Heat & Glo LifeStyle 8000CMOD-IPI Vent Clearances and Framing, Pipe Clearances to Combustibles

Page 32

8 Vent Clearances and Framing

A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance to vent. DO NOT pack insulation or other combustibles:

Between ceiling firestops

Between wall shield firestops

Around vent system

Failure to keep insulation or other material away from vent pipe may cause over heating and fire.

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

‡DVP heat shield - designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick.

‡,f wall thickness is less than 4 in. the e[isting heat shields must be field trimmed. ,f wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required.

‡SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8 in. (111 mm to 194 mm thick).

‡,f wall thickness is less than 4-3/8 the e[isting heat shields must be field trimmed. ,f wall thickness is greater than 7-5/8 in. a DVP-HSM-B will be required.

(DVP-SLP Pipe Shown)

B. Wall Penetration Framing

Combustible Wall Penetration

Whenever a combustible wall is penetrated, you must frame a hole for the wall shield firestop(s). The wall shield firestop maintains minimum clearances and prevents cold air infiltration.

The opening must be framed on all four sides using the same size framing materials as those used in the wall construction.

SLP pipe - A wall shield firestop must be placed on each side of an interior wall. A minimum 1-1/2 in. (38 mm) overlap of attached heat shields must be maintained.

DVP pipe - A wall shield firestop is required on one side only on interior walls. If your local inspector requires a wall shield firestop on both sides, then both wall shield firestops must have a heat shield (refer to Section 16.B.) attached to them.

See Section 10.L for information for regarding the in- stallation of a horizontal termination cap.

3 in. (76 mm) top clearance

1 in. (25 mm) clearance around vertical sections

Heat

3 in. (76 mm)

Shield

top clearance *

 

Heat

 

Shield

 

1 in. (25 mm)

Wall

clearance

Shield

bottom & sides

Firestop

 

 

WALL

Non-Combustible Wall Penetration

If the hole being penetrated is surrounded by noncom- bustible materials such as concrete, a hole with diameter one inch greater than the pipe is acceptable.

Whenever a non-combustible wall is penetrated, the wall shield firestop is only required on one side and no heat shield is necessary.

*When using SLP or SL-D pipe, minimum clearances from the vent pipe to combus- tible materials at inside wall firestops are: Top: 2-1/2 in. (64 mm)

Bottom: 1/2 in. (13 mm)

Sides: 1 in. (25 mm)

Figure 8.1 Horizontal Venting Clearances To Combustible Materials

10 in. 12 in.

A*

B

 

 

A*

B

6000

in.

42-3/4

41-3/4

mm

1086

1060

 

8000

in.

44-3/4

44-1/8

mm

1137

1111

 

*Shows center of vent framing hole for top or rear venting. The center of the hole is one (1) in. (25.4 mm) above the center of the horizontal vent pipe.

Figure 8.2 Wall Penetration

32

Heat & Glo • 6000CMOD-IPI, 8000CMOD-IPI2241-900 Rev. H • 5/12

Image 32
Contents Hot glass will cause burns What to do if you smell gasHOT Surfaces Congratulations Homeowner Reference InformationTable of Contents User GuideAppliance Setup TroubleshootingFinishing Reference MaterialsLimited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions Listing and Code Approvals Non-Combustible Materials SpecificationCombustible Materials Specification Electrical CodesInstallation of Carbon Monoxide Detectors Requirements for the Commonwealth of MassachusettsYour Fireplace Gas Fireplace SafetyOperating Instructions User Guide Fixed Glass Assembly Remote Controls, Wall Controls and Wall SwitchesFan Kit optional Clear SpaceIPI Battery Tray/Battery Installation Module ResetNine Hour Safety Shutdown Feature Control Module OperationLighting Instructions IPI Final inspection byWhat to do if YOU Smell GAS GAS ValveAfter Fireplace is Lit Frequently Asked QuestionsIssue Solutions Maintenance and Service Interior Ceramic Glass Panel Cleaning FireboxControl Compartment and Firebox Top Burner Ignition and OperationAppearance MAY VaryBurner Identification 6000CMOD-IPI NG6000CMOD-IPI LP 8000CMOD-IPI NGGetting Started Typical Appliance SystemDesign and Installation Considerations Tools and Supplies NeededInspect Appliance and Components Any such action may cause a fire hazardFraming and Clearances Selecting Appliance Location6000 8000Constructing the Appliance Chase Clearances6000 8000Combustible Mantel Legs or Wall Projections Mantel and Wall ProjectionsCombustible Mantels Termination Locations Vent Termination Minimum ClearancesCovered Alcove Applications Inches U.S.AVent Information and Diagrams Approved PipeVent Table Key Use of ElbowsVent Diagrams Top Vent Horizontal Termination One Elbow6000CMOD-IPI 8000CMOD-IPITwo Elbows V1 Minimum H1 + H2 MaximumTop Vent Horizontal Termination Three Elbows Min MaxBreak Here Top Vent Vertical Termination Maximum + V 2 MinTop Vent Vertical Termination Three Elbows H1 + H2 V1 + V2 Minimum H1 + H2 MaximumVent Clearances and Framing Pipe Clearances to CombustiblesWall Penetration Framing Combustible Wall PenetrationInstall the Ceiling Firestop Pipe DVP SLPInstall Attic Insulation Shield Installing the Optional Heat-ZoneGas KitFlat Ceiling Installation Vaulted Ceiling InstallationAppliance Preparation Top VentHeader Installing the Non-combustible BoardSecuring and Leveling the Appliance Installing Vent Pipe DVP and SLP Pipe Attach Vent to the Firebox AssemblyAssemble Vent Sections DVP Pipe Only Assemble Pipe SectionsAssemble Vent Sections SLP Pipe Only Assemble Slip SectionsSecure the Vent Sections Disassemble Vent SectionsInstall Decorative Ceiling Components SLP only Install Metal Roof Flashing Assemble and Install Storm CollarHeat Shield Requirements for Horizontal Termination Install Vertical Termination CapInstall Decorative Wall Components SLP only Install Horizontal Termination Cap DVP and SLP Pipe DVP-HPC1 DVP-HPC2High Altitude Installations Gas InformationFuel Conversion Gas PressureWiring Requirements IntelliFire PlusTM Ignition System WiringOptional Accessories Requirements Electrical InformationElectrical Service and Repair Junction Box Installation Wall Switch Installation for Fan OptionalFinishing Facing Material Finish and Sealing JointsFinishing Around Opening with Gypsum Wallboard PaintingCmod Door Application Door SelectionFolio Door Application NON-COMBUSTIBLE Finishing Material Finishing Material Inch Thick or Less Overlap Fit MethodDoor FIT Finish Material See Thickness Finishing Material Inches Inside Fit Method ModelsAppliance Setup Media Placement Remove ScrewBurner Install Trim and/or Surround Air Shutter SettingAir Shutter Settings Fully OpenIntelliFire PlusTM Ignition System TroubleshootingSymptom Possible Cause Corrective Action Troubleshooting Location Inches Millimeters Appliance Dimension DiagramReference Materials GAS Line Access R Left Side TOP View Front View Right View Vent Components Diagrams DVP-AS2DVP-TRAP Horizontal Termination CapRF6M RF12M BEK DVP-BEK2DVP-TRAPFL COOL-ADDDVP-TVHW Optional Wire Harness DVP-HRC-SS DVP-HRC-ZC-SS Horizontal Termination CAPPVI-SLP SLP-LPC222 mm 165 mm 165 mm9-1/4 235 mm 152 mm 168 mm Elbow251 mm Effective Height LengthSLP-DCF-BK SLP-WT-BK SLK-SNKD SLP-CCS-BK SLP-TVHWDVP-2SL DVP-HSM-B Service Parts StockedAt Depot Modern Direct Vent Fireplace8000CMOD-IPI #12 Valve Assembly 8000CMOD-IPIService Parts List Battery Pack 2166-323Contact Information

6000CMOD-IPI, 8000CMOD-IPI specifications

The Heat & Glo LifeStyle 6000CMOD-IPI and 8000CMOD-IPI models represent the pinnacle of modern fireplace design, marrying aesthetics with advanced technology to create a unique heating experience. These versatile, linear gas fireplaces are designed to seamlessly integrate into any living space while offering exceptional performance and style.

One of the standout features of the LifeStyle series is its impressive heating efficiency. Both models utilize advanced heating technology to maximize warmth while minimizing energy consumption. The innovative IPI (Intermittent Pilot Ignition) system enhances efficiency by using a pilot light only when the fireplace is in use, ensuring that energy costs remain low.

The design of the LifeStyle series is both contemporary and customizable. Homeowners have the option to choose from various finishes, media styles, and decorative elements. The large, expansive viewing area enhances the ambiance of any room, showcasing the mesmerizing flames. The 6000CMOD-IPI with its 60-inch firebox and the 8000CMOD-IPI with an 80-inch firebox add a dramatic focal point to any setting.

Another significant innovation incorporated in these models is the use of advanced flame technology. This feature allows for an adjustable flame height, providing flexibility in terms of heat output and visual effects. Users can tailor the flames to suit mood and occasion, whether they desire a cozy ambiance for a quiet evening or a more robust heat output for entertaining.

The user-friendly controls add to the convenience of the LifeStyle series. Homeowners can easily operate the fireplace with a remote control or smart home integration, enabling adjustments from the comfort of their seating. Additionally, the fireplaces come equipped with a safety shut-off feature, providing peace of mind while enhancing user safety.

Maintenance is simplified with the LifeStyle series as well. The design minimizes creosote buildup and offers easy access for cleaning. The contemporary linear design also allows for easy installation, making it an appealing choice for both new builds and renovations.

In summary, the Heat & Glo LifeStyle 6000CMOD-IPI and 8000CMOD-IPI models combine cutting-edge heating technology, elegant design, and user-friendly features. These fireplaces not only serve as a source of comfort but also enhance the aesthetic appeal of any living space, making them a valuable addition for homeowners looking to elevate their interiors with warmth and style.