fans (option or accessory required)

opening the exhaust dampers. See Fig. 79 for wiring.

SMOKE PURGE — Smoke Purge mode removes smoke from the interior spaces and replaces it with fresh outside air. The factory-installed optional economizer with option/ accessory power exhaust are required for this function. Smoke purge is accomplished by the following:

turning supply fan on

opening the economizer (option required)

running the exhaust fans (option or accessory required)

opening the exhaust dampers See Fig. 79 for wiring.

SMOKE CONTROL INSTALLATION — Implementation of the various smoke control modes on these units requires the in- staller to modify the unit wiring to add contacts (via either manual switches or relays) that will selectively interrupt and override standard factory control sequences. See Table 21 and Fig. 78 and 79 for more information.

Table 21 — Smoke Control Modes

 

 

MODE

 

FUNCTION

Fire

Pressur-

Evacuation*

Smoke

 

 

Shutdown

ization

 

Purge*

Supply Fan

Off

On

Off

On

IGV/VFD†

Open/On

Open/On

Economizer

Closed

Open

Open

Open

Return Air

Open

Closed

Closed

Closed

Damper

 

 

 

 

Exhaust

Off

Off

On

On

Fans

 

 

 

 

Exhaust

Closed

Closed

Open

Open

Damper

 

 

 

 

LEGEND

 

 

 

IGV — Inlet Guide Vane

 

 

 

PIC — Product Integrated Control

 

 

VAV — Variable Air Volume

 

 

VFD — Variable Frequency Drive

 

 

*Power exhaust option required for this mode. †Applicable to VAV and PIC units with appropriate options.

FIELD SUPPLIED THERMOSTAT

R

 

RC

Y1

Y2

W1

W2

G

 

 

 

 

Y1

Y2

W1

W2

G

R

 

 

1

 

 

6

5

4

3

2

 

 

 

 

TB203

 

 

 

Fig. 67 — Field Control Thermostat Wiring

T55- SPTT56- SPT

T1 T2

 

TH

C

SN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

3

 

5

 

7

 

9

 

11

 

13

 

15

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB202

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

4

 

6

 

8

 

10

 

12

 

14

 

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 68 — T55 or T56 Wiring

61

Image 61
Contents Installation Instructions Installation Base Unit Physical Data 48ZG,ZN030-050Alternate High-Capacity Evaporator Coil Base Unit Physical Data 48ZG,ZN055-070Base Unit Physical Data 48ZG,ZN075-105Outside AIR Screens Physical Data 48Z6,Z8075-105 RETURN/EXHAUST FAN Physical Data 48ZT,ZW075-105 Power Exhaust Operating Weights of Options and Accessories lbHigh-Capacity Power Exhaust Fan Drive Data 48ZT,ZW Units Power Exhaust Fan Drive DataSupply Fan Drive Data Return/Exhaust Fan Drive Data 48Z6,Z8 UnitsRoof Curb Sizes 055-105 Roof Curb Sizes 075-105 with High-Capacity Power Exhaust Condenser Section Roof Curb Size 055 and 060 Only Condenser Section Roof Curb Size 070-105 Only Condenser END Support Gasket Location on Roof Curb 48ZT,ZW075-105 Units Rigging Label Size 055-105 Units Standard Chassis Rigging Label Size 055,060 Units Extended Chassis Weight Distribution and Center of Gravity Page 24 → Page Page A48-8451 Page Page A48-8452 A48-8453 A48-8454 Install Outdoor Hoods 48ZG,ZN,Z6,Z8 Units Outdoor Air Hood Installation Sizes Install Economizer Hoods 48ZT,ZW Units Field Wire Routing Disconnect Location Size 030-050 Units Disconnect Location 48ZG,ZN055-105 and 48Z6,Z8075-105 Units Field Power Wiring Connections MCA Mocp FLA Electrical Data, 48ZG,ZN030 UnitsElectrical Data, 48ZG,ZN035 Units Electrical Data, 48ZG,ZN040 Units Electrical Data, 48ZG,ZN050 Units MCA Mocp FLA Electrical Data, 48ZG,ZN055 UnitsElectrical Data, 48ZG,ZN060 Units 460 Electrical Data, 48ZG,ZN070 UnitsElectrical Data 48ZG,ZN075-105 Units Electrical Data 48Z6,Z8075-105 Units Electrical Data 48ZT,ZW075-105 Units Indoor Evaporator Fan Motor Auxiliary Control Box Location Sizes Sizes Sizes 055-105 without Return Fan Auxiliary Control Box DetailsReturn/Exhaust-Fan Shipping Brackets 48Z6 Shipping Brackets Sizes Compressor Mounting 48Z Series Staged Gas Implementation Gas Piping DetailsFlue/Inlet Hood Locations, 030-060 Units Inlet Hood View Port Cover Installation Units Only Point SGC Thermistor DesignationsCCN Connection Approved Shielded Cables Smoke Control Modes Field Control Thermostat WiringSpace Temperature Averaging Wiring Heat Interlock Relay Wiring Fan Status Switch Wiring Return Air Smoke Detector Wiring CCN Connections Page Copyright 2009 Carrier Corporation
Related manuals
Manual 8 pages 37.42 Kb

Z6, 48ZG, 48ZT, ZW, Z8075-105 specifications

The Carrier Z8075-105, Z6, 48ZG, 48ZT, and ZW series of HVAC systems represent a significant advancement in heating, ventilation, and air conditioning technology. These units are specifically designed for enhanced energy efficiency, superior performance, and ultimate comfort in residential and commercial spaces.

The Carrier Z8075-105 model stands out due to its impressive cooling and heating capabilities. It features a high Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), allowing for reduced energy consumption and lower utility bills. This model is equipped with advanced inverter technology that enables variable speed operation, significantly reducing noise levels and providing consistent temperature control.

Turning to the Z6 model, it is engineered for both robustness and reliability. It incorporates a modular design that allows for easy installation and maintenance. One of its key features is the use of innovative insulation materials that minimize sound levels, making it ideal for noise-sensitive environments. Furthermore, the Z6 series comes with a smart control system that allows users to monitor and adjust settings remotely, further optimizing energy usage.

The 48ZG and 48ZT models are designed with durability in mind. They utilize a fully enclosed compressor system that protects critical components from environmental damage. These models also boast enhanced dehumidification capabilities, making them suitable for humid climates. Equipped with advanced filtration systems, they improve indoor air quality by removing allergens and particulates effectively.

Carrier's ZW series exemplifies cutting-edge technology with its dual fuel capability, which allows the system to switch between a heat pump and a gas furnace, depending on outdoor temperatures. This feature maximizes energy savings while ensuring a comfortable indoor climate year-round. The ZW models also support integration with smart home systems, providing seamless control through mobile apps.

Collectively, these Carrier models are designed to meet the diverse needs of today’s consumers, offering a blend of efficiency, comfort, and intelligent control. Their ability to adapt to various environmental conditions while maintaining optimal performance makes them a leading choice in the HVAC market. With a focus on sustainability, these systems not only offer significant energy savings but also contribute to reducing the carbon footprint. As technology continues to evolve, Carrier remains at the forefront, delivering reliable, innovative HVAC solutions.