Heat & Glo LifeStyle 8000CMOD-IPI Install Attic Insulation Shield, Flat Ceiling Installation

Page 34

D. Install Attic Insulation Shield

WARNING! Fire Risk. DO NOT allow loose materials or insulation to touch vent. Hearth & Home Technologies Inc. requires the use of an attic shield.

The National Fuel Gas Code ANSI Z223.1 and NFPA 54 requires an attic shield constructed of 26 gauge minimum metal that extends at least 2 in. (51 mm) above insulation.

Attic shields must meet specified clearance and be se- cured in place.

Flat Ceiling Installation

• Remove one shield from box.

NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.

Wrap shield around pipe if pipe is already installed in

 

area to be insulated.

Match the three holes in each side and fasten with three

 

screws to form a tube.

Bend three tabs on the bottom of the shield outward to

 

allow attachment to the ceiling firestop.

Bend the remaining bottom tabs inward 90º to maintain

 

the air space between the pipe and the shield. Set the

BEND ALL TABS INWARD 90° TO MAINTAIN CLEARANCE AND PREVENT INSULATION FROM FALLING INSIDE

INSERT 3

SCREWS

Figure 8.5 Attic Insulation Shield

BEND 3 TABS

OUTWARD TO FASTEN TO CEILING FIRESTOP-BEND REMAINING TABS INWARD 90 DEGREES TO MAINTAIN CLEARANCE

shield on the ceiling firestop and attach to the firestop.

• Bend all tabs inward 90º around the top of the shield.

These tabs must be used to prevent blown insulation

from getting between the shield and vent pipe, and to

maintain air space clearance.

Vaulted Ceiling Installation

• Remove one shield from box.

NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.

Cut the attic insulation shield (if application is for vaulted ceiling) to fit your ceiling pitch. Snip cut edge to recreate 1 in. bend tabs all the way around the bottom.

Wrap shield around pipe if pipe is already installed in area to be insulated.

Match the three holes in each side and fasten with three screws to form a tube.

Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling firestop.

Bend the remaining bottom tabs inward 90º to maintain the air space between the pipe and the shield. Set the shield on the ceiling firestop and attach to the firestop.

Bend all tabs inward 90º around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance.

E. Installing the Optional Heat-Zone®Gas Kit

Remove the knockout from the fireplace and discard it (see Figure 8.6).

Center the duct collar around the exposed hole and attach it to the fireplace with 3 screws. Note: Do this BEFORE final positioning of fireplace.

Determine the location for the air register/fan housing assembly.

Reference the Heat-Zone®Gas kit instructions for the remaining installation steps.

HEAT-ZONE® GAS

ATTACHES HERE

Figure 8.6 Heat Zone Cover Plate

34

Heat & Glo • 6000CMOD-IPI, 8000CMOD-IPI2241-900 Rev. H • 5/12

Image 34
Contents HOT Surfaces What to do if you smell gasHot glass will cause burns Congratulations Homeowner Reference InformationTable of Contents User GuideFinishing Appliance SetupTroubleshooting Reference MaterialsLimited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions Combustible Materials Specification Listing and Code ApprovalsNon-Combustible Materials Specification Electrical CodesInstallation of Carbon Monoxide Detectors Requirements for the Commonwealth of MassachusettsOperating Instructions User Guide Gas Fireplace SafetyYour Fireplace Fan Kit optional Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Clear SpaceNine Hour Safety Shutdown Feature IPI Battery Tray/Battery InstallationModule Reset Control Module OperationWhat to do if YOU Smell GAS Lighting Instructions IPIFinal inspection by GAS ValveIssue Solutions Frequently Asked QuestionsAfter Fireplace is Lit Maintenance and Service Control Compartment and Firebox Top Interior Ceramic Glass Panel CleaningFirebox Burner Ignition and OperationAppearance MAY Vary6000CMOD-IPI LP Burner Identification6000CMOD-IPI NG 8000CMOD-IPI NGGetting Started Typical Appliance SystemInspect Appliance and Components Design and Installation ConsiderationsTools and Supplies Needed Any such action may cause a fire hazard6000 Framing and ClearancesSelecting Appliance Location 80006000 Constructing the Appliance ChaseClearances 8000Combustible Mantels Mantel and Wall ProjectionsCombustible Mantel Legs or Wall Projections Termination Locations Vent Termination Minimum ClearancesCovered Alcove Applications Inches U.S.AVent Table Key Vent Information and DiagramsApproved Pipe Use of Elbows6000CMOD-IPI Vent Diagrams Top Vent Horizontal TerminationOne Elbow 8000CMOD-IPITwo Elbows V1 Minimum H1 + H2 MaximumTop Vent Horizontal Termination Three Elbows Min MaxBreak Here Top Vent Vertical Termination Maximum + V 2 MinTop Vent Vertical Termination Three Elbows H1 + H2 V1 + V2 Minimum H1 + H2 MaximumWall Penetration Framing Vent Clearances and FramingPipe Clearances to Combustibles Combustible Wall PenetrationInstall the Ceiling Firestop Pipe DVP SLPFlat Ceiling Installation Install Attic Insulation ShieldInstalling the Optional Heat-ZoneGas Kit Vaulted Ceiling InstallationAppliance Preparation Top VentSecuring and Leveling the Appliance Installing the Non-combustible BoardHeader Assemble Vent Sections DVP Pipe Only Installing Vent Pipe DVP and SLP PipeAttach Vent to the Firebox Assembly Assemble Pipe SectionsAssemble Vent Sections SLP Pipe Only Assemble Slip SectionsSecure the Vent Sections Disassemble Vent SectionsInstall Decorative Ceiling Components SLP only Install Metal Roof Flashing Assemble and Install Storm CollarInstall Decorative Wall Components SLP only Install Vertical Termination CapHeat Shield Requirements for Horizontal Termination Install Horizontal Termination Cap DVP and SLP Pipe DVP-HPC1 DVP-HPC2Fuel Conversion High Altitude InstallationsGas Information Gas PressureOptional Accessories Requirements Wiring RequirementsIntelliFire PlusTM Ignition System Wiring Electrical InformationElectrical Service and Repair Junction Box Installation Wall Switch Installation for Fan OptionalFinishing Finishing Around Opening with Gypsum Wallboard Facing MaterialFinish and Sealing Joints PaintingFolio Door Application Door SelectionCmod Door Application Door FIT Finish Material See Thickness Finishing Material Inch Thick or Less Overlap Fit MethodNON-COMBUSTIBLE Finishing Material Finishing Material Inches Inside Fit Method ModelsAppliance Setup Media Placement Remove ScrewBurner Air Shutter Settings Install Trim and/or SurroundAir Shutter Setting Fully OpenSymptom Possible Cause Corrective Action TroubleshootingIntelliFire PlusTM Ignition System Troubleshooting Reference Materials Appliance Dimension DiagramLocation Inches Millimeters GAS Line Access R Left Side TOP View Front View Right View Vent Components Diagrams DVP-AS2DVP-TRAP Horizontal Termination CapDVP-TRAPFL RF6M RF12MBEK DVP-BEK2 COOL-ADDDVP-TVHW PVI-SLP Optional Wire HarnessDVP-HRC-SS DVP-HRC-ZC-SS Horizontal Termination CAP SLP-LPC251 mm 222 mm 165 mm 165 mm9-1/4 235 mm 152 mm 168 mmElbow Effective Height LengthDVP-2SL DVP-HSM-B SLK-SNKD SLP-CCS-BK SLP-TVHWSLP-DCF-BK SLP-WT-BK At Depot Service PartsStocked Modern Direct Vent Fireplace8000CMOD-IPI #12 Valve Assembly 8000CMOD-IPIService Parts List Battery Pack 2166-323Contact Information

6000CMOD-IPI, 8000CMOD-IPI specifications

The Heat & Glo LifeStyle 6000CMOD-IPI and 8000CMOD-IPI models represent the pinnacle of modern fireplace design, marrying aesthetics with advanced technology to create a unique heating experience. These versatile, linear gas fireplaces are designed to seamlessly integrate into any living space while offering exceptional performance and style.

One of the standout features of the LifeStyle series is its impressive heating efficiency. Both models utilize advanced heating technology to maximize warmth while minimizing energy consumption. The innovative IPI (Intermittent Pilot Ignition) system enhances efficiency by using a pilot light only when the fireplace is in use, ensuring that energy costs remain low.

The design of the LifeStyle series is both contemporary and customizable. Homeowners have the option to choose from various finishes, media styles, and decorative elements. The large, expansive viewing area enhances the ambiance of any room, showcasing the mesmerizing flames. The 6000CMOD-IPI with its 60-inch firebox and the 8000CMOD-IPI with an 80-inch firebox add a dramatic focal point to any setting.

Another significant innovation incorporated in these models is the use of advanced flame technology. This feature allows for an adjustable flame height, providing flexibility in terms of heat output and visual effects. Users can tailor the flames to suit mood and occasion, whether they desire a cozy ambiance for a quiet evening or a more robust heat output for entertaining.

The user-friendly controls add to the convenience of the LifeStyle series. Homeowners can easily operate the fireplace with a remote control or smart home integration, enabling adjustments from the comfort of their seating. Additionally, the fireplaces come equipped with a safety shut-off feature, providing peace of mind while enhancing user safety.

Maintenance is simplified with the LifeStyle series as well. The design minimizes creosote buildup and offers easy access for cleaning. The contemporary linear design also allows for easy installation, making it an appealing choice for both new builds and renovations.

In summary, the Heat & Glo LifeStyle 6000CMOD-IPI and 8000CMOD-IPI models combine cutting-edge heating technology, elegant design, and user-friendly features. These fireplaces not only serve as a source of comfort but also enhance the aesthetic appeal of any living space, making them a valuable addition for homeowners looking to elevate their interiors with warmth and style.