(long cycles), you may want to adjust the anticipation setting.
!CAUTION
A cooling anticipation setting of less than 10 may cause decreased compressor life.
To adjust heat anticipation, press CLOCKSET and
DAYSET at the same time. The display will show
HEAT 5 (this is the factory preprogrammed heating anticipation setting). You may se- lect any anticipation setting from 2 to 40 (note that for hydronic systems, a mini- mum anticipation setting of 15 is recom- mended). Whenever adjusting anticipation, increase or decrease the displayed number by only one or two digits, then let the system run for a while to see if the adjustment is
sufficient. If the heat cycles are too short,
press TIMEFWD to increase the cycle time. If the
heat cycles are too long, press BACKTIME to de-
crease the cycle time. To set cooling antici-
pation, press CLOCKSET and DAYSET at the same time
again. The display will show COOL 14 (fac- tory preprogrammed cooling anticipation). You may select any anticipation setting from
4 to 40. Use | TIMEFWD | and BACKTIME to adjust anticipa- |
tion. Press | PRGMRUN | to return to your program. |
•LOW BATTERY INDICATOR — The word BATTERY will flash on the display if the “AA” alkaline batteries are low and should be replaced. The word BATTERY will be displayed continuously
16