F-Horizontal Venting-Residential Two Pipes

1-For horizontal residential installations these units are certified as Category I appliances. The vent may be single wall material minimum 25 GSG (0.46mm) galvanized steel or equivalent grade stainless steel or a single section of type B-1 vent installed according to the sections Venting A-General Recommendations and Requirements and C-Horizontal Venting General and F-HorizontalVenting–Residential Two Pipes. Refer to figure 6.

2-The vent pipe diameter for horizontal residential installations shall be 4” (100mm) on 45 units and 5” (127mm) on 60/75/100/125 units. Refer to table 4 for vent diameter and termination requirements.

3-The maximum vent length is 5’ (1.5m) plus one 90- degree elbow.

4-The vent must maintain a ¼” rise per foot of slope upwards toward the termination

TABLE 4

HORIZONTAL VENT REQUIREMENTS

MODEL

INSTALLATION

FLUE TYPE

FLUE DIA.

VENT CAP

MAX. VENT

 

 

AIR INLET TYPE

INLET AIR

INLET AIR CAP

LENGTH (MIN.

 

 

 

DIA.

 

VENT LENGTH 3’)

45

RESIDENTIAL

SINGLE WALL

4”

TEE or

5’ MAY USE ONE

 

 

 

 

4” BELMONT

SECTION OF

 

 

SINGLE WALL PIPE or

3”

TEE or

B-VENT

 

 

METAL FLEX VENT

 

3” BELMONT

 

45

RESIDENTIAL

CONCENTRIC

4”

4” CONCENTRIC

5’

 

 

SINGLE WALL PIPE or

3”

VENT/ ADAPTER/CAP

 

 

 

METAL FLEX VENT

 

KIT REQUIRED

 

45

COMMERCIAL

SINGLE WALL

3”

TEE or

25’ MAY USE ONE

 

 

 

 

3” BELMONT

SECTION OF

 

 

SINGLE WALL PIPE or

3”

TEE or

B-VENT

 

 

METAL FLEX VENT

 

3” BELMONT

 

45

COMMERCIAL

CONCENTRIC

3”

4” CONCENTRIC

25’

 

 

SINGLE WALL PIPE or

3”

VENT/ ADAPTER/CAP

 

 

 

METAL FLEX VENT

 

KIT REQUIRED

 

60, 75

RESIDENTIAL

SINGLE WALL

5”

TEE or

5’ MAY USE ONE

 

 

 

 

5” BELMONT

SECTION OF

 

 

SINGLE WALL PIPE or

4”

TEE or

B-VENT

 

 

METAL FLEX VENT

 

4” BELMONT

 

60, 75

RESIDENTIAL

CONCENTRIC

4”

4” CONCENTRIC

5’

 

 

SINGLE WALL PIPE or

4”

VENT/ ADAPTER/CAP

 

 

 

METAL FLEX VENT

 

KIT REQUIRED

 

60, 75

COMMERCIAL

SINGLE WALL

4”

TEE or

25’ MAY USE ONE

 

 

 

 

4” BELMONT

SECTION OF B-

 

 

SINGLE WALL PIPE or

4”

TEE or

VENT

 

 

METAL FLEX VENT

 

4” BELMONT

 

60, 75

COMMERCIAL

CONCENTRIC

4”

4” CONCENTRIC

25’

 

 

SINGLE WALL PIPE or

4”

VENT/ ADAPTER/CAP

 

 

 

METAL FLEX VENT

 

KIT REQUIRED

 

100, 125

RESIDENTIAL

SINGLE WALL

5”

TEE or

5’ MAY USE ONE

 

 

 

 

5” BELMONT

SECTION OF

 

 

SINGLE WALL PIPE or

4”

TEE or

B-VENT

 

 

METAL FLEX VENT

 

4” BELMONT

 

100, 125

COMMERCIAL

SINGLE WALL

5”

TEE or

5’ MAY USE ONE

 

 

 

 

5” BELMONT

SECTION OF

 

 

SINGLE WALL PIPE or

4”

TEE or

B-VENT

 

 

METAL FLEX VENT

 

4” BELMONT

 

Page 10

Image 11
Contents TUA*SN,LA,SF Table Of Contents45, 60, and 75 Unit Dimensions Unit Clearances 125 Unit DimensionsRequirements CSA in Canada ShippingRequirements CSA in the USA Combustion and Ventilation Air Unit Heater InstallationVenting and Combustion Air Inlet Horizontal Venting-Commercial Vent and AIR Intake Termination on Single Wall VentHorizontal Venting General Recommendations and Requirements. In areas Condensate Drain Through TEE Pipe and Drain LoopGeneral Recommendations RequirementsCondensate Drain Through Vent Termination Vertical Vent Requirements Horizontal Venting Residential InstallationHorizontal Vent Requirements Horizontal Venting-Residential Two PipesRemoval Of Unit From Common Vent Horizontal Venting Concentric Vent InstallationHorizontal Venting Concentric Kit Residential Electrical Connections Line Voltage Field WiringGAS Supply to Unit Heater GAS Supply Connection Gas ConnectionLeak Check Operation for Honeywell VR8205 Series Gas Valve Figure Unit Start-UpAttempt to light the burners manually White Rodgers 36E GAS ValveRobertshaw 2000DER GAS Valve To light the burners manuallyOptional Gas Conversion Kit To Turn Off Gas To UnitHeating Sequence of Operation Ignition Control LEDLimit Control Louver Vane AdjustmentCombustion Air Inducer Proving Switch Flame Rollout SwitchGas Flow Rate Ft.3/Hr Gas FlowLP/PROPANE GAS Manifold Pressures in.wg. kPa Combustion Air Blower Repair PartsBurners Flue Passageway and Flue BoxTUA45/60/75/100/125SN,LA,SF

TUA45S, T-CLASS TM SEPARATED COMBUSTION UNIT HEATERS, TUA75S, TUA100S, TUA60S specifications

Lennox International Inc. stands out as a leader in the heating and cooling industry, and its T-Class™ Separated Combustion Unit Heaters, including models such as TUA60S, TUA100S, TUA125S, and TUA45S, epitomize innovation and efficiency. These unit heaters are engineered to provide reliable warmth in commercial and industrial environments, ensuring comfort and productivity even in the coldest conditions.

One of the most significant features of the T-Class™ heaters is their separated combustion design. This technology allows the heater to draw air for combustion from outside the building, which means that interior air remains untouched and is not used for heating. This design not only improves indoor air quality but also enhances energy efficiency by minimizing heat loss.

The TUA60S, with a heating capacity of 60,000 BTUs, is ideal for smaller spaces, while the TUA100S provides a robust 100,000 BTUs, making it suitable for medium-sized areas. For larger installations, the TUA125S delivers a powerful 125,000 BTUs, ensuring even the most expansive environments remain comfortably warm. Lastly, the TUA45S is perfect for smaller facilities or specific zones requiring efficient heating solutions.

These heaters are equipped with advanced technology such as modulating burners that adjust the heat output based on the current temperature needs, leading to energy savings and reduced operational costs. The T-Class™ units are designed with reliable components, ensuring longevity and reducing maintenance requirements. Additionally, the exterior reflects a modern and durable finish, ensuring they withstand the rigors of industrial settings.

Installation is straightforward thanks to their flexible configurations, allowing for both vertical and horizontal venting options. This adaptability makes them suitable for various applications, from warehouses to manufacturing plants.

In terms of safety, Lennox emphasizes top-tier mechanisms, including built-in safety limits and high-temperature shutoff features to prevent overheating. Furthermore, their models are compliant with industry regulations, reflecting Lennox International's commitment to safety and environmental stewardship.

In conclusion, Lennox International Inc.’s T-Class™ Separated Combustion Unit Heaters, including the TUA60S, TUA100S, TUA125S, and TUA45S, offer a blend of efficiency, reliability, and advanced technology. These heaters are suitable for a variety of commercial and industrial applications, ensuring optimal comfort while prioritizing safety and energy savings.