Heart & Home Collectables MHR36, MHC36 manual Chimney Requirements, Sidewalls/Surrounds

Page 11

MHC36 AND MHR36 INSTALLATION INSTRUCTIONS

3.Sidewalls/Surrounds

Adjacent combustible side walls must be located a minimum of 12 in. from the fireplace opening. See Figure 6. If you are using a decorative surround constructed of combustible material, it must be located within the shaded area defined in Figure 6. Short stub walls are also acceptable if they are contained within the shaded area.

Figure 6 - Sidewalls and Surrounds

E. CHIMNEY REQUIREMENTS

When planning your fireplace location, the chimney construction and necessary clearances must be considered. The fireplace system and chimney components have been tested to provide flexibility in construction. The following figures are the minimum distances from the base of the fireplace.

1.

Minimum overall straight height

14.5 ft

2.

Minimum height with offset/return

14.5 ft

3.

Maximum height

90 ft

4.

Maximum chimney length between an offset and return

20 ft

5.

Maximum distance between chimney stabilizers

35 ft

6.

Double offset/return minimum height

20 ft

7.

Maximum unsupported chimney length between the offset and return

6 ft

8.

Maximum straight unsupported chimney height above the fireplace

25 ft

08/04

31072 Rev G

11

Image 11
Contents Installation & Operating Instructions Table of Contents Design and Installation Considerations Optional Components Include Listings and Code ApprovalsDescription of the Fireplace System Heatilator fireplace system consists of the followingFireplace Components System ComponentsAS8 Chimney ComponentsAS8 Fireplace Locations and Space Requirements PRE-INSTALLATION PreparationMHC36 and MHR36 Installation Instructions Framing the Fireplace Frame the FireplaceSidewalls/Surrounds Chimney RequirementsOffset Chart Using Offsets and ReturnsNumber of Sections Required Chimney Height Requirements above roof lineLevel the Fireplace Fireplace InstallationPosition the Fireplace Place the Protective Metal Hearth StripsAssemble Chimney Sections Install the Firestop SpacersSecure the Chimney System Double-check the Chimney AssemblyAttic Insulation Shield See Figures 14 MH842 Ceiling/Roof ThimbleTermination Cap Install the Outside Air KitGas Log/Lighter Provisions Complete the EnclosureField Constructed Hearth Extension Hearth ExtensionGlass Doors Position the Hearth ExtensionFinishing Material MantelFlue Damper Operating InstructionsGeneral Information Outside Air Wood Fuel GrateFirescreen Starting a Fire Draft ProblemsFlue Draft Creosote and Soot Maintenance InstructionsChimney Cleaning Disposal of AshesIndex Heatilator Woodburning Fireplace Limited WarrantyReplacement Parts Advantage How to Obtain Service