Roberts Gorden CRV-B-8, CRV-B-6 Pump Capacity, Tailpipe Flow, Pump Exhaust Length Requirements

Page 20

CRV-SERIES DESIGN MANUAL

5.2 Pump Capacity

The flow unit capacity of the pump is indicated on Page 14, Table 2, as a function of installed altitude. When the CRV-Series system is designed in accor- dance with this set of instructions and is in proper operating condition, a vacuum from 2-3" w.c. will be obtainable at each end vent (i.e. at all burners).

Table 2: Pump Capacity

Installed Altitude

Maximum Flow Units

 

 

 

 

 

Feet Above

Meters Above

EP-100

EP-200

EP-300

Sea Level

Sea Level

Series

Series

 

 

 

 

 

 

0' - 2000'

0 m - 609 m

66

112

224

 

 

 

 

 

2001' - 3000'

610 m - 914 m

63

105

215

 

 

 

 

 

3001' - 4000'

915 m - 1219 m

60

100

206

 

 

 

 

 

4001' - 5000'

1220 m - 1524 m

57

95

197

 

 

 

 

 

5001' - 6000'

1525 m - 1828 m

54

90

188

 

 

 

 

 

6001' - 7000'

1829 m - 2134 m

51

84

180

 

 

 

 

 

7001' - 8000'

2135 m - 2438 m

48

80

170

 

 

 

 

 

8001' - 9000'

2439 m - 2743 m

45

75

161

 

 

 

 

 

There are a number of design requirements which, if not met, will reduce the vacuum obtainable and thereby the effective flow capacity of the pump. These include:

Minimum Length of Tailpipe - If less than the minimum length of tailpipe is provided per radiant branch, there will be insufficient cooling of the com- bustion gases and improper operation of the pump.

Line Loss Check for Tailpipe is applicable to sections of tailpipe which are common to two or more radiant branches (i.e. shared lengths). See Page 14, Figure 15.

Excessive back pressure on discharge line of pump can be caused by partial blockage or too much flow for length. See Section 5.3.1

More than maximum number of burners or flow units per radiant branch. See Page 14, Table 2.

Excessive number of elbow or tee fittings which increases vacuum loss.

5.3 Tailpipe Flow

Excessive flow loading in a single section of tailpipe can cause low vacuum and lower effective pump capacity. For the pump to develop the proper vacuum, the length of tailpipe must not be excessive for the

number of flow units carried in the tube.

See Figure 15. Readings for length and flow when plotted on the graph must fall on OK side to avoid excessive vacuum losses.

FIGURE 15: Vacuum Loss Curve for 4" Shared

Tailpipe

 

130

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOT

OK

 

 

 

 

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(feet)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Section

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

SIDE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tailpipeof

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Length

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

40

50

60

70

80

90

100

110 120

 

Maximum Flow Units per Single Tailpipe Section

NOTE: For 6" (15 m) tailpipe, length is limited to a maximum of 100’ (30 m). See Page 16, Section 6.3 for more details.

Lengths shown include allowance for 1 elbow every 50' (15 m); deduct 15% of length for each additional elbow used per 50' (15 m) length.

5.3.1 Pump Exhaust Length Requirements

The tube length on the exhaust side of the pump is considered excessive if not within the following condi- tions:

Table 3: Pump Exhaust Requirements

Pump Series

Exhaust Tube Length

Exhaust Tube Diameter

 

 

 

EP-100

Up to 25' (7.6 m)

4" 3 Elbows

 

 

 

EP-100

Up to 50' (15 m)

5" 3 Elbows

 

 

 

EP-200

Up to 10' (3 m)

4" 0 Elbows

 

 

 

EP-200

Up to 25' (7.6 m)

5" 3 Elbows

 

 

 

EP-200

Up to 50' (15 m)

6" 3 Elbows

 

 

 

EP-300

Up to 10' (3 m)

6" 1 Elbows

 

 

 

EP-300

Up to 25' (7.6 m)

7" 3 Elbows

 

 

 

EP-300

Up to 50' (15 m)

8" 3 Elbows

 

 

 

14

Image 20
Contents Design Manual Page Roberts-Gordon LLC Page Table of Figures Page Concept Zero Regulator SafetyCRV-SERIES System Assembly Overview Two Branch System Shown Fuel Savings and Comfort Clearances to combustibles at all times for safety Standard Reflector ONE Side ReflectorUniversal SHIELD, Position Foot Deco Grille Radiant Adjustment to Heat Loss Radiant Height Adjustment FactorSizing and Design Considerations ExampleSelecting the Burners Radiant DistributionRadiant Distribution Average Coverage Radiant Distribution Increased Coverage= mounting height Flow Loading Radiant Branch FlowBurner Flow Units Pump Exhaust Length Requirements Pump CapacityTailpipe Flow Radiant Tube and Tailpipe Radiant Tube LengthMinimum Radiant Tube Length Maximum Radiant Tube LengthDesign Parameters Pump Model Series Maximum LoadingCRV-Series Design Methods Flow Units Per BranchAfter Each Burner Allowable Tailpipe Lengths Burner ModelTailpipe Design Method Rule of Thumb Unshared CalculationsSystem with EP-300 Series Pump To Calculate the Total System TailpipeDamper Couplings Possible Damper Coupling Locations Example CRV-SERIES System Layouts Example System Layout Option12 m 10 3 m 20 6 m 12 m Tailpipe 10 3 m 100 30 m Example System Layout Option 7, 8 Roberts Gordon Ultravac Control MethodsRoberts Gordon System Control P/N Pressure Switch AIR Supply System PressurizedNon-Pressurized Pressurized SystemsBlower P/N 90707501 Performance 112 Flow Units Pipe sizingDuct Design Rules Sample Layout for Pressurized Outside Air Systems Roberts Gordon Ultravac Design Requirements CRV-SERIES Equipment Specifications Page Maintain Clearance Side Clearance below
Related manuals
Manual 72 pages 5.13 Kb

CRV-B-4, CRV-B-2, CRV-B-6, CRV-B-8 specifications

Roberts Gorden is renowned for its innovative heating solutions, particularly the CRV series of infrared radiant heaters, which include models CRV-B-2, CRV-B-4, CRV-B-6, and CRV-B-8. These heaters are designed to provide effective and efficient heating, making them ideal for various industrial, commercial, and agricultural applications.

One of the standout features of the Roberts Gorden CRV series is its advanced infrared heating technology. Unlike conventional heating systems that heat the air, infrared heaters warm objects and people directly, allowing for a more energy-efficient and comfortable environment. This makes the CRV series particularly effective in large spaces, such as warehouses, manufacturing facilities, and greenhouses.

The CRV-B models are engineered for versatility and can be mounted in various configurations, including horizontal and vertical placements, providing installation flexibility. Each model is available in different sizes and heating outputs, ensuring that users can select a unit tailored to their specific heating requirements. The CRV-B-2, for instance, is ideal for smaller spaces, while the CRV-B-8 offers higher power for larger areas.

Moreover, these heaters come equipped with advanced control systems that allow for precise temperature regulation. The units can be integrated with building management systems, enabling users to monitor and adjust settings remotely. This feature not only enhances comfort but also contributes to energy savings, as the heaters can be programmed to operate only during necessary hours.

Structural durability is another significant characteristic of the CRV series. Constructed with high-quality materials, the heaters are designed to withstand the rigors of industrial environments while maintaining optimal performance over time. The reflective surfaces enhance heat distribution, ensuring that warmth is evenly distributed throughout the space.

Safety is paramount with Roberts Gorden’s CRV heaters. They are designed with built-in safety mechanisms, including overheat protection and automatic shut-off features to prevent accidents.

Overall, the Roberts Gorden CRV-B-2, CRV-B-4, CRV-B-6, and CRV-B-8 models exemplify cutting-edge infrared heating technology, delivering effective, efficient, and reliable heating solutions tailored to diverse applications. With a combination of flexibility, advanced control capabilities, and safety features, these heaters are an excellent choice for anyone in need of powerful heating solutions.