Therma-Stor Products Group 200 MAX Troubleshooting, Refrigerant Charging, Blower Replacement

Page 5

The mixture of gas and liquid refrigerant enter the accumulator after leaving the evaporator coil. The accumulator prevents any liquid refrigerant from reaching the compressor. The compressor evacuates the cool refrigerant gas from the accumulator and compresses it to a high pressure and temperature to repeat the process.

4.3 Troubleshooting

No dehumidification, neither blower nor compressor run and power switch does not light when ON.

1.Unit unplugged or no power to outlet.

2.Power switch defective (Sec. 2.6).

3.Loose connection in internal wiring (Fig. 3).

No dehumidification, neither blower nor compressor run with power switch ON & lit.

1.Low pressure control open (Sec. 2.10).

2.Power switch defective (Sec. 2.6).

3.Loose connection in internal wiring (Fig. 3).

Some dehumidification, blower runs continuously but compressor only runs sporadically.

1.Unit is in defrost cycle (Sec. 2.9 & 4.7).

2.Defrost thermostat defective or loose (Sec. 2.9 & 4.7).

3.Loose connection in compressor circuit (see Fig. 3).

4.Defective compressor overload (Sec. 4.6A).

5.Defective compressor (Sec. 4.6).

6.Defective relay (Sec. 4.10).

No dehumidification, blower runs but compressor does not.

1.Bad connection in compressor circuit (Fig. 3).

2.Pump safety switch closed

2.Defective compressor capacitor (Sec. 4.6A).

3.Defective compressor overload (Sec. 4.6A).

4.Defective compressor (Sec. 4.6).

5.Defective relay (Sec. 4.10).

Blower does not run. Compressor runs briefly but cycles on & off.

1.Loose connection in blower circuit (see Fig. 3).

2.Obstruction prevents impeller rotation.

3.Defective blower (Sec. 4.5).

Unit removes some water but not as much as expected.

1.Air temperature and/or humidity have dropped.

2.Humidity meter and/or thermometer used are out of calibration.

3.Unit has entered defrost cycle (Sec. 2.9 & 4.7).

4.Air filter dirty (Sec. 3.1).

5.Defrost timer incorrectly set for conditions (Sec. 2.9 & 4.7).

6.Defective defrost thermostat (Sec. 4.7)

7.Low refrigerant charge (Sec. 4.4).

8.Air leak such as loose front cover.

9.Defective compressor (Sec. 4.6).

10.Restrictive exhaust ducting (Sec. 2.5)

Unit runs but does not pump water.

1.Hose kinked or plugged.

2.Pump motor or float switch defective (Sec. 4.8).

3.Pump check valve plugged (Sec. 4.8).

4.Bad connection in pump circuit (Fig. 3).

5.Hose disconnected internally.

Unit pumps water automatically but not when purge switch is pushed.

1.Bad connection in purge switch circuit (Fig. 3).

2.Defective purge switch (Sec. 2.7).

Evaporator coil frosted continuously, low dehumidifying capacity.

1.Defrost thermostat loose or defective (Sec. 2.9 & 4.7).

2.Defrost timer incorrectly set or defective (Sec. 2.9 & 4.7).

2.Low refrigerant charge (Sec. 4.4).

3.Dirty air filter or air flow restricted. (Sec. 3.1).

Compressor runs with power switch OFF.

1.Defective relay (Sec. 4.10).

2.Defective power switch (Sec. 2.6)

4.4 Refrigerant Charging

If the refrigerant charge is lost due to service or a leak, a new charge must be accurately weighed in. If any of the old charge is left in the system, it must be removed before weighing in the new charge. Refer to the unit nameplate for the correct charge weight and refrigerant type.

4.5 Blower Replacement

The centrifugal blower has a PSC motor and internal thermal overload protection. If defective, the complete assembly must be replaced.

1.Unplug the power cord.

2.Remove the top panel and cabinet front (6 screws).

3.Disconnect the blower leads.

4.Remove the four screws holding the blower outlet flange to the cabinet end.

Toll-Free 1-800-533-7533

www.thermastor.com • sales@thermastor.com

Image 5
Contents Phoenix 200 MAX LGR High Capacity Dehumidifier Read and Save These InstructionsTable of Contents SpecificationsOperation Transporting the PhoenixDefrost Control Adjustment Power SwitchPump Purge Switch Electrical RequirementsService MaintenanceRefrigerant Charging TroubleshootingBlower Replacement Compressor/Capacitor Replacement Condensate Pump Defrost Thermostat and TimerGravity Drain Option RelayElectrical schematic of 200 MAX Wiring Diagram1613 Service PartsThis page intentionally left blank Toll-Free Phoenix 200 MAX Dehumidifier Limited Warranty

200 MAX specifications

The Therma-Stor Products Group 200 MAX is a state-of-the-art dehumidification solution designed to meet the rigorous demands of both residential and commercial environments. Renowned for its efficiency and durability, the 200 MAX stands out among its competitors with a suite of advanced technologies and features.

At the heart of the Therma-Stor 200 MAX is its powerful rotary compressor, engineered to provide maximum moisture removal capability while maintaining low energy consumption. This innovative compressor enables the unit to operate efficiently even in challenging conditions, making it an ideal choice for flood restoration and general dehumidification projects.

One of the standout characteristics of the 200 MAX is its impressive moisture removal rate. Capable of extracting substantial amounts of water from the air, this unit is suitable for spaces up to 6,000 square feet, effectively handling high humidity levels in basements, crawl spaces, and large commercial areas. Its ability to quickly create a drier environment helps prevent damage caused by mold and mildew, making it an essential tool for maintaining indoor air quality.

The 200 MAX incorporates a user-friendly digital control panel that allows for precise humidity and temperature adjustments. This intuitive interface not only simplifies operation but also provides real-time feedback on the unit's performance. Additionally, the integrated hygrometer helps monitor relative humidity levels, ensuring optimal performance and settings are maintained.

For ease of use, the Therma-Stor 200 MAX features a built-in pump, enabling continuous drainage of collected water without the need for manual intervention. This feature is particularly beneficial in areas where water disposal is challenging, as it eliminates the inconvenience of frequently emptying a collection tank.

Robust construction materials enhance the durability and longevity of the 200 MAX, making it suitable for demanding environments. Its compact and portable design, coupled with heavy-duty wheels, facilitates easy transportation and positioning in any space.

Moreover, the 200 MAX is designed with energy efficiency in mind, contributing to reduced operational costs. Its environmentally-friendly refrigerants align with modern energy standards, underscoring Therma-Stor's commitment to sustainable practices.

In summary, the Therma-Stor Products Group 200 MAX combines cutting-edge technology with practical features to deliver a superior dehumidification solution. Its powerful moisture removal, user-friendly controls, and energy-efficient design make it a leading choice for those seeking reliable performance in managing humidity levels. Whether for home use or commercial applications, the 200 MAX promises to create healthier, safer indoor environments.