Carrier 48ZG, ZN030-105, ZW, Z6, 48ZT, Z8075-105 installation instructions

Page 23

Condensate Drain Connections — There are a to- tal of five drain connections required on each unit: one primary drain (on right-hand side of the unit) and four secondary drains (two on each side of unit).

PRIMARY DRAIN — The primary drain is a 2-in. NPT pipe connection located on the right-hand side of the unit looking at the unit from the return air end. See Fig. 15-24.

With field-supplied fittings and pipe sections, plumb the pri- mary condensate drain to the 2-in. FPT connector on the base rail. Use a trap height of at least 4-in. for size 030-070 units and 7-in. for size 075-105 units. See Fig. 24 and 25. Install with a height dimension of at least 2-in. from the top of the exit pipe from the trap section to the bottom of the connector. Apply a bead of RTV or similar sealant around the pipe joint at the con- nector in the base rail.

SECONDARY DRAINS (Units Installed on Curb) — There are two secondary drain connections on each side of the unit. See Fig. 26. There are secondary drains on each side of the unit in the filter section and one on each side of the unit in the supply fan section. There are labels marking each location on the unit base rail. See Fig. 15-23.

Locate the four 11/4-in. drain coupling assemblies and mounting screws (shipped in a bag taped to the basepan in the supply fan section, located behind the access panel marked FAN SECTION). The drain couplings are a 10-gage plate with a 11/4 in. half coupling welded to the plate.

At each secondary drain hole location, there is a 13/8-in. hole pre-drilled in the bottom of the base rail, surrounded by four 0.20-in. engagement holes. Install a drain coupling assem- bly using screws provided at each secondary drain hole loca- tion. See Fig. 27. Do not attach any drain coupling assemblies in the condenser section base rail.

Using field-supplied fittings and pipe sections, assemble U- traps at each secondary drain fitting. See Fig. 28. Provide a minimum size of ½-in. pipe for secondary drains. Use a trap at least 4-in. deep for size 030-070 units and 7-in. deep for size 075-105 units. Apply a bead of RTV or similar sealant around the drain assemblies.

Consult local plumbing codes for direction on joining multi- ple drain lines. Total size of any combined line does not need to exceed nominal 2-in. size of primary drain connection.

Fill the U-traps at the secondary drain locations prior to unit start-up. Also check the U-traps before each cooling season to ensure the traps are filled and functioning properly.

SECONDARY DRAINS (Units Installed on Steel Beam or Slab) — There are two secondary drain connections required on each side of the unit. See Fig. 26. There are secondary drains on each side of the unit in the filter section and one on each side of the unit in the supply fan section. There are labels marking each location on the unit base rail. See Fig. 15-23. Pri- or to final positioning of the unit, apply a bead of RTV or simi- lar sealant around each secondary drain hole in the bottom of the unit base rail. Then position the unit into final location.

Locate the four 11/4-in. drain coupling assemblies and mounting screws (shipped in a bag taped to the basepan in the supply fan section, located behind the access panel marked FAN SECTION). The drain couplings are a 10-gage plate with a 11/4 in. half coupling welded to the plate.

After final positioning of the unit, perform the following procedure:

1.At each of the four secondary drain locations (marked with labels on the unit base rail), position the drain cou- pling assembly in the side of the base rail. Mark the screw holes and the drain hole locations on the base rail.

2.Drill holes for drain outlet (use 13/8-in. hole saw) and for the mounting screws (use 3/16-in. drill bit).

3.Install a drain coupling assembly using screws provided at each secondary drain hole location.

4.Using field-supplied fittings and pipe sections, assemble U-traps at each secondary drain fitting. See Fig. 28. Pro- vide minimum size of ½-in. pipe for secondary drains. Use a trap at least 4-in. deep for size 030-070 units and 7-in. deep for size 075-105 units.

5.Apply a bead of RTV or similar sealant around the drain assemblies.

Consult local plumbing codes for direction on joining multi- ple drain lines. Total size of any combined line does not need to exceed nominal 2-in. size of primary drain connection.

Fill the U-traps at the secondary drain locations prior to unit start-up. Also check the U-traps before each cooling season to ensure the traps are filled and functioning properly.

23

Image 23
Contents Installation Instructions Installation Base Unit Physical Data 48ZG,ZN030-050Alternate High-Capacity Evaporator Coil Base Unit Physical Data 48ZG,ZN055-070Base Unit Physical Data 48ZG,ZN075-105Outside AIR Screens Physical Data 48Z6,Z8075-105 RETURN/EXHAUST FAN Physical Data 48ZT,ZW075-105 Power Exhaust Operating Weights of Options and Accessories lbReturn/Exhaust Fan Drive Data 48Z6,Z8 Units Power Exhaust Fan Drive DataHigh-Capacity Power Exhaust Fan Drive Data 48ZT,ZW Units Supply Fan Drive DataRoof Curb Sizes 055-105 Roof Curb Sizes 075-105 with High-Capacity Power Exhaust Condenser Section Roof Curb Size 055 and 060 Only Condenser Section Roof Curb Size 070-105 Only Condenser END Support Gasket Location on Roof Curb 48ZT,ZW075-105 Units Rigging Label Size 055-105 Units Standard Chassis Rigging Label Size 055,060 Units Extended Chassis Weight Distribution and Center of Gravity Page 24 → Page Page A48-8451 Page Page A48-8452 A48-8453 A48-8454 Install Outdoor Hoods 48ZG,ZN,Z6,Z8 Units Outdoor Air Hood Installation Sizes Install Economizer Hoods 48ZT,ZW Units Field Wire Routing Disconnect Location Size 030-050 Units Disconnect Location 48ZG,ZN055-105 and 48Z6,Z8075-105 Units Field Power Wiring Connections MCA Mocp FLA Electrical Data, 48ZG,ZN030 UnitsElectrical Data, 48ZG,ZN035 Units Electrical Data, 48ZG,ZN040 Units Electrical Data, 48ZG,ZN050 Units MCA Mocp FLA Electrical Data, 48ZG,ZN055 UnitsElectrical Data, 48ZG,ZN060 Units 460 Electrical Data, 48ZG,ZN070 UnitsElectrical Data 48ZG,ZN075-105 Units Electrical Data 48Z6,Z8075-105 Units Electrical Data 48ZT,ZW075-105 Units Indoor Evaporator Fan Motor Auxiliary Control Box Location Sizes Sizes Sizes 055-105 without Return Fan Auxiliary Control Box DetailsReturn/Exhaust-Fan Shipping Brackets 48Z6 Shipping Brackets Sizes Compressor Mounting 48Z Series Staged Gas Implementation Gas Piping DetailsFlue/Inlet Hood Locations, 030-060 Units Inlet Hood View Port Cover Installation Units Only Point SGC Thermistor DesignationsCCN Connection Approved Shielded Cables Smoke Control Modes Field Control Thermostat WiringSpace Temperature Averaging Wiring Heat Interlock Relay Wiring Fan Status Switch Wiring Return Air Smoke Detector Wiring CCN Connections Page Copyright 2009 Carrier Corporation
Related manuals
Manual 8 pages 37.42 Kb

Z6, 48ZG, 48ZT, ZW, Z8075-105 specifications

The Carrier Z8075-105, Z6, 48ZG, 48ZT, and ZW series of HVAC systems represent a significant advancement in heating, ventilation, and air conditioning technology. These units are specifically designed for enhanced energy efficiency, superior performance, and ultimate comfort in residential and commercial spaces.

The Carrier Z8075-105 model stands out due to its impressive cooling and heating capabilities. It features a high Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), allowing for reduced energy consumption and lower utility bills. This model is equipped with advanced inverter technology that enables variable speed operation, significantly reducing noise levels and providing consistent temperature control.

Turning to the Z6 model, it is engineered for both robustness and reliability. It incorporates a modular design that allows for easy installation and maintenance. One of its key features is the use of innovative insulation materials that minimize sound levels, making it ideal for noise-sensitive environments. Furthermore, the Z6 series comes with a smart control system that allows users to monitor and adjust settings remotely, further optimizing energy usage.

The 48ZG and 48ZT models are designed with durability in mind. They utilize a fully enclosed compressor system that protects critical components from environmental damage. These models also boast enhanced dehumidification capabilities, making them suitable for humid climates. Equipped with advanced filtration systems, they improve indoor air quality by removing allergens and particulates effectively.

Carrier's ZW series exemplifies cutting-edge technology with its dual fuel capability, which allows the system to switch between a heat pump and a gas furnace, depending on outdoor temperatures. This feature maximizes energy savings while ensuring a comfortable indoor climate year-round. The ZW models also support integration with smart home systems, providing seamless control through mobile apps.

Collectively, these Carrier models are designed to meet the diverse needs of today’s consumers, offering a blend of efficiency, comfort, and intelligent control. Their ability to adapt to various environmental conditions while maintaining optimal performance makes them a leading choice in the HVAC market. With a focus on sustainability, these systems not only offer significant energy savings but also contribute to reducing the carbon footprint. As technology continues to evolve, Carrier remains at the forefront, delivering reliable, innovative HVAC solutions.