Therma-Stor Products Group 200 MAX owner manual Maintenance, Service

Page 4

2.10 Low Pressure Control

If the low side refrigerant pressure drops to 15 PSIG, the low pressure control opens and shuts off the compressor and blower. It is an automatically reset control. Its primary function is to prevent damage to the compressor if a leak develops in the refrigeration system. It may also open if the unit is A) used in a cool area (below 50°F) and the defrost timer is not adjusted (see Sec. 2.9) or B) stored where it is below 40°F and then started. Under these conditions, the unit will restart within several minutes; it may cycle several times until the unit warms up.

3 Maintenance

3.1 Air Filter

The Phoenix 200 MAX is equipped with a pleated fabric air filter that must be checked regularly. The standard filter is a MERV-11 high efficiency filter. Operating the unit with a dirty filter will reduce the dehumidifier’s capacity and efficiency and may cause the compressor to cycle off and on unnecessarily on the defrost control.

The filter can generally be vacuumed clean several times before needing replacement. Replacement filters can be ordered from the factory or purchased locally if available. DO NOT operate the unit without the filter or with a less effective filter as the heat exchange coils inside the unit could become clogged and require disassembly to clean.

4 Service

CAUTION: Servicing the Phoenix 200 MAX with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death, serious bodily injury, and/or property damage. Only qualified service people should service this unit.

4.1 Warranty

A warranty certificate has been enclosed with this unit; read it before any repair is initiated. If a warranty repair is required, call the factory first at 1-800-533-7533 for warranty claim authorization and technical assistance.

4.2 Technical Description

The Phoenix 200 MAX uses a refrigeration system similar to an air conditioner’s to remove heat and moisture from incoming air, and to add heat to the air that is discharged (see Fig. 2).

3.2 Storage

There are two issues to consider when the Phoenix 200 MAX is stored between uses and both pertain to the water trapped in the unit: damage caused by freezing or biological growth. The effect of the trapped water can be greatly reduced if precautions are taken to remove as much as possible before storage.

1.Use the pump purge switch (see Sec. 2.7 & Fig. 4) to reduce the water level in the reservoir.

2.Stretch the hose flat to drain it completely. Walk under out of the hose to open end.

If the unit will not be exposed to freezing temperatures, an alternative to reduce biological growth is to flush the unit with a bio-fungicide that is approved for use with copper, aluminum and polyethylene. To flush:

1.Run the hose to a drain.

2.Plug in the unit but do not turn it on.

3.Remove the air filter. Slowly pour a quart of the chemical through the heat exchanger

4.Hold in the pump purge switch to reduce the water level in the reservoir.

5.Flush with water.

Figure 2: Refrigeration system of Phoenix

Hot, high pressure refrigerant gas is routed from the compressor to the condenser coil (see Figure 2). The refrigerant is cooled and condensed by giving up its heat to the air that is about to be discharged from the unit. The refrigerant liquid then passes through a filter/drier and capillary tubing which cause the refrigerant pressure and temperature to drop. It next enters the evaporator coil where it absorbs heat from the incoming air and evaporates.

The evaporator operates in a flooded condition, which means that all the evaporator tubes contain liquid refrigerant during normal operation. A flooded evaporator should maintain constant pressure and temperature across the entire coil, from inlet to outlet.

Toll-Free 1-800-533-7533

www.thermastor.com • sales@thermastor.com

Image 4
Contents Read and Save These Instructions Phoenix 200 MAX LGR High Capacity DehumidifierSpecifications Table of ContentsOperation Transporting the PhoenixPower Switch Defrost Control AdjustmentPump Purge Switch Electrical RequirementsMaintenance ServiceBlower Replacement TroubleshootingRefrigerant Charging Compressor/Capacitor Replacement Defrost Thermostat and Timer Condensate PumpGravity Drain Option RelayWiring Diagram Electrical schematic of 200 MAXService Parts 1613This page intentionally left blank Toll-Free Phoenix 200 MAX Dehumidifier Limited Warranty

200 MAX specifications

The Therma-Stor Products Group 200 MAX is a state-of-the-art dehumidification solution designed to meet the rigorous demands of both residential and commercial environments. Renowned for its efficiency and durability, the 200 MAX stands out among its competitors with a suite of advanced technologies and features.

At the heart of the Therma-Stor 200 MAX is its powerful rotary compressor, engineered to provide maximum moisture removal capability while maintaining low energy consumption. This innovative compressor enables the unit to operate efficiently even in challenging conditions, making it an ideal choice for flood restoration and general dehumidification projects.

One of the standout characteristics of the 200 MAX is its impressive moisture removal rate. Capable of extracting substantial amounts of water from the air, this unit is suitable for spaces up to 6,000 square feet, effectively handling high humidity levels in basements, crawl spaces, and large commercial areas. Its ability to quickly create a drier environment helps prevent damage caused by mold and mildew, making it an essential tool for maintaining indoor air quality.

The 200 MAX incorporates a user-friendly digital control panel that allows for precise humidity and temperature adjustments. This intuitive interface not only simplifies operation but also provides real-time feedback on the unit's performance. Additionally, the integrated hygrometer helps monitor relative humidity levels, ensuring optimal performance and settings are maintained.

For ease of use, the Therma-Stor 200 MAX features a built-in pump, enabling continuous drainage of collected water without the need for manual intervention. This feature is particularly beneficial in areas where water disposal is challenging, as it eliminates the inconvenience of frequently emptying a collection tank.

Robust construction materials enhance the durability and longevity of the 200 MAX, making it suitable for demanding environments. Its compact and portable design, coupled with heavy-duty wheels, facilitates easy transportation and positioning in any space.

Moreover, the 200 MAX is designed with energy efficiency in mind, contributing to reduced operational costs. Its environmentally-friendly refrigerants align with modern energy standards, underscoring Therma-Stor's commitment to sustainable practices.

In summary, the Therma-Stor Products Group 200 MAX combines cutting-edge technology with practical features to deliver a superior dehumidification solution. Its powerful moisture removal, user-friendly controls, and energy-efficient design make it a leading choice for those seeking reliable performance in managing humidity levels. Whether for home use or commercial applications, the 200 MAX promises to create healthier, safer indoor environments.